42 WHC/WHE
GB - 5
E N G L I S H
Table III: Operating limits
Minimum entering water temperature: 6
°
C
Water circuit
Water- side maximum pressure
Maximum entering water temperature: 60
°
C
1400 kPa (142 m Water Gauge)
Maximum entering water temperature
with electric heaters: 45
°
C
Indoor temperature
Minimum temperature: 5
°
C
(1)
Maximum temperature: 32
°
C
Power supply
Nominal single-phase voltage
230V ~ 50Hz - min. 198V - max. 264V
Ref.
Description
Q.ty
Use
Unit
1
Installation manual
1
Unit installation
Hanging panel / valve kit
1
Unit installation
1
Screw anchors and screws
4 + 4
Fixing the hanging panel to the wall
2
Control
1
Selecting the ambient temperature
3
Screw anchors and screws
2+2
Control installation
4
Screw
1
Safety screw
Minimum clearances (mm)
20
20
80
Table II: Material supplied
(1)
If the outdoor temperature can go down to 0
°
C, it is advisable to empty the water circuit to avoid breaks caused by ice (see paragraph on water
connections).