background image

4.5 - Constant-volume fresh air controller

4.5.1 - Constant-volume fresh air controller

The 42BJ ICM can be fitted with a constant fresh air flow controller 

allowing the introduction of fresh air and the air change rate to be 

controlled. 
The following range of fresh air controllers is available:

Option a: 

8.3 l/s (30 m

3

/h) (-10%; +20%)

Option b:

 16.6-44.4 l/s (60-160 m

3

/h) (-10%; +20%) 

Options a and b: 

the diameter of the spigot housing the fresh air 

flow controller is 125 mm.
The 16.6 1/s (60 m

3

/h) fresh air controller may be modified on site 

by relocating or removing two plastic restrictors in order to increase 

the maximum constant fresh air flow capacity to 44.4 1/s (160 

m

3

/h). A label on the 42BJ ICM shows how to adjust the two plastic 

restrictors (Fig. 11).
Modification procedure

 

-

Disconnect the fresh air duct from the spigot on the unit.

 

-

Remove or reposition the two plastic restrictors, following the 

fresh air flow controller.

 

-

Reconnect the fresh air duct to the spigot.

IMPORTANT:  If  the  42BJ  ICM  is  fitted  with  a  return  air 

temperature sensor, the constant fresh air flow rate must not 

exceed 50% of the supply air flow delivered by the unit at 

minimum speed.

NOTE: To operate correctly, the 8.3 l/s (30 m

3

/h) constant fresh 

air flow controller requires a differential pressure in the range 

50 Pa to 200 Pa. The 16.6 l/s (60 m

3

/h) constant fresh air 

controller requires a differential pressure in the range 70 to 

200 Pa.

4.5.2 - Fresh air controller with variable air volume

The 42BJ ICM can be equipped with an optional variable fresh air 

flow controller from 0 to 55 l/s (0 to 200 m

3

/h).

This is connected to the numeric Carrier controller and can regulate 

the fresh air intake in two ways:

 

-

either  using  a  fixed  rate  set  by  the  installer  that  can  be 

reconfigured as required

 

-

or based on the CO

2

 level; in this case it is connected to a 

CO

2

 sensor via the Carrier numeric controller.

NOTE: With the variable fresh air flow controller the upstream 

pressure in the fresh air duct must be 180 Pa.

4.6 - 

Optional water flow control valves

These valves are two-way or three-way type, with a body designed 

to withstand a 16 bar operating pressure.

4.6.1 - 

Thermoelectric actuator (on/off)

The actuator is a 230 V a.c. on/off type.

NOTE: The thermoelectric actuator is supplied in the normally 

closed position for both the two- and the three-way valve (way 

A-AB closed for a three-way valve).

To enable the installation to be filled with water, the water circuits 

to be equalised and the units to be purged, the actuators must be 

connected to the power supply to open the valves via a command 

from the wall thermostats or from the BMS.

4.6.2 - Actuator replacement procedure

The actuators on both the chilled water and the hot water valves 

may be replaced if either develops a fault.

 

-

Disconnect the power supply to the unit before carrying out 

any work on a unit.

 

-

Disconnect the actuator power supply cable equipped with 

a quick connector.

 

-

Uncouple the faulty actuator. Refitting is by the reversal of 

the procedure described above.

WARNING: Ensure that the actuator is firmly screwed to the 

valve body (maximum torque 15 N·m).

4.6.3 - Valve body replacement procedure

 

-

Disconnect the power supply before carrying out any work 

on a unit.

 

-

Close the isolating valves on the manifolds.

 

-

Unscrew the union nuts to disconnect the flexible water pipes.

 

-

Remove the valve actuators taking care to identify the cooling 

and heating valves.

 

-

Remove the two-way or three-way water flow control valve 

bodies. Depending how the unit is configured, the three-way 

valve  coupling  may  be  fitted  with  a  heating/cooling 

changeover switch, if so do not remove it.

 

-

Fit the new valve body to the coil (fit new gaskets).

 

-

Refit the valve actuators taking care to ensure that they are 

correctly fixed to the valve body.

 

-

Reconnect the flexible water pipes by tightening the union 

nuts. Retighten all the water connections and ensure that all 

gaskets have been changed and correctly fitted (maximum 

torque 15 N·m).

 

-

Open the isolating valves on the manifolds and purge all air 

from the system.

 

-

Check that there are no leaks and reconnect the power to 

the unit.

WARNING: When replacing a valve always ensure that the 

direction of flow through the valve is as shown by the arrow 

on the valve body. If the direction of flow is wrong, the valve 

body will deteriorate rapidly.

4.7 - Replacing the electric heater (Fig. 13)

CAUTION: It is vital to disconnect the ICM from the general 

power supply before carrying out any work on the electric 

heater.

If  the  electric  heater  develops  a  fault,  the  assembly  must  be 

removed and replaced; the fan unit will have to be removed to 

make this possible.
a)  Refer to the fan removal procedure.
b)  Remove  the  support  assembly  and  the  electric  heater  by 

removing the two screws.

c)  Disconnect the electric heater cable (3 wires terminating in flat 

spade connectors).

d)  Release the heater mounting and remove the heater.
e)  Replace the defective heater.
f)  Use the above procedure in reverse to install the new heater 

and to reinstall the fan motor assembly.

WARNING

 

-

Do not touch the heater elements when the heater is 

switched on.

 

-

Do not touch the fan wheel during the removal and re-

assembly process.

4 - COMPONENTS

12

Summary of Contents for 42BJ ULTRA

Page 1: ...I N S TA L L AT I O N I N S T R U C T I O N S Original document INDIVIDUAL COMFORT MODULE FOR VARIABLE AIR VOLUME SYSTEMS 42BJ MCI LEC Sizes 1 9 2 9 4 9 ...

Page 2: ...2 ...

Page 3: ...n conditions 9 2 4 Caution for the control of the 42BJ ICM LEC 9 2 5 Regulations 9 3 INSTALLATION OF THE UNIT 10 3 1 Installing the unit in the false ceiling 10 3 2 Installation procedure 10 3 3 Remocal procedure 10 4 COMPONENTS 11 4 1 Fan motor assembly 11 4 2 Water coil 11 4 3 Duct connection spigots 11 4 4 Optional air filter and filter access air filter replacement 11 4 5 Constant volume fresh...

Page 4: ...B C D E F G H I 4 ...

Page 5: ...m m 50 mm l s m3 h A B MR60 17 60 4 4 4 4 MR75 21 75 4 3 4 3 MR85 24 85 3 3 3 2 MR90 25 90 3 2 2 2 MR100 28 100 2 1 2 1 MR105 29 105 2 1 1 1 MR110 31 110 1 1 1 1 MR120 33 120 3 3 MR130 36 130 2 1 MR140 39 140 1 1 MR160 44 160 L M N O 5 ...

Page 6: ... A 2 wV In Out In Out Cold Hot Ø 16 61 75 75 10 5 4 Ø 1 2 gas 25 82 5 69 188 A 3 wV In 42BJ A 1 9 151 mm 2 9 190 mm 42BJ MCI LEC 4 9 Out Ø 16 75 61 4 Ø 1 2 gas 163 5 192 225 69 2 wV In In Out Cold Hot Out Ø 16 75 61 4 Ø 1 2 gas 163 5 192 62 5 69 3 wV In In Out Cold Hot 6 ...

Page 7: ...g device for installation in a false ceiling H I Levelling the unit J Condensate drain pipe K Several units connected to one condensate collector L Fresh air controller modification M Fan motor assembly removal 12a Door 12b Locking screw 12C Fan fixing screw N Electric heater removal O Underfloor installation P Coil water inlet outlet positions sizes 1 9 and 4 9 In Water in Out Water out Hot Hot w...

Page 8: ...acteria and chemicals in order to avoid problems due to corrosion and scaling The water circuit must include all the necessary elements for the treatment of the water filters additives intermediate exchangers purges drains isolating valves etc according to the analysis results The results must be in accordance with the values shown below Total hardness in mmol l 1 mmol l 1 5 Chloride CL 10 mg litre...

Page 9: ...rown green yellow and its cross section and type must comply with the specifications set out by the applicable EN or IEC standard Refer to the selection sheet or the name plate to determine the maximum input current These devices are not supplied by Carrier In general terms the following rules must be applied Upstream over voltage protection Unit without electric heater T2A Unit with electric heat...

Page 10: ... over the whole horizontal pipe run Install a 50 mm minimum siphon to prevent gases and odours from flowing back into the ceiling void If several units are connected to a common collector a device must be installed Fig 10 Before operating the unit ensure that the water flows into the internal condensate drain pan by pouring some water into it If problems are detected check the drain pipe slope and l...

Page 11: ...d all air from the coil during refilling ATTENTION It is advisable to tighten the valve body to the coils with caution 15 N m is sufficient to ensure they are not damaged 4 2 2 Coil inlet outlet positions Fig 15 Water inlets outlets sizes 1 9 2 9 Water inlets outlets size 4 9 ATTENTION Carefully observe the direction indicated by the arrow on the valves based on the connection side and the valve typ...

Page 12: ...e actuators must be connected to the power supply to open the valves via a command from the wall thermostats or from the BMS 4 6 2 Actuator replacement procedure The actuators on both the chilled water and the hot water valves may be replaced if either develops a fault Disconnect the power supply to the unit before carrying out any work on a unit Disconnect the actuator power supply cable equipped...

Page 13: ...umeric controller 4 10 Adjustable feet accessories for installation in a false floor void 4 10 1 Introduction An ICM may be installed in a floor void Adjustable feet with built in vibration absorbers are available as accessories for installation on site For further information please contact your local Carrier representative 4 10 2 Procedure for fitting see Figs 14 and 15 a Install angle bracket 1 u...

Page 14: ... high pressure PTC 4 wired stages Digit 14 F F5 access from below G F5 side access H F5 access from above K F6 access from below L F6 side access M F6 access from above S Activated carbon filters UVPCO access from below T Activated carbon filters UVPCO side access U Activated carbon filters UVPCO access from above Digit 15 None A 125 mm Ø fresh air spigot only B 8 3 l s 30 m3 h C 16 6 44 4 l s 21 ...

Page 15: ...15 ...

Page 16: ...7 2021 replaces No 14281 11 2011 The manufacturer reserves the right to modify the product specifications without prior notice Manufacturer Carrier S C S Rte de Thil 01120 Montluel France Printed in the European Union ...

Reviews: