System Fan Coil Unit

HVAC Guide Specifications

Size Range: 

800 to 4000 Nominal Cfm

Carrier Model Number: 

42BHC

Part 1 — General

1.01 SYSTEM DESCRIPTION

Horizontal, 2-pipe or 4-pipe, belt-driven, galvanized
casing model fan coil unit for ducted installation
above the ceiling, with full access to internal
components.

1.02 QUALITY ASSURANCE

Each coil shall be factory tested for leakage at
350 psig air pressure with coil submerged in water.
Insulation and adhesive shall meet NFPA-90A
requirements for flame spread and smoke genera-
tion. Factory-installed motors shall be UL approved.

1.03 DELIVERY, STORAGE AND HANDLING

Unit shall be handled and stored in accordance with
the manufacturer’s instructions.

Part 2 — Products

2.01 EQUIPMENT

A. General:

Factory-assembled, horizontal, draw-thru type fan
coil unit for ducted installation above the ceiling.
Unit shall be complete with water coils, fan(s),
motor, belt drive, drain pan, and filter.

B. Casing:

Construction shall be heavy-gage galvanized steel,
lined with one-in. thick fiberglass Tuf-Skin™ II
thermal/acoustical insulation. Knockouts shall be
provided for hanging the unit, that will accept 

3

/

8

-in.

threaded rod at the top, and bottom of all unit cor-
ners. Supply and return duct connection shall be
one inch long. Removable side panels shall be pro-
vided for access to the fan/motor assembly. A
double-sloped drain pan shall be constructed of
stainless steel, extending under the full length and
width of the coil(s) with a 

3

/

4

-in. male nominal pipe

thread stainless steel drain connection and 

1

/

2

-in.

male MPT stainless secondary drain connection
(capped when not required). The outside surface of
the drain pan shall be insulated with 

1

/

8

-in. closed

cell insulation.

C. Fans:

Belt-driven, double-width fan wheels shall have
forward-curved blades and be statically and dynami-
cally balanced. Fan drive shall consist of variable-
pitch motor pulley, fixed-pitch fan pulley and V-belt.
Fans and scrolls shall be of galvanized steel.

D. Coils:

Standard unit shall be equipped with a 4-row coil for
installation in a 2-pipe system and additional rows of
coil shall be provided for installation in a 4-pipe sys-
tem as described in the Special Features section.
Coils shall have 

1

/

2

-in. copper tubes, aluminum fins

bonded to the tubes by mechanical expansion and
have a working pressure of 250 psig at 200 F. Each
coil shall have a manual air vent and sweat connec-
tions for copper tubes.

E. Operating Characteristics:

A single-circuit coil unit installed in a 2-pipe system
shall be capable of providing heating or cooling as
determined by the operating mode of the central
water supply system. A double-circuit coil unit
installed in a 4-pipe system shall be capable of pro-
viding sequenced heating and cooling.

F. Motor(s):

Fan motors shall be open, drip-proof, single-speed,
60 Hz, 1750 rpm single or 3-phase, suitable for
continuous duty at 104 F (40 C). Single-phase
motors are capacitor start, include automatic reset
thermal overload protection and are available in
115, 208, 230, or 277 volts (60 Hz). Three-phase
motors are available in 208, 230, or 460 volts
(60 Hz). Motors are resilient base mounted (except
3 hp motors which are rigid base mounted).

G. Electric Heat:

Electric heaters are available on the 42BHC units.
The heater shall be constructed of high-grade resis-
tance wire supported by ceramic insulators on plated
steel brackets. These heat elements are suspended
in front of the outlet, after the blower and coil. High-
limit thermal cutouts shall protect the heat elements
in the event of an air failure.

H. Special Features:

Certain standard features are not applicable when the
features designated by * are specified. See your local
Carrier Sales Office for amending specifications.

* 1. Coils:

a. Unit coil(s) shall be equipped with automatic

air vent(s).

b. Unit shall be equipped with a high-capacity

6-row or 8-row coil for installation in a
2-pipe system. 

c. For installation in a 4-pipe system, unit shall

be equipped with either a 4-row cooling/
1-row hot water heating split-circuit coil, or
a 4/2, 6/1, or 6/2 split-circuit coil as
required.

Guide specifications

Summary of Contents for 42BHC08

Page 1: ... 6 or 8 row cooling coils combine the capacities you need with the most efficient heat transfer surface For 4 pipe systems select either of two split coil options Coils consist of alu minum fins securely bonded to 1 2 in OD seamless copper tubes Each fin s aluminum collar ensures accurate con trol of the fin spacing while complete ly covering the tubes to lengthen coil life All coils also feature ...

Page 2: ...smission The stainless steel double sloped condensate drain pan extends under full coil surface to cut maintenance costs Slide in return duct collar filter makes it possible to remove and replace the filter without disturbing return air ductwork Coil Rows B 4 2 Pipe L 6 2 Pipe H 4 1 Same End Conn K 4 2 Same End Conn N 6 1 Same End Conn Q 6 2 Same End Conn R 8 2 Pipe 1 4 With Electric Heat 2 6 With...

Page 3: ...08 v 230 v and 277 v single phase 60 Hz 208 v 230 v and 480 v three phase 60 Hz Electric heat is available with the following staging options 3 phase staging is balanced 1 to 4 kW 1 stage only single phase 5 to 12 kW 1 or 2 stage only single phase 1 to 12 kW 1 stage only 3 phase 15 to 20 kW 1 or 2 stage only 3 phase 25 to 40 kW 1 2 or 3 stage 3 phase Heater coils are constructed of high grade resi...

Page 4: ...actory Product specifications are subject to change without notice 2 All dimensions are in inches 1 4 in 3 RH shown LH opposite 4 Hanger rods which are field supplied are shown for reference only UNIT 42BHC DIMENSIONS in A B C D E F G H J K L 08 2811 16 363 16 181 2 85 8 109 16 137 8 241 16 167 16 273 16 351 4 11 8 12 371 16 373 4 201 4 10 1111 16 137 8 331 16 183 16 363 16 3613 16 11 8 16 471 16 ...

Page 5: ...ry Product specifications are subject to change without notice 2 All dimensions are in inches 1 4 in 3 RH shown LH opposite 4 Hanger rods which are field supplied are shown for reference only UNIT 42BHC DIMENSIONS in A B C D E F G H J K L 08 2811 16 363 16 181 2 85 8 109 16 137 8 241 16 167 16 273 16 351 4 11 8 12 371 16 373 4 201 4 10 1111 16 137 8 331 16 133 16 363 16 3613 16 11 8 16 471 16 3715...

Page 6: ...factory Product specifications are subject to change without notice 2 All dimensions are in inches 1 4 in 3 RH shown LH opposite 4 Hanger rods which are field supplied are shown for reference only UNIT 42BHC DIMENSIONS in A B C D E F G H J K L M N 08 2811 16 363 16 181 2 85 8 109 16 137 8 241 16 167 16 273 16 351 4 1 11 8 61 4 12 371 16 373 4 201 4 10 1111 16 137 8 331 16 133 16 363 16 3613 16 1 1...

Page 7: ... 47 52 55 51 52 47 205 With Heat 52 61 62 71 61 52 71 62 246 12 No Heat 64 72 56 64 72 64 64 56 256 With Heat 65 79 71 85 79 65 85 71 300 16 No Heat 80 87 69 76 87 80 76 69 312 With Heat 81 94 84 97 94 81 97 84 356 20 No Heat 90 98 74 82 98 90 82 74 344 With Heat 92 105 90 103 105 92 103 90 390 30 No Heat 118 127 92 100 127 118 100 92 437 With Heat 120 134 108 122 134 120 122 108 484 40 No Heat 15...

Page 8: ... Factor and Water Flow Rate table on page 18 From the Cv Factor by Coil and Unit Size table on page 17 find the Cv value for unit size 16 with four rows Cv 7 2 P GPM 0 658 x Cv 2 7 0 0 658 x 7 2 2 2 18 feet of H2O b For selections other than those listed here please contact the factory IV Determine motor and drive To determine motor and drive selection requirements and obtain the cfm for a specifi...

Page 9: ... 00 1 00 1 00 0 95 0 97 0 97 0 90 0 94 0 93 0 85 0 90 0 89 0 80 0 86 0 85 0 75 0 82 0 81 0 70 0 78 0 77 0 65 0 74 0 72 0 60 0 70 0 67 0 55 0 66 0 62 0 50 0 62 0 57 0 45 0 58 0 52 0 40 0 53 0 47 0 35 0 48 0 42 0 30 0 43 0 38 0 25 0 38 0 33 OF NOMINAL CFM CORRECTION FACTOR Total Sensible 80 0 95 0 93 90 0 97 0 96 100 1 00 1 00 110 1 02 1 04 120 1 05 1 08 ELEVATION ft TOTAL HEAT Et SENSIBLE HEAT Es 1...

Page 10: ... 20 9 45 23 2 18 1 50 17 7 15 5 6 40 40 7 26 2 45 32 2 22 6 50 24 4 19 3 8 40 46 8 29 3 45 38 0 25 3 50 29 1 21 5 12 1200 4 40 47 8 32 5 45 37 7 28 2 50 28 8 24 4 6 40 62 5 40 0 45 50 2 34 6 50 38 2 29 6 8 40 71 5 44 5 45 58 2 38 4 50 44 7 32 7 16 1600 4 40 63 2 43 1 45 49 4 37 3 50 37 9 32 3 6 40 83 2 53 3 45 66 9 46 1 50 51 1 39 5 8 40 95 5 59 5 45 77 7 51 3 50 60 1 43 8 20 2000 4 40 79 8 54 1 4...

Page 11: ...8 84 3 7 9 82 5 74 3 13 9 146 4 103 1 11 9 124 8 94 0 9 8 102 8 84 7 16 4 172 1 111 9 14 3 149 7 103 1 12 0 126 1 94 1 25 10 3 129 1 96 7 8 5 105 8 86 2 6 8 84 4 75 9 12 4 155 3 106 9 10 5 130 7 96 5 8 5 106 6 86 6 14 7 183 3 116 3 12 6 157 7 106 2 10 6 132 0 96 5 DB Dry Bulb Temperature EWT Entering Water Temperature MBtuh Thousands of Btuh SCb Base Sensible Capacity at Nominal Cfm TCb Base Total...

Page 12: ...09 3 20 4 254 9 150 8 17 6 220 1 135 9 14 8 184 9 121 8 28 13 2 184 3 126 7 10 8 151 1 111 1 8 6 120 9 97 6 15 9 222 2 140 9 13 4 187 9 125 2 10 9 153 2 110 7 18 8 262 8 154 3 16 2 226 7 138 8 13 6 190 1 123 8 DB Dry Bulb Temperature EWT Entering Water Temperature MBtuh Thousands of Btuh SCb Base Sensible Capacity at Nominal Cfm TCb Base Total Capacity at Nominal Cfm WB Wet Bulb Temperature T Chan...

Page 13: ...re T Change in Water Temperature F UNIT SIZE 42BHC T 75 F DB 63 F WB 80 F DB 67 F WB 85 F DB 71 F WB 40 F EWT 45 F EWT 50 F EWT 40 F EWT 45 F EWT 50 F EWT 40 F EWT 45 F EWT 50 F EWT GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb GPM TCb SCb 08 10 7 4 36 9 25 4 5 7 28 5 21 4 4 4 21 9 18 4 9 3 46 8 29 3 7 6 38 0 25 3 5 8 29 1 21 5 11 6 57 7 33 2 9 7 4...

Page 14: ...8 7 8 1800 40 47 8 37 3 49 9 46 3 61 0 34 1 61 7 43 0 75 6 39 5 76 3 48 3 45 35 2 31 5 39 1 39 1 47 4 28 5 48 2 37 3 62 3 34 2 63 0 43 0 50 24 3 24 3 31 8 31 8 32 6 22 7 35 1 31 7 47 4 28 6 48 2 37 5 2000 40 50 6 40 1 53 1 49 9 64 4 36 5 65 1 46 1 79 6 42 1 80 3 51 7 45 37 5 34 1 42 1 42 1 50 1 30 6 50 9 40 2 65 7 36 5 66 4 46 2 50 26 3 26 3 34 3 34 3 34 4 24 5 37 3 34 3 50 1 30 7 51 0 40 4 2200 4...

Page 15: ...6 9 65 7 56 8 80 0 43 6 80 6 53 3 96 6 49 4 97 0 59 1 45 50 2 40 3 53 1 50 5 65 8 37 3 66 4 47 1 82 9 43 7 83 6 53 4 50 35 7 33 6 41 5 41 5 49 3 30 6 50 5 40 5 67 2 37 4 67 8 47 2 2000 40 68 7 50 6 70 0 61 5 84 6 46 6 85 3 57 3 101 9 52 7 102 4 63 3 45 53 5 43 7 57 1 54 9 69 8 40 2 70 4 50 9 87 7 46 9 88 4 57 5 50 38 5 36 7 45 1 45 1 52 4 33 1 53 8 44 0 71 2 40 4 71 9 51 1 2200 40 72 3 54 2 74 0 6...

Page 16: ...29 1 14 657 1 22 684 1 30 711 1 37 736 1 45 761 1 52 786 1 59 809 1 67 833 1 74 4400 806 1 79 829 1 87 852 1 95 UNIT SIZE 42BHC BLOWER CFM TOTAL STATIC PRESSURE in wg 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 08 9 x 6 600 1208 0 24 700 1220 0 28 1266 0 30 1310 0 33 1353 0 35 1395 0 37 800 1236 0 33 1280 0 35 1324 0 38 1366 0 40 1407...

Page 17: ... 39 0 52 0 03 0 06 0 12 0 18 0 24 0 04 0 13 0 07 0 10 1500 0 09 0 30 0 45 0 60 0 03 0 07 0 14 0 21 0 28 0 04 0 15 0 09 0 12 1600 0 10 0 34 0 51 0 68 0 04 0 08 0 16 0 24 0 32 0 05 0 17 0 10 0 13 1700 0 11 0 38 0 58 0 77 0 04 0 09 0 18 0 27 0 36 0 06 0 19 0 11 0 15 1800 0 12 0 43 0 65 0 86 0 05 0 10 0 20 0 30 0 40 0 06 0 21 0 12 0 17 20 1800 0 12 0 30 0 45 0 60 0 03 0 07 0 14 0 21 0 28 0 04 0 13 0 0...

Page 18: ...0 9 12 0 13 2 14 4 15 7 18 4 21 3 24 5 27 9 31 5 4 8 0 6 0 9 1 2 1 6 2 0 2 5 3 0 3 6 4 2 4 9 5 6 6 4 7 2 8 1 9 0 10 0 11 0 12 1 13 2 14 4 16 9 19 6 22 5 25 6 28 9 5 0 0 5 0 8 1 1 1 4 1 8 2 3 2 7 3 3 3 9 4 5 5 2 5 9 6 6 7 4 8 3 9 2 10 1 11 1 12 2 13 3 15 6 18 1 20 7 23 6 26 7 29 9 5 3 0 5 0 7 1 0 1 3 1 6 2 0 2 4 2 9 3 4 4 0 4 6 5 2 5 9 6 6 7 4 8 2 9 0 9 9 10 8 11 8 13 9 16 1 18 5 21 0 23 7 26 6 29 ...

Page 19: ...19 Typical wiring schematics BASE UNIT SINGLE PHASE POWER MOTOR CONTROL DISCONNECT OPTION SINGLE PHASE POWER ...

Page 20: ...20 Typical wiring schematics cont BASE UNIT THREE PHASE POWER MOTOR CONTROL DISCONNECT OPTION THREE PHASE POWER ...

Page 21: ... disconnect switch Heater power fusing 24 v class 2 transformer 40 va 8 pole control terminal strip Auto reset temperature limit switch Manual reset backup temperature limit switch Airflow safety switch 80 20 heater element wire Motor power fusing Motor control contactor Agency listed for 0 in clearance Electric heat options Single phase single stage or 2 stage heat Three phase single stage 2 or 3...

Page 22: ...l be of galvanized steel D Coils Standard unit shall be equipped with a 4 row coil for installation in a 2 pipe system and additional rows of coil shall be provided for installation in a 4 pipe sys tem as described in the Special Features section Coils shall have 1 2 in copper tubes aluminum fins bonded to the tubes by mechanical expansion and have a working pressure of 250 psig at 200 F Each coil...

Page 23: ...cated on the equipment schedule 3 Insulation a Units shall be equipped with edge sealed 1 in thick Tuf Skin RX insulation b Unit shall be equipped with edge sealed 1 in thick foil faced insulation 4 Controls a Unit shall be equipped with 24 v trans former motor contactor and terminal strip for connection to field provided controller b Unit shall be equipped with interlocking door disconnect switch...

Page 24: ...ge at any time specifications or designs without notice and without incurring obligations New Pg 24 Catalog No 524 232 Printed in U S A PC 201 Form 42BHC 1PD Replaces 42BH 4PD Book 3 Tab 7a Carrier Corporation Syracuse New York 13221 10 03 Book 4 Tab 4FC4 ...

Reviews: