INSTALLATION MANUAL

Summary of Contents for 42VQV050

Page 1: ...42VQV Console Underceiling T h e S t andards Institutiono f I s r a e l Q u ality Assured Fi r m SI ISO 9001 INSTALLATION MANUAL...

Page 2: ...anuals supplied with the remote controls The operation and maintenance instructions for the indoor unit and the installation instructions for the indoor and the outdoor unit are given in the manuals f...

Page 3: ...to the outdoor unit installation instructions Dimensions mm and weights Minimum clearances Wall installation Ceiling installation B A 80 D C 50 min 500 min 50 min 42VQV050 080 050 080 050 080 42VQV 05...

Page 4: ...llation manual Outoor unit Indoor unit Height difference 1 The accessories have not been awarded IMQ certification Description Part number Condensate discharge 42VKG9002 pump 220 240V 50Hz Cable cover...

Page 5: ...r s outdoor unit Coupling units which have different control systems may cause irreversible damage and void the warranty protection The manufacturer declines any liability for system malfunction resul...

Page 6: ...ause condensate dripping flattening or kinking the refrigerant pipes or condensate pipes excessive height difference between outdoor and indoor units see installation manual of outdoor unit unnecessar...

Page 7: ...connections to the outdoor unit can be concealed For better operation of the thermostat located on the unit it is advisable to avoid unit installation in enclosed spaces There are three alternatives f...

Page 8: ...n For exit to the rear the wall hole must be made in the position shown in the illustration Drill a 70 or 80 mm diameter hole The hole must have a 5 10 mm downward slope towards the outside Insert the...

Page 9: ...g diameter Model Gas Liquid 42VQV Suction Discharge mm inches mm inches 050 12 70 1 2 6 35 1 4 080 15 87 5 8 9 52 3 8 For refrigerant tubes use seamless insulated refrigeration grade tube Cu DHP type...

Page 10: ...hat mains supply connection is made through a switch that disconnects all poles with contact gap of a least 3 mm The indoor outdoor unit connecting wires must be A07 RN F type 245 IEC 57 or higher wit...

Page 11: ...ller Press the and buttons of the infrared remote control and hold them pressed for more than 5 seconds The display will be cleared the temperature segments will display the first configuration item C...

Page 12: ...e it OFF Energise the system turning the power supply ON Fault code operating test and guide for the owner Press the and buttons of the infrared remote control and hold them pressed for more than 5 se...

Page 13: ...m the room is drawn into the unit through the grilles and filter at the bottom of the unit No draught guide vane fully open position recommended for ceiling installation in cooling mode to avoid draug...

Page 14: ...ensate dripping the manufacturer will not be held responsible for any damage caused The supplementary fan motor for outside air intake has to be supplied separately and controlled by a bipolar ON OFF...

Page 15: ...26H17 0604 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice June 2004 Supersedes April 2004 Printed in Is...