Carrier 40VML007-024 Installation And Maintenance Instructions Manual Download Page 16

16

3. While the system is in operation, check the following on

the outdoor unit:

a. No abnormal vibration or noise is noticed.

b. Condenser fan is in operation.

c. Indicator light is showing normal operation and no

error is indicated.

NOTE:

 If the unit is turned off or restarted, there is a time

delay of three minutes for the compressor to start from the time

the power is restored.

MAINTENANCE

EVERY 3 MONTHS:

• Check  the  air  filter  condition.  Clean  or  replace  if

necessary.

EVERY 6 MONTHS:

Follow the 3-month maintenance schedule. In addition:
• Clean condensate tray with suitable cleaning agent.
• Clean the grille and panel if applicable.

EVERY 12 MONTHS:

Follow the 6-month maintenance schedule. In addition:
• Be sure all electrical connections are secure.
• Check condensate pump operation if applicable.
• Check the heating and cooling action to confirm proper

operation.

INDOOR UNIT ADDRESSING

For  proper  system  operation,  each  indoor  unit  must  have  a

unique address set from 0 to 63. When setting an address by

remote  controller, the outdoor  units, indoor units,  and MDC

must be powered on. If 

FE

 is displayed on the LED screen or

display board, this unit has no address. After setting all indoor

unit addresses, turn off the power supply to all indoor units to

clear the errors.

Indoor unit addressing can be distributed automatically in the

heat pump system. When dip switch “S6” on the outdoor unit’s

main PCB board is set to 00 (default set in factory), indoor

units are set for auto-addressing. When powering on for the

first time, it takes six minutes or more to finish auto-addressing

each indoor unit. The heat recovery system cannot accomplish

this function at this time.

Wireless Remote Controller (40VM900001)  — 

 

Indoor unit addressing can be performed using the wireless 

remote controller. When using the wireless controller, the user 

must maintain a line of sight with the receiver on the indoor 

unit. See Fig. 29 for a description of the buttons on the wireless 

remote.

Fig. 29 —Wireless Remote Controller 

(40VM900001)

1. Use a tool to press and hold the LOCK button for at least

ten seconds. 

2. Press         to activate. 

3. Click        or         to select an address and press        to send

the setting.

To display an indoor unit address, use a tool to press and hold

the LOCK button for at least ten seconds, and press        to

query the addresses.

Non-Programmable Controller

When setting an address, connect only one wired controller to 

an indoor unit.

Press 

ROOM TEMP

 and 

SWING

 simultaneously for three

seconds. If there is no address for this indoor unit, the display

shows 

FE# 00

. See Fig. 30. Otherwise, the display shows the

current address of the indoor unit.

Fig. 30 —Non-Programmable Controller IDU 

Addressing Menu

CAUTION

When  servicing  or  repairing  this  unit,  use  only  factory-

approved  service  replacement  parts.  Refer  to  the  rating

plate on the unit  for complete unit model number, serial

number, and company address. Any substitution of parts or

controls not approved by the factory will be at the owner’s

risk and may result in equipment damage.

CAUTION

To avoid equipment damage, do not attempt to reuse any

mechanical  or  electrical  controllers  that  have  been  wet.

Replace defective controller.

RESET

TIMER ON

TIMER OFF

SWING

AIR DIRECTION

CLOCK

OK

SWING

MODE

FAN

AUTO

COOL

DRY

HEAT

FAN

TEMP

SET

CLOCK

SET

HOUR

FAN SPEED

LOCK C/H

6 – AIR DIRECTION

2 – FAN SPEED SETTING

4 – ADJUST UP

9 – CLOCK SETTING

10 – TIMER ON

14 – OK (CONFIRM)

11 – TIMER OFF

1 – MODE SETTING

5 – ON/OFF

3 – ADJUST DOWN

7 – AIR VERT. SWING

8 – AIR HORIZ. SWING

12 – RESET

13 – LOCK

15 – COOL/HEAT

A40-1734

MODE

FAN

TEMP. DOWN

OK

TEMP. UP

ON/OFF

TIMER

ROOM TEMP.

SWING

#

Summary of Contents for 40VML007-024

Page 1: ...could result in personal injury or death CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage Recognize safety information This is th...

Page 2: ...OT re use compressor oil or any oil that has been exposed to the atmosphere Dispose of oil per local codes and regulations DO NOT leave refrigerant system open to air any longer than the actual time r...

Page 3: ...0 37 0 Medium 32 0 34 6 35 2 38 0 38 8 High 34 0 34 5 37 0 36 7 40 2 41 3 UNIT Unit Dimensions W x H x D in 30 3 4 x 8 1 4 x 19 3 4 39 1 4 x 8 1 4 x 19 3 4 48 x 8 1 4 x 19 3 4 Packing Dimensions W x...

Page 4: ...015 018 36 1 4 39 3 8 28 7 8 32 1 4 7 7 8 37 3 4 024 44 7 8 48 37 5 8 41 46 1 2 AIR FILTER ELECTRICAL CONTROL BOX SIDE VIEW FRONT VIEW REAR VIEW BOTTOM VIEW P TOP VIEW SUSPENSION BRACKETS 4 P N 3 4 20...

Page 5: ...M Low ax ESP er lim it of ESP P Upper limit of ESP p e r l i m Min ES U p M a x E S P i t o f E S P H S M S L S H S M S L S ESP FAN SPEED RANGE OF AVAILABLE AIRFLOW RATE IN H SPEED Max Point Mid Poin...

Page 6: ...ESP r l i m M L o w a x e E S P i t o f E S P Min p e r l i m ESP Upper limit of ESP U p M a x E S P i t o f E S P Fig 6 Size 018 Fan Curves ESP FAN SPEED RANGE OF AVAILABLE AIRFLOW RATE IN H SPEED Ma...

Page 7: ...ture theft vandalism and debris on jobsite Equipment covered in this manual is not suitable for outdoor installations Do not allow foreign material to fall into drain pan Prevent dust and debris from...

Page 8: ...wo inches below the mounting brackets as shown in Fig 9 INSTALLING THE DUCT Connect the return and supply ducts to the duct collars provided on the unit Adequate distance between the return and supply...

Page 9: ...piping The highest point in the condensate piping should be as close to the unit as possible See Fig 15 Condensate piping should slope downward in the direction of condensate flow with a minimum grad...

Page 10: ...ge to or failure of units caused by incorrect wiring or voltage is not covered by the warranty Electric wiring must be sized to carry the full load amp draw of the motor starter and any other controls...

Page 11: ...let Pipe Temperature Sensor XP1 4 Connectors XS1 4 XT1 2 Terminal Block Optional Component or Field Wiring EEV FM ALARM PUMP CN24 N3 CN1 C 8 CN2 EARTH Y G CN15 CN9 CN17 Y G L1 L2 controller To wired c...

Page 12: ...Connector 2 Strip a suitable length of the insulation layer as shown in Fig 20 below Fig 20 Stripping The Wire 3 Use a suitable screwdriver to fix the communication wire on the outdoor unit communicat...

Page 13: ...indoor To No 3 indoor To No 4 indoor To No 1 indoor To No 2 indoor To Sub MDC Main MDC unit To outdoor To outdoor L1 L2 L3 L3 L3 L3 L4 L4 L5 L6 L7 L8 L9 L10 L11 Indoor unit 1 HA HB Indoor unit 2 Indoo...

Page 14: ...ontroller HA HB L1 L3 L5 L6 L7 L8 L9 L10 L11 L3 L3 L3 L3 Indoor unit 1 Indoor unit 2 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 3 P Q HA HB HA HB HA HB HA HB HA HB HA HB P Q Network Resisto...

Page 15: ...e unit ON in cooling mode The pump comes on Watch the end of the drain pipe for any water It may take time for the water to travel depending on the length of the drain pipe 4 During this test check an...

Page 16: ...oller 40VM900001 Indoor unit addressing can be performed using the wireless remote controller When using the wireless controller the user must maintain a line of sight with the receiver on the indoor...

Page 17: ...32 2 Press TEMP UP or TEMP DOWN to move the cursor and choose IDU ADDRESSING Press MENU OK to access this setting 3 Press TEMP UP or TEMP DOWN to choose the address you want to set as shown in Fig 33...

Page 18: ...ting Cooling Mode Conflict E1 None Communication Error Between Indoor and Outdoor Unit E2 None Check Indoor Ambient Temperature Sensor T1 E4 None Check Evaporator Temperature Sensor T2B E5 None Check...

Page 19: ...board E9 Communication Error Between Indoor Unit and Controller Signal wires are short circuited or disconnected Check or reconnect signal wires Signal wires close to electromagnetic source Distance...

Page 20: ...the default settings v POSITION 1 START UP OFF Auto Addressing Mode Default ON Factory Test Mode POSITION 2 MODE OFF Normal Mode default ON Factory Self Checking Mode POSITION 3 NOT USED POSITION 4 IN...

Reviews: