background image

42/38SHDV105

42/38SHDV095

42/38SHDV165

 

 

   

IMPORTANT NOTE:

Read this manual carefully before 

installing or operating your new air 

conditioning unit. Make sure to save 

this manual for future reference. 

This manual only describes the installation of 

outdoor unit. When installing the indoor unit,

refer to the installation manual of indoor unit. 

• 

• 

INSTALLATION MANUAL

HIGH STATIC DUCTED AIR CONDITIONER

42/38SHDV125
42/38SHDV140

Summary of Contents for 42/38SHDV095

Page 1: ...ting your new air conditioning unit Make sure to save this manual for future reference This manual only describes the installation of outdoor unit When installing the indoor unit refer to the installa...

Page 2: ...structions 08 Safety Precautions 05 Outdoor Unit Installation a Outdoor Unit Installation Instructions b Outdoor Unit T c Notes on Drilling Hole in Wall Drainpipe Installation Table of Contents Instal...

Page 3: ...16 16 Page 3 Refrigerant Piping Connection A Notes on Pipe Length and Elevation B Refrigerant Piping Connection Instructions Wiring a Outdoor Unit Wiring b Indoor Unit Wiring Air Evacuation a Evacuati...

Page 4: ...ail QUANTITY SHAPE NAME Soundproof insulation sheath 2 1 1 1 Tubing Fittings Others Installation manual Component of display control unit some models 1 Owner s manual Drainpipe Fittings for cooling he...

Page 5: ...rong winds typhoons and earthquakes that might affect your unit and locate it accordingly Failure to do so could cause the equipment to fail After installation ensure there are no refrigerant leaks an...

Page 6: ...3 4 5 MC MC 6 7 Install the indoor unit Page 7 INSTALLATION ORDER Install the outdoor unit Page 13 Install the drainpipe Page 16 Evacuate the refrigeration system Page 25 Connect the wires Page 21 Con...

Page 7: ...following requirements Enough room for installation and maintenance Enough room for the connecting pipe and drainpipe The ceiling is horizontal and its structure can sustain the weight of the indoor u...

Page 8: ...he following diagrams to locate the four positioning screw bolt holes on the ceiling Be sure to mark the paces where you will drill ceiling hook holes This unit has been installed air intake pipe flan...

Page 9: ...same size before moving on 2 Install and fit pipes and wires after you have finished installing the main body When choosing where to start determine the direction of the pipes to be drawn out Especial...

Page 10: ...9 x 10 screw 4 Connect the duct according to the following diagram Canvas tie in Canvas tie in Air outlet Isolation booth Isolation booth checking orifice Air inlet Air dust filter 1 Install the dust...

Page 11: ...length between the outdoor and indoor unit may not exceed the maximum allowable pipe length If possible DO NOT install the unit where it is exposed to direct sunlight If possible make sure the unit i...

Page 12: ...n Table 5 1 Length Specifications of Split Type Outdoor Split Type Outdoor Unit Refer to Fig 5 4 5 5 5 6 5 10 and Table 5 1 Fig 5 6 Fig 5 5 A B D W H W H Fig 5 4 Model Unit mm W D H A B 946 410 810 67...

Page 13: ...ter from the unit during heating mode NOTE Make sure the water drains to a safe location where it will not cause water damage or a slipping hazard Seal Drain joint A B Base pan hole of outdoor unit Se...

Page 14: ...ensation which could lead to water damage If the drainpipe is bent or installed incorrectly water may leak and cause a water level switch malfunction In HEAT mode the outdoor unit will discharge water...

Page 15: ...roper water drainage See Fig 6 5 Place the protective wall cuff in the hole This protects the edges of the hole and will help seal it when you finish the installation process Wall Indoor Outdoor 12mm...

Page 16: ...poor operating capacity high pressure in the refrigeration cycle explosion or injury Ventilate the area immediately if there is refrigerant leakage during the installation Leaked refrigerant gas is bo...

Page 17: ...he pipe is cut at a perfect 90 angle Refer to Fig 7 1 for examples of bad cuts Oblique Rough Warped 90 Fig 7 1 Step 2 Remove burrs Burrs can affect the air tight seal of refrigerant piping connection...

Page 18: ...o tighten the are nut according to the torque values in table 7 2 NOTE Use both a spanner and a torque wrench when connecting or disconnecting pipes to from the unit Fig 7 7 CAUTION Ensure to wrap ins...

Page 19: ...nnection is made through a switch that disconnects all poles with contact gap of at least 3mm 0 118 DO NOT modify the length of the power cord or use an extension cord CAUTION Connect the outdoor wire...

Page 20: ...cable for connection a Using wire strippers strip the rubber jacket from both ends of the signal cable to reveal about 15cm 5 9 of the wire b Strip the insulation from the ends of the wires c Using a...

Page 21: ...s CONFIRM The air conditioning unit will then start the fan for airflow automatic adjustment ON will flash during when the fan is on during automatic airflow adjustment After 3 to 6 minutes the air co...

Page 22: ...auxiliary heating type circuit breaker fuse need to add more than 10 A Model Power Supply Hz Voltage Min Max MFA 50 220 240V 198V 254V 30 50 220 240V 198V 254V 30 38SHDV125 50 220 240V 198V 254V 40 3...

Page 23: ...he manifold gauge Keep the High Pressure side closed 4 Turn on the vacuum pump to evacuate the system 5 Run the vacuum for at least 15 minutes or until the Compound Meter reads 76cmHG 1x105Pa 6 Close...

Page 24: ...g the system DO NOT mix refrigerants types of the unit Extend pipe length will reduce the capacity and energy efficiency amount of 5 meter piping on specification or nameplate to the actual pipe lengt...

Page 25: ...ed correctly d Ensure the indicators on the remote control and the display panel on the indoor unit work properly e Ensure the manual buttons on the indoor unit works properly f Check to see that the...

Page 26: ......

Reviews: