Carrier 40WAD007 Installation And Maintenance Instructions Manual Download Page 10

10

System Operation Check — 

Once the installation

and pre-start checks are completed, follow these steps:

1. Using remote controller, select cooling or heating mode

to check the operation of the system.

2. While the system is in operation, check the following on

indoor unit:
a. Switches or buttons on the remote controller are easy to   

push.

b. Indicator light is showing normal operation and no er-

ror is indicated.

c. Swing mode of air louvers is working (if applicable to

unit).

d. Drain pump operation is normal (if applicable).
e. No abnormal vibration or noise is noticed.

3. While the system is in operation, check the following on

outdoor unit:
a. No abnormal vibration or noise is noticed.
b. Condenser fan is in operation.
c. Indicator light is showing normal operation and no er-

ror is indicated.

NOTE: If the unit is turned off or restarted, there is a time

delay of 3 minutes for the compressor to start from the time the

power is restored.

MAINTENANCE

EVERY 3 MONTHS:
• Check the air filter condition. Clean or replace if neces-

sary.

EVERY 6 MONTHS — Follow 3-month maintenance sched-

ule.  In addition:
• Clean condensate tray with suitable cleaning agent.
• Clean the grille and panel if applicable.
EVERY 12 MONTHS — Follow 6-month maintenance

schedule. In addition:
• Be sure all electrical connections are secure.
• Check condensate pump operation if applicable.
• Check the heating and cooling action to confirm proper

operation.

TROUBLESHOOTING

Figure 14 shows the LED display panel on the indoor unit.

See Table 3 for a summary of display indicators. Table 4 lists

problems, possible causes, and possible solutions.

Replacement Parts — 

Quote the unit model number

and unit serial number when ordering replacement parts or

contacting the factory about the unit. This information can be

found on the serial plate attached to the unit. See Fig. 15.

TUBE/PIPE

A40-1854

Fig. 13 — Tube/Pipe Insert

CAUTION

When servicing or repairing this unit, use only factory-

approved service replacement parts. Refer to the rating

plate on the unit for complete unit model number, serial

number and company address. Any substitution of parts or

controls not approved by the factory will be at the owner’s

risk and may result in equipment damage.

CAUTION

To avoid equipment damage, do not attempt to reuse any

mechanical or electrical controllers that have been wet.

Replace defective controller.

MANUAL OPERATION TIMER DEF./FAN ALARM

a40-1873

Fig. 14 — LED Display Panel

40WAD007---3

1

60

208/230

0.34

32

1/6

2115V20001

Carrier Corporation

Carrier Corporation

7310 West Morris Street

7310 West Morris Street

Indianapolis, IN 46231 USA

Indianapolis, IN 46231 USA

CONCEALED UNIT  

a40-1874

Fig. 15 — Unit Serial Plate (Example)

Summary of Contents for 40WAD007

Page 1: ...rds DANGER WARNING and CAUTION DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards that could result in personal inju ry or death...

Page 2: ...ze Figure 2 shows unit dimen sions See Fig 3 for fan performance curves CAUTION DO NOT re use compressor oil or any oil that has been exposed to the atmosphere Dispose of oil per local codes and regul...

Page 3: ...wg 0 04 to 0 20 INDOOR NOISE LEVEL dBA Low 31 31 33 33 34 Medium 34 34 36 37 38 High 35 36 37 38 40 UNIT Unit Dimensions W x H x D in 27 1 2 x 8 1 4 x 19 3 4 36 1 4 x 8 1 4 x 19 3 4 44 7 8 x 8 1 4 x...

Page 4: ...1847 1 3 8 Fig 2 40WAD007 024 Dimensions NOTE All dimensions shown in inches 40WAD UNIT SIZE DIMENSION in A B C D E F G H I J K L M 007 012 27 1 2 8 1 4 19 3 4 17 3 4 30 3 4 1 1 4 20 1 8 5 8 5 3 4 23...

Page 5: ...erial on the motor or blower wheels will not be covered by the manufacturer s war ranty Some units and or job conditions may require some form of temporary covering during construction PREPARING JOBSI...

Page 6: ...for the drain 3 Secure the unit in position with locknuts and washers on both sides of the mounting bracket Ensure that the threaded rod does not protrude more than 2 in below the mounting brackets as...

Page 7: ...ring must comply with CSA C22 1 Electrical Code This equipment in its standard form is designed for an elec trical supply of 208 230 1 60 Any damage to or failure of units caused by incorrect wiring o...

Page 8: ...r electrical devices WIRED REMOTE CONTROLLER PROGRAMMA BLE To connect a programmable wired remote controller thermostat to the indoor unit use 4 core shielded cable and 4 pin connector from electrical...

Page 9: ...nd liquid line service valves are in open posi tion Drain Pump and Drainage Test Follow these steps to perform the test 1 Remove the test cover by rotating it counter clockwise as shown in Fig 12 2 Us...

Page 10: ...addition Be sure all electrical connections are secure Check condensate pump operation if applicable Check the heating and cooling action to confirm proper operation TROUBLESHOOTING Figure 14 shows t...

Page 11: ...are short circuited or disconnected Check or reconnect signal wire Signal wire order is incorrect Correct signal wire order Signal wires crossing over high voltage power wires Separate and distance th...

Page 12: ...2 a40 1932 Fig B SW2 Settings POSITION 1 2 COIL TEMPERATURE HEATING MODE OFF OFF Coil Temperature 59 F No Heat Default OFF ON Coil Temperature 68 F No Heat ON OFF Coil Temperature 75 2 F No Heat ON O...

Reviews: