background image

harmful interference to radio communications. Operation

accordance with the instruction manual, may cause

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 17-40VM9006-01

Printed in China

Form 40VM-5SIR1

Pg 1 

09-17

Replaces: 40VM-5SI

Installation Instructions

Part Number 40VM900006

For Commercial Use Only

CONTENTS

Page

SAFETY CONSIDERATIONS

.......................................1

GENERAL

..................................................................1

DIMENSIONAL DRAWINGS

.......................................... 2

INSTALLATION CONSIDERATIONS

.............................4

INSTALLATION

..........................................................4

SETTING NETWORK ADDRESS

.......................................

6

BASIC CONFIGURATION

....................................................

6

•   LOGIN........................................................................6
•   BRAND CHOICE.......................................................7
•   AUTO SEARCH.........................................................7

SAFETY CONSIDERATIONS

Read and follow manufacturer instructions carefully. 

Follow all local electrical codes during installation. All wiring 
must conform to local and national electrical codes. Improper 
wiring or installation may damage thermostat.

Understand the signal words — DANGER, WARNING, 

and CAUTION. DANGER identifies the most serious hazards 
which will result in severe personal injury or death. 
WARNING signifies hazards that could result in personal 
injury or death. CAUTION is used to identify unsafe practices, 
which would result in minor personal injury or product and 
property damage.

Recognize safety information. This

symbol (

). When this symbol is displayed on the unit and in 

instructions or manuals, be alert to the potential for personal 
injury. Installing, starting up, and servicing equipment can be 
hazardous due to system pressure, electrical components, and 
equipment location.

GENERAL

The VRF (variable refrigerant flow) touch screen central 

controller is a wall-mounted, low-voltage controller that 
provides site-level control of multiple VRF systems. The 
controller allows central management of mode, setpoint, 
and scheduling of indoor units (IDUs). 

The touch screen central controller is available for use

with the VRF (variable refrigerant flow) outdoor units /
systems listed in Table 1.

NOTES:

1.

Changes or modifications of this product not expressly
approved by the party responsible for compliance could
void the user's authority to operate the equipment.

2.

This equipment has been tested and found to comply with
the limits for a Class A digital device, pursuant to Part 15
of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when
the equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio

Table 1:  Touch Screen Central Controller 

Accessory Usage 

Table 2: Components shipped with Unit

Table 3: Specifications

UNIT

SIZES

38VMAR Heat Recovery System

072,096,120,144, 168, 192, 216, 
240, 264, 288, 312, 336

38VMAH Heat Pump System

036, 048, 060, 072, 096, 120, 
144, 168, 192, 216, 240, 264, 
288, 312, 336, 360, 384, 408, 
432

NAME

IMAGE

QTY

FUNCTION

Mounting 

Box

1

Plastic mounting enclosure

Mounting 

Plate

1

Steel plate connecting 

controller to front of Mounting 

Box

Screws 

(Short)

6

Used to Install Mounting Box 

to Wall

Screws

4

Used to install Mounting Plate 

on Mounting Box

Washers

8

Used to install Mounting Plate 

on Mounting Box

(2 extra washers for fine 

adjustment if wall is uneven)

Power Supply 

(field provided)

Rated Voltage

24VAC, 60 Hz

Current Requirement

1A

Dimensions 

(inches)

H

7-3/8

W

10-7/8

D

1-1/4

Total Weight

Touch Screen Controller, Mounting Box, 

Mounting Plate, & Screws: 2 lbs 12 oz

Number of X/Y 

Bus Lines

6

Max. Refrigerant 

Systems/IDUs 

per Line

8/64

38VM/40VM Series

VRF (Variable Refrigerant Flow) System

Touch Screen Central Controller Accessory

of this equipment in a residential area is likely to cause
harmful interference-in which case the user will be
required to correct the interference at their own expense.
This equipment should be installed and operated with a 
minimum distance of 20 centimeters between the radiator
and your body.

Summary of Contents for 40VM900006

Page 1: ...ouch screen central controller is available for use with the VRF variable refrigerant flow outdoor units systems listed in Table 1 NOTES 1 Changes or modifications of this product not expressly approv...

Page 2: ...2 DIMENSIONAL DRAWING 10 7 8 7 3 8 1 1 4 3 8 Fig 1 Dimensions...

Page 3: ...2 reserved AI1 reserved AI2 reserved LAN Local Area Network connection Ethernet USB Universal Serial Bus connection for service Emergency Shutdown input is not suitable for life safety applications su...

Page 4: ...he 10 1 4 by 6 5 8 opening in dry wall or mounting surface making sure the box is flush with the wall surface See Figure 3 Use the 6 short screws to fasten the plastic mounting box Use plastic washers...

Page 5: ...stems with dual or triple modules on a refrigerant system wire X Y daisy chain only to the Header outdoor unit of each refrigerant system See Figure 6 Connect field supplied 24VAC power copper wire to...

Page 6: ...rational the controller may be powered up for initial login and basic configuration Login Log in from the unit s home screen with user name superAdmin The default password is 66668888 See Figure 11 Fi...

Page 7: ...of the following Home Screens will display depending on whether the user chose Bryant or Carrier 5 Select Setting Hardware Testing The following screen will display 6 Select Carrier or Bryant and sele...

Page 8: ...or change at any time specifications or designs without notice and without incurring obligations Catalog No 17 40VM9006 01 Printed in China Form 40VM 5SIR1 Pg 8 09 17 Replaces 40VM 5SI Refer to the U...

Reviews: