background image

21

Table 6 — Troubleshooting

Replacement Parts — 

Quote the unit type and unit

serial number when ordering replacement parts or contacting

the factory about the unit. This information can be found on the

serial plate attached to the unit. See Fig. 43.

DIGITAL 

DISPLAY

DESCRIPTION

POSSIBLE CAUSES

POSSIBLE SOLUTIONS

dd

Heating/Cooling Mode Conflict

System is in cooling or fan mode only and heating 

signal is received from a unit in the system.

All units should be in cooling mode for system to 

stay in cooling mode.

System is in heating mode and cooling signal is 

received from a unit in the system.

All units should be in heating mode.

E1

Communication Error Between 

Indoor and Outdoor Unit

Signal wires are short-circuited or disconnected.

Check or reconnect signal wire.

Signal wires close to electromagnetic source.

Distance signal wires from electromagnetic 

source.

PC board fault.

Replace PC board.

E2, E4, 

E5

Check Temperature Sensor

Loose connection at port on PC board.

Tighten the connection at port on PC board.

Sensor is short-circuited.

Using multi-meter, measure resistance of the 

sensor. If the resistance is 

 100 ohms, change 

the sensor.

PC board fault.

Replace PC board.

E6

Check DC Fan Motor

Operating beyond limits.

Check and correct external static pressure on 

the unit.

DC motor fault.

Replace DC motor.

PC board fault.

Replace PC board.

E7

EEPROM Error (Data Storage) Chip or PC board fault.

Replace PC board.

E9

Communication Error Between 

Indoor Unit and Controller

Signal wires are short-circuited or disconnected.

Check or reconnect signal wires.

Signal wires close to electromagnetic source.

Distance signal wires from electromagnetic 

source.

PC board fault.

Replace PC board.

Eb

EEV Error

EEV wires are short-circuited or disconnected.

Check or reconnect signal wire.

EEV stop.

Replace EEV.

PC board fault.

Replace PC board.

Ed

Outdoor Unit Error

Outdoor unit fault.

Refer to outdoor unit troubleshooting guide.

EE

Condensate Overflow

Loose connection or disconnected at port on PC 

board.

Tighten the connection or reconnect at port on 

PC board.

Condensate switch float is stuck.

Inspect the float.

Trap slope is too steep.

Adjust the trap slope.

Drain pipe is too long.

Adjust the length of the drain pipe.

Drain pump faulty.

Replace the drain pump.

FE

No Address When Powered 

ON For First Time

Indoor unit without address.

Run automatic addressing option at outdoor 

unit.
Use remote wireless or wired controller to 

readdress the indoor unit.

UU

MDC In Auto System-Check 

Mode

MDC Fault.

Refer to MDC troubleshooting guide.

LEGEND:
EEPROM

— Electronically Erasable Programmable Read-only Memory

EEV

— Electronic Expansion Valve

MDC

— Multiport Distribution Controller

PC

— Process Controller

ONE-WAY CASSETTE

AIR CONDITIONER INDOOR UNIT

MODEL

R410A

HIGH

LOW

REFRIGERANT

250 PSIG

650 PSIG

DESIGN
PRESSURE

POWER SUPPLY

MINIMUM CIRCUIT AMPACITY

MAX FUSE OR HACR BREAKER

FAN MOTOR

FLA

OUTPUT

CONFORMS TO UL STD. 1995 
CERTIFIED TO CSA STD. 
C22. 2 No. 236

ELECTRIC CHARACTERISTICS ARE 
ONLY FOR INDOOR UNIT.

SERIAL NO.

                         Carrier Corporation

  40VMI005---A

0.29A

15 A

0.23 A

208/230V-1Ph-60Hz

20W (1/30HP)

Fig. 43 — Unit Serial Plate (Example)

Summary of Contents for 40VMI Series

Page 1: ...st serious hazards which will result in severe personal injury or death WARNING signifies hazards that could result in personal injury or death CAUTION is used to identify unsafe practices which would...

Page 2: ...omenclature Figs 2 and 3 show unit dimensions Table 2 shows components that may or may not be used for a particular installation Fig 1 Model Number Nomenclature CAUTION DO NOT re use compressor oil or...

Page 3: ...3 6 High 31 7 35 4 41 5 45 0 40 7 45 5 46 2 UNIT Unit Dimensions W x H x D in 42 x 6 x 16 3 4 51 1 2 x 7 1 2 x 18 Panel W x H x D in 46 1 2 x 1 x 18 1 4 53 x 1 x 19 3 4 Unit Net Shipping Weight lb 27...

Page 4: ...2 For piping connections Rope Tie 10 For fastening and tightening Condensate Connection 1 For drain connection Clamp 1 For connecting the drain Washer 8 To secure suspended unit Nut 8 To secure suspe...

Page 5: ...5 DIMENSIONS NOTE All dimensions are shown in inches Fig 2 40VMI005 012 6 1 46 1 2 34 3 4 35 2 3 4 8 3 4 18 1 4 3 4 16 3 4 2 1 2 3 4 2 2 3 4 40 11 1 2 42 2 1 1 2...

Page 6: ...6 NOTE All dimensions are shown in inches Fig 3 40VMI015 024 1 7 1 2 53 41 1 2 2 3 4 19 3 4 9 41 3 4 2 1 4 1 1 4 1 2 3 4 2 18 3 4 1 1 4 2 3 4 48 1 2 1 2 11 3 4 51 1 2 1...

Page 7: ...mplete sample installation in a typical room at the jobsite Check all critical dimensions such as pipe wire and duct connection requirements Refer to job drawings and product dimension drawings as req...

Page 8: ...ns are in inches MOUNTING UNIT The unit can now be lifted on to the hanging rods for mounting 1 Use rods and fasteners to suspend the unit at the factory provided mounting holes 2 Adjust the height of...

Page 9: ...e panel assembly NOTE Be aware that the louver and display wires are connected so be careful when removing the panel a Unhook the clip on the left side of the unit first b Gently angle and twist the p...

Page 10: ...trol panel Remove Panel control display box wire Panle wind deflector motor wire Wind deflector motor wire cable plug connects to the CN21 of the main control panel Room temp sensor T1 wire cable plug...

Page 11: ...nt any breakage in piping Use proper cutting and flaring tools to avoid leakage Use a torque wrench for flare nuts Refer to Table 3 for flare nut torque recommendations Table 3 Flare Nut Torque Recomm...

Page 12: ...indoor unit requires its own power supply Indoor units are not powered through outdoor units Table 4 40VMF Electrical Data Fig 26 Power Supply Specifications WARNING All units must be wired strictly i...

Page 13: ...T2A T2B T1 RED BLUE Occupancy sensor ON OFF Dry contact SW8 SW1 ENC2 ENC1 5V GND 12V ONLY USED FOR TESTING ON 1 2 3 4 ON 1 2 ON ON To wired controller comm bus WHITE BLUE XT2 Red L1 L2 Blue Y G XT1 PO...

Page 14: ...plied in the accessory kit and follow the steps below 1 Cut connector on outdoor unit side Fig 29 Fig 29 Shearing Outdoor Connector 2 Strip a suitable length of insulation layer Fig 30 3 Use a suitabl...

Page 15: ...WUDOL HG FRQWUROOHU ZLUHG FRQWUROOHU ZLUHG FRQWUROOHU 7R 1R LQGRRU 7R 1R LQGRRU 7R 1R LQGRRU 7R 1R LQGRRU 7R 1R LQGRRU 7R 1R LQGRRU 7R RXWGRRU 7R 6XE 0 7R RXWGRRU L1 L2 L4 L4 L5 L6 QGRRU XQLW HB P Q Q...

Page 16: ...L3 L3 L5 L6 L7 Indoor unit 1 HA HB P Q Indoor unit 2 HA HB P Q L8 L10 L11 Indoor unit 5 HA HB P Q Indoor unit 6 HA HB P Q Indoor unit 4 HA HB P Q L9 Indoor unit 3 HA HB P Q L1 4 Matched resistance net...

Page 17: ...is showing normal operation and no error is indicated c Swing mode of air louvers is working if applicable to unit d Drain pump operation is normal if applicable e No abnormal vibration or noise is n...

Page 18: ...ss and hold the LOCK button for at least 10 seconds then press to activate Click or to select an address and press to send the setting To display an indoor unit address use a tool to press and hold th...

Page 19: ...Press TEMP UP or TEMP DOWN to move the cursor and choose IDU ADDRESSING Press MENU OK to access this setting 3 Press TEMP UP or TEMP DOWN to choose the address you want to set See Fig 41 Press MENU O...

Page 20: ...ing Mode Conflict Error E1 Communication Error Between Indoor and Outdoor Unit E2 Check Indoor Temperature Sensor T1 E4 Check Evaporator Outlet Temperature Sensor T2B E5 Check Evaporator Temperature S...

Page 21: ...and Controller Signal wires are short circuited or disconnected Check or reconnect signal wires Signal wires close to electromagnetic source Distance signal wires from electromagnetic source PC board...

Page 22: ...the settings for each parameter controlled by a switch Switches are shown in the default settings POSITION 1 START UP POSITION 2 POSITION 3 NOT USED POSITION 4 INDOOR UNIT IDENTIFICATION Fig A SW1 SE...

Reviews: