3

CONNECT TO OUTDOOR UNIT

IN

S

ULATE PIPE

IN

S

ULATE PIPE

CONNECT TO 1 TO 4 INDOOR UNIT

S

HANGING BAR

BRANCH
BOX

a

40-1790

Fig. 3 — Branch Box Installation

OUTDOOR
UNIT

INDOOR
UNIT

BRANCH
BOX

A40-1792

40 in. MINIMUM

40 in.

MINIMUM

20 in. MINIMUM

20 

in.

 MINIMUM

Fig. 4 — Straight Pipe Minimum Lengths

BRANCH BOX

OUTDOOR UNIT

INDOOR UNIT

65 ft MAX.

OUTDOOR UNIT 

T

O

 INDOOR UNIT

ELEV

A

TION DIFFERENTIAL

26 ft MAX.

INDOOR UNIT 

T

O

 

INDOOR UNIT

ELEV

A

TION

DIFFERENTIAL

A40-1791

Fig. 5 — Maximum Pipe Length and Elevation Differential

PIPE LENGTH 

MAXIMUM 

PIPING

TOTAL 
(ACTUAL)

328 ft

L1+L2+L3+

L4+L5

MAXIMUM 
PIPING

147 ft

L1+L2
L1+L3
L1+L4
L1+L5

BRANCH BOX 
TO INDOOR UNIT

65 ft

L2, L3, 

L4, L5

ELEVATION

DIFFERENTIAL 

MAXIMUM

INDOOR UNIT TO 
OUTDOOR UNIT

65 ft

INDOOR UNIT TO 
INDOOR UNIT

26 ft