background image

Selection procedure

Example 1: Selection for specified total
cooling

I Determine job requirements:

Given:
Total Cooling Load . . . . . . . . . . . . . . . . . . 67.0 MBtuh
Sensible Cooling Load . . . . . . . . . . . . . . . 41.0 MBtuh
Air Delivery . . . . . . . . . . . . . . . . . . . . . . . . . . 1800 Cfm
Entering Air Temperature . . . . 75.0 F db, 64.5 F wb
Entering Water Temperature. . . . . . . . . . . . . . . . . 43 F
External Static Pressure . . . . . . . . . . . . . . . 0.30 in. wg
Maximum Chilled Water Flow Rate . . . . . . 15.0 Gpm

I Select unit based on required air delivery.

From Fan Performance table on page 22, select a unit
that delivers required airflow. Model 42BH size 20 de-
livers 1800 cfm.

I Determine water temperature rise.

This step is used to determine the actual water tem-
perature rise required to provide the specified cooling
capacity.
(This can be done to meet either specified sensible or
specified total capacity. For this example, we will de-
termine water temperature rise required to meet the
specified total capacity after it has been corrected to
the rating curve capacity. The resulting rating curve
sensible capacity will be determined in Step IV and then
corrected to actual capacity. If the sensible capacity
were the critical requirement, the reverse procedure
would be followed.)
A. Determine the air delivery correction factors using

actual unit air delivery (1800 cfm).
Enter the 42BH Cooling Capacity Correction Fac-
tors table, page 7, at 1800 cfm and find that a
42BH size 20 unit has a total heat (TH) factor of
0.94 and a sensible heat (SH) factor of 0.93.

B. Correct the specified total capacity to the required

rating curve capacity.

Specified Total Cap.

Rating Curve Capacity =

TH Factor

67.0 MBtuh

=

0.94

= 71.3 MBtuh

C. Enter the cooling capacity curve for a size 20 unit

with standard 4-row coil at 71.3 MBtuh and project
vertically to the specified entering wet bulb (65 F).
Project from this point horizontally to the right to
the specified entering water temperature (43 F) and
then vertically to read water temperature rise of 9.2
degrees F.

I Determine the rating curve sensible capacity and

the actual sensible capacity..

A. Enter the cooling curve at the intersection of total

capacity

(71.3

MBtuh)

and

entering

wet

bulb temperature (65 F). Read horizontally to the
left to the specified dry bulb (75 F). Read down to
the rating curve sensible capacity of 46.0 MBtuh.

B. Correct the rating curve capacity to actual

capacity:
Actual Sensible Cooling
= SH x Rating Curve Sensible Cooling
= 0.93 (From Step III A) x 46.0 MBtuh
= 42.8 MBtuh

I Determine water flow and pressure drop.

A.

Actual Total Cooling

Actual Gpm =

.5 x Temp Rise

67.0

=

.5 x 9.2

(From Step III C)

= 14.6

B. Pressure drop is obtained from the curve on page

18 for the 4-row cooling coil and is 10 ft of
water.

I Find Leaving Air Dry Bulb (LDB) and Leaving

Wet Bulb (LWB) Temperatures.

A.

Actual Sensible MBtuh

LDB = EDB −

Actual Cfm x .00108

42.8 (Step IV B)

= 75

1800 x .00108

= 53.0 F

B. Leaving wet bulb is computed by referring to the

Enthalpy at Saturation table on page 21. First de-
termine that the enthalpy at saturation for the en-
tering (h

) wet bulb of 64.5 is 29.69 Btu per lb

ent

of dry air.

Actual Total Capacity

h

= h

lvg

ent

.00445 x Actual Cfm

67.0

= 29.69 −

.00445 x 1800

= 21.33

Again referring to the table, the temperature cor-
responding to 21.33, by interpolation, is 51.8 F,
which is the leaving wet bulb.

I Verify that the selected unit will provide the re-

quired external static pressure of 0.30 in. wg
with the selected coil, options, and ductwork.

A. Determine total static pressure. For an application

with ductwork, the total static pressure is equal to
the sum of the external static pressure, duct grilles,
and component static pressures.
Assume for this example that the selected 42BH
size 20 unit with 4-row cooling coil has a double
deflection grille and throwaway filter. Enter the
42BH Component Static Resistance table (page 21)
at unit size 20, 1800 cfm, and find the static resis-
tance (in. wg) for the following components:

Cabinet

0.12

4-Row Coil

0.37

Throwaway Filter

0.12

Double Deflection Grille

+ 0.07

0.68

5

Summary of Contents for 42BH Series

Page 1: ...either of two split coil options Coils consist of alu minum fins securely bonded to 1 2 in OD seamless copper tubes Each fin s aluminum collar ensures accurate control of the fin spacing while complet...

Page 2: ...teel reinforced for maximum rigidity and structural strength Removable side panels allow easy access for servicing interior components One inch matte surface glass fiber thermal acoustical insula tion...

Page 3: ...8 OD COPPER COIL CONN 1 AND 2 ROW in 5 8 OD 5 8 OD 5 8 OD 5 8 OD 5 8 OD 5 8 OD COPPER DRAIN CONN SIZES in 7 8 OD 7 8 OD 7 8 OD 7 8 OD 7 8 OD 7 8 OD Options and accessories Coils Choice of 2 pipe syste...

Page 4: ...th unit horsepower Above 3 4 hp motors are base mounted 6 Four row coil shown DIMENSION UNIT SIZE 42BH 08 12 16 20 30 40 A 35 35 35 389 16 441 16 389 16 B 18 18 18 22 29 29 C 109 16 109 16 115 8 1311...

Page 5: ...er temperature rise of 9 2 degrees F I Determine the rating curve sensible capacity and the actual sensible capacity A Enter the cooling curve at the intersection of total capacity 71 3 MBtuh and ente...

Page 6: ...65 F Project from this point horizontally to the right to the speci fied entering water temperature 42 F and then verti cally to read water temperature rise of 11 0 degrees F I Calculate actual water...

Page 7: ...0 88 1400 1 06 1 10 0 94 0 92 1500 0 97 0 96 1600 1 00 1 00 0 89 0 85 1700 1 03 1 03 0 92 0 90 1800 1 06 1 08 0 94 0 93 1900 1 09 1 12 0 97 0 96 2000 1 12 1 16 1 00 1 00 2100 1 02 1 04 2200 1 06 1 07...

Page 8: ...110 120 130 140 150 160 170 180 190 200 50 0 455 0 545 0 636 0 727 0 818 0 909 1 000 1 091 1 182 1 273 1 364 55 0 409 0 500 0 591 0 682 0 773 0 864 0 955 1 045 1 136 1 227 1 318 60 0 363 0 455 0 545 0...

Page 9: ...0 6 40 16 2 81 0 50 0 45 11 9 59 5 42 0 50 7 5 37 5 33 0 20 2000 4 40 18 8 94 0 58 0 45 13 4 67 0 48 0 50 8 6 43 0 39 0 6 40 21 0 105 0 63 5 45 16 0 80 0 52 2 50 11 0 55 0 42 0 30 3000 4 40 25 6 128...

Page 10: ...Performance data cont COOLING CAPACITY 42BH08 4 ROW 800 CFM 6 ROW 800 CFM 10...

Page 11: ...COOLING CAPACITY 42BH12 4 ROW 1200 CFM 6 ROW 1200 CFM 11...

Page 12: ...Performance data cont COOLING CAPACITY 42BH16 4 ROW 1600 CFM 6 ROW 1600 CFM 12...

Page 13: ...COOLING CAPACITY 42BH20 4 ROW 2000 CFM 6 ROW 2000 CFM NOTE Arrows illustrate Step III and IV of Selection Procedure Example 1 13...

Page 14: ...Performance data cont COOLING CAPACITY 42BH30 4 ROW 3000 CFM 6 ROW 3000 CFM 14...

Page 15: ...COOLING CAPACITY 42BH40 4 ROW 4000 CFM 6 ROW 4000 CFM 15...

Page 16: ...3 48 3 45 35 2 31 5 39 1 39 1 47 4 28 5 48 2 37 3 62 3 34 2 63 0 43 0 50 24 3 24 3 31 8 31 8 32 6 22 7 35 1 31 7 47 4 28 6 48 2 37 5 2000 40 50 6 40 1 53 1 49 9 64 4 36 5 65 1 46 1 79 6 42 1 80 3 51 7...

Page 17: ...4 47 1 82 9 43 7 83 6 53 4 50 35 7 33 6 41 5 41 5 49 3 30 6 50 5 40 5 67 2 37 4 67 8 47 2 2000 40 68 7 50 6 70 0 61 5 84 6 46 6 85 3 57 3 101 9 52 7 102 4 63 3 45 53 5 43 7 57 1 54 9 69 8 40 2 70 4 50...

Page 18: ...Performance data cont 42BH WATER PRESSURE DROP 18...

Page 19: ...42BH WATER PRESSURE DROP cont 19...

Page 20: ...Performance data cont 42BH WATER PRESSURE DROP cont 20...

Page 21: ...800 08 34 51 05 08 15 22 05 06 14 10 900 10 36 54 06 10 18 27 06 07 17 11 12 1000 07 33 49 04 06 11 17 02 03 15 09 1100 08 35 51 04 07 13 20 03 03 18 11 1200 09 36 54 05 08 16 23 03 04 19 12 1300 10...

Page 22: ...5 1 2 1345 1 2 1345 1 2 1680 1 2 1680 1 2 1680 1 2 800 1250 1 3 1345 1 2 1345 1 2 1345 1 2 1345 1 2 1345 1 2 1680 3 4 1680 3 4 900 1345 1 2 1345 1 2 1345 1 2 1345 1 2 1345 1 2 1345 1 2 1680 3 4 1680 3...

Page 23: ...these are draw through units it will be necessary to calculate the air temperature leaving the coil for all heating applications If this temperature exceeds 104 F consult Syra cuse to determine avail...

Page 24: ...ded Since these are draw through units it will be necessary to calculate the air temperature leaving the coil for all heating applications If this temperature exceeds 104 F consult Syra cuse to determ...

Page 25: ...8 4 4 4 3 4 13 0 6 5 1 15 0 7 5 50 HZ THREE PHASE MOTORS 1425 Rpm HORSEPOWER VOLTAGE 190 380 1 3 1 8 0 9 1 2 2 8 1 4 3 4 3 2 1 6 1 4 0 2 0 11 2 5 6 2 8 2 7 2 3 6 NOTES 1 Motor full load amps listed re...

Page 26: ...the tubes by mechanical expansion and have a work ing pressure of 250 psig Each coil shall have a manual air vent and sweat connections for copper tubes E Operating Characteristics A single circuit co...

Page 27: ...5 90 Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 3 Tab 7a Page 28 Catalog No 524 228 Printed in...

Reviews: