background image

9

Step 2 — Make Piping Connections

Access to piping is available through the access panels at the

front, top, or end of the vertical unit (horizontal access from bot-

tom or side). Route piping through the pipe tunnel or the unit’s

back panel or floor panel. Metal blank-off panels must be

trimmed to complete piping installation. Metal blank-off panels

must be retrofitted around the piping to restore installation integ-

rity. All piping connections must be performed by qualified per-

sonnel in accordance with local and national codes.

DRAIN CONNECTIONS
Condensate drain connections are located on each end of the

drain pan near the bottom of the unit. Access by removing the

end panel. Condensate drain line must be 

3

/

4

-in. copper tubing,

galvanized pipe, PVC or similar plastic pipe. Install drain line in

accordance with all applicable codes. Insulate the drain line to

prevent sweating. See Fig. 8 for typical drain trap construction.

Fig. 8 — Typical Condensate Drain Trap 

Condensate

NOTE: Drain pan is sloped toward the connections of the largest

coil or toward the connections of the DX (direct expansion) coil.

In a unit with 2-row right hand coils and 4-row left-hand coils for

example, the drain pan is sloped down to the left-hand side. The

uphill connection is sealed with a plug. The downhill field con-

nection is covered with a plastic cap except when the drain pan is

stainless steel, then both connections are sealed with a plug. Re-

move cap (or plug on stainless steel) on the downhill connection.

Do not remove the high side drain connection plug. The slope

may be reversed in the field by removing the drain pan screws (2

per side), using the opposite set of holes to install the pan, and

sealing the uphill connection. See Fig. 9 and 10.
Units with cooling coils require traps to prevent air from entering

the condensate fitting and preventing proper drainage. Drain

must be sloped downhill from the unit a minimum of 

1

/

8

-in. per

ft. Drain must be free and clear at all times. It is not recommend-

ed to tie multiple units into one condensate line due to potential

for overflow.

Fig. 9 — Drain Pan Connection Holes, Inside View

Fig. 10 — Drain Pan Connection Holes, Outside 

View

WATER SUPPLY/RETURN CONNECTIONS
Install piping in accordance with all applicable codes. All piping

must be supported separately from coils.
Water supply must be connected so that entering water is on

leaving-air side of coil. See the connection labels on the unit to

locate the inlet. Coils must be adequately vented to prevent air

binding. Be sure valves are in proper operating position and are

easily accessible for adjustment.
If coil and valve package connections will be made with a solder

joint, care should be taken to ensure that components in the valve

package are not subjected to high temperatures which may dam-

age seals or other materials. Many 2-position electric control

valves are provided with a manual operating lever. This lever

should be in the OPEN position during all soldering operations.
If coil connection is made with a union, the coil side of the union

must be prevented from turning (it must be backed up) during

tightening.

 Do not overtighten! Overtightening will distort (egg

shape) the union seal surface and destroy the union.

NOTE: A freezestat is factory-installed when a hot water/steam

coil is installed.
STEAM CONNECTIONS
On units with steam heating coils, the maximum steam pres-

sure applied to the unit should never exceed 6 psig. Carrier rec-

ommends float and thermostatic ("F&T") type steam traps for

best results. However, other styles may work and selection is

the responsibility of the customer. Sizing and selection of the

steam trap and design of the steam system piping should be

done with the recommendation of the steam trap supplier. A

CAUTION

When making solder connections, care must be taken to

prevent the dripping of solder or other debris onto the insu-

lation, control wiring, control box, actuators, and DDC

(Direct Digital Controls) controller (if so equipped). When

using a torch anywhere in the unit, care must be taken to

not burn any components.

CAUTION

Insulate drain lines to prevent condensate. Care must be

taken to avoid interference with control panel on left side

drain. Failure to comply could result in equipment damage.

2-1/2" MIN

3

/4"

GALVANIZED PIPE

3

/4"

PVC OR COPPER

2-1/2" MIN

1-1/2" MIN

1-1/2" MIN

DRAIN PAN

UPPER HOLE

S

LOWER
HOLE

S

NOTE: Reverse slope by reversing connections on each end of the
pan.

UPPER HOLE

S

LOWER HOLE

S

Summary of Contents for 40UH050

Page 1: ...ters Only trained and qualified service personnel should perform all other operations See Fig 1 for Proposition 65 warning label When installing this unit observe precautions in the literature tags an...

Page 2: ...s 2 Make sure wall behind unit is smooth and plumb if necessary install furring strips on walls with irregular surfaces or mullions Furring strips must be positioned behind mounting holes in unit Fast...

Page 3: ...Nominal Size in 2 in thick 93 4 x 361 4 93 4 x 481 4 93 4 x 601 4 93 4 x 721 4 93 4 x 721 4 Quantity 1 1 1 1 1 40UV SHIPPING WEIGHT Approx lb 165 8 in Deep Unit 330 400 480 590 660 217 8 in Deep Unit...

Page 4: ...100 1000 74 48 46 74 480 460 125 1250 86 60 61 81 590 570 150 1500 98 72 78 47 660 640 2 95 2 00 12 10 TYP W1 SEE NOTE 2 1 00 UNIT SHOWN WITH 1 00 END PANELS MOTOR ELECTRICAL BOX RECESSED RETURN AIR K...

Page 5: ...non fused disconnect switch 5 Connection hand is determined by facing dis charge of unit 27 30 30 00 19 37 2 40 13 75 7 02 1 74 PIPING TUNNEL 2 00 3 00 12 00 TYP 1 00 UNIT SHOWN WITH 1 00 END PANELS W...

Page 6: ...62 36 31 67 420 405 100 1000 74 48 46 74 500 480 125 1250 86 60 61 81 620 600 150 1500 98 72 78 47 690 670 2 00 W1 SEE NOTE 2 BOTTOM VIEW LEFT SIDE VIEW REAR VIEW W2 0 92 18 59 TYP 21 86 TYP 6 75 TYP...

Page 7: ...AL BOTTOM SERVICE PANELS SEE NOTE 3 TOP VIEW SEE NOTE 2 LEFT SIDE VIEW SIZE 200 PIPE TUNNEL 4 00 7 50 39 50 43 50 W6 UNIT 40UH AIRFLOW cfm DEPTH in DIMENSIONS in APPROXIMATE SHIPPING WEIGHT lb APPROXI...

Page 8: ...TE 3 43 50 16 63 TOP VIEW SEE NOTE 2 LEFT SIDE VIEW SIZE 200 PIPE TUNNEL 47 50 4 00 7 50 NOTES 1 All dimensions are in inches 2 Dimension does not include end panels 3 Two bottom panels provided for s...

Page 9: ...ig 10 Drain Pan Connection Holes Outside View WATER SUPPLY RETURN CONNECTIONS Install piping in accordance with all applicable codes All piping must be supported separately from coils Water supply mus...

Page 10: ...applica tions Valve packages must always be field insulated to prevent sweating See Fig 12 for piping recommendations Step 3 Make Electrical Connections Refer to unit serial plate for required supply...

Page 11: ...GEND S Supply R Return Union NOTE Factory supplied vacuum breaker assembly Field install in vertical orientation with flow arrow up and piping down so that ball seats with gravity Equalizer line and t...

Page 12: ...110 24 4 25 6 3 240 3 60 3 12 1 97 15 1 20 4 2 4 17 9 106 22 4 25 5 6 5 22 2 115 27 8 30 7 0 6 22 2 124 27 8 30 8 4 460 3 60 3 6 0 97 7 5 15 4 2 4 8 9 106 11 1 15 5 6 5 11 0 115 13 8 15 7 0 6 11 0 124...

Page 13: ...3 45 11 9 240 3 60 3 21 3 96 26 6 30 8 0 4 32 4 104 40 5 45 10 7 5 40 5 112 50 7 60 13 3 6 40 5 121 50 7 60 16 0 460 3 60 3 10 6 96 13 2 15 8 0 4 16 1 104 20 1 25 10 7 5 20 2 112 25 2 30 13 3 6 20 2...

Page 14: ...74 2 102 92 8 100 15 0 6 88 7 108 110 8 125 18 0 240 1 60 3 52 0 96 65 0 70 12 0 4 68 7 104 85 8 90 16 0 5 85 3 113 106 7 110 20 0 6 277 1 60 3 44 9 96 56 2 60 12 0 4 59 4 104 74 2 80 16 0 5 73 8 113...

Page 15: ...1 4 97 14 3 15 4 2 4 17 2 106 21 6 25 5 6 5 21 5 115 26 9 30 7 0 6 21 5 124 26 9 30 8 4 460 3 60 3 5 4 97 6 8 15 4 2 4 8 3 106 10 4 15 5 6 5 10 5 115 13 1 15 7 0 6 10 5 124 13 1 15 8 4 40UV UH075 at 7...

Page 16: ...6 27 3 30 8 0 4 33 0 104 41 2 45 10 7 5 41 1 112 51 4 60 13 3 6 41 1 121 51 4 60 16 0 460 3 60 3 10 6 96 13 3 15 8 0 4 16 2 104 20 2 25 10 7 5 20 3 112 25 3 30 13 3 6 20 3 121 25 3 30 16 0 40UV UH125...

Page 17: ...3 32 2 96 40 3 45 12 0 4 48 9 104 61 1 70 16 0 5 61 1 113 76 4 80 20 0 6 61 1 121 76 4 80 24 0 460 3 60 3 15 6 96 19 5 20 12 0 4 24 0 104 30 0 30 16 0 5 30 1 113 37 6 40 20 0 6 30 1 121 37 6 40 24 0 4...

Page 18: ...5 265 1 6 2 0 3 6 15 150 1 5 115 3 7 4 6 8 3 15 208 230 2 0 2 5 4 5 15 265 1 6 2 0 3 6 15 UNIT 40UV UH SIZE MOTOR Hp VOLTAGE FLA MCA MOP Amps MAX FUSE SIZE Amps 050 1 3 115 1 4 1 8 3 1 15 208 230 1 3...

Page 19: ...DX COILS Select Drawing NOTES 1 Make electrical installation in accordance with job diagram and in compliance with national and local electrical codes 2 Low limit thermostat LLT is installed on all u...

Page 20: ...X COILS SELECT DRAWING NOTES 1 Make electrical installation in accordance with job diagram and in compliance with national and local electrical codes 2 Low limit thermostat LLT is installed on all uni...

Page 21: ...FOR HARNESS WIRING BRN 513 SELECT DRAWING GRN NOTES 1 Make electrical installation in accordance with job diagram and in compliance with national and local electrical codes 2 Low limit thermostat LLT...

Page 22: ...CONNECTED TO REMOTE COMPRESSOR CONDENSER UNIT 3 1 DX1 BLU 517 3 LLR 3 1 2 8 9 ORN 518 GRA 519 LEGEND CBC Control Box Connection DDC Direct Digital Controls DISC Disconnect Switch DX Direct Expansion F...

Page 23: ...1 4 3 2 SEE CONTROL DIAGRAM FOR HARNESS WIRING BRN 513 GRN LEGEND CBC Control Box Connection DDC Direct Digital Controls DISC Disconnect Switch FR Fan Relay FU Fuse GND Ground PSC Permanent Split Capa...

Page 24: ...LLED ONLY ON UNITS WITH DX COILS 2 RED 503 RED 502 WHT BLK GRN LEGEND DISC Disconnect Switch DX Direct Expansion ECM Electronically Commutated Motor ESP External Static Pressure FU Fuse GND Ground LLR...

Page 25: ...K BLK 109 SEE NOTE 2 2 1 NOTES 1 Make electrical installation in accordance with job diagram and in compliance with national and local electrical codes 2 Low limit thermostat LLT is installed on all u...

Page 26: ...ESS WIRING BRN 505 BRN EC1 RED 514 RED 502 RED 503 MAX LOW HIGH LEGEND CBC Control Box Connection DDC Direct Digital Controls DISC Disconnect Switch EC Electronically Commutated ECM Electronically Com...

Page 27: ...CTED TO REMOTE COMPRESSOR CONDENSER UNIT 3 1 DX1 BLU 517 3 BRN 506 LLR 3 1 2 8 9 ORN 518 GRA 519 LEGEND CBC Control Box Connection DDC Direct Digital Controls DISC Disconnect Switch DX Direct Expansio...

Page 28: ...OTOR 11 5 BLK BRN 504 LEGEND CBC Control Box Connection DDC Direct Digital Controls DISC Disconnect Switch EC Electronically Commutated ECM Electronically Commutated Motor ESP External Static Pressure...

Page 29: ...507 RED 508 RED 508 FR Optional Field Provided and Installed Fan Relay Break wire RED 507 and connect as shown Do NOT break motor power wiring to start stop the fan motor as this will significantly d...

Page 30: ...without intended ductwork attached Ensure that units ducted to multiple openings have sufficient straight duct immediately after the unit FACTORY SETTINGS CHILLED WATER COIL APPLICATIONS Unit Speed A...

Page 31: ...older than the dew point of the surrounding air If a unit is start ed and is piped with low temperature chilled water in a hot hu mid atmosphere condensation will form on many parts of the unit In ord...

Page 32: ...posable filters See Table 1 for fil ter sizes PERMANENT FILTER FIBER TYPE 1 Tap on solid surface to dislodge heavy particles 2 Wash in hot water If needed use mild solution of com mercial solvent such...

Page 33: ...motor wire plugs are front facing on a vertical plane 10 Secure the 3 setscrews on the shaft coupling when the motor is properly positioned and the blower wheels are centered within their housing 11 R...

Page 34: ...SHROUD OPENING OVER MOTOR ELECTRICAL CONNECTIONS INSTALL MOTOR AND COOLING SHROUD ELECTRICAL CONNECTIONS FACING UNIT FRONT MOTOR SHAFT COUPLING FAN SHAFT 125 032 0 500 0 063 1 000 0 063 NOTES 1 All di...

Page 35: ...6 4 Re install two carriage bolts that attach the front brace to the frame sides See Item 6 in Fig 25 5 Rotate the fan shaft by hand to ensure that fans are unrestricted and can rotate freely Check fo...

Page 36: ...EMPERATURE SENSOR OPTIONAL OPENING DISCHARGE AIR TEMPERATURE SENSOR OPTIONAL OPENING MOTOR COUPLING SETCREW ACCESS MOTOR MOTOR ELECTRICAL BOX NOTES 1 Unit shown in vertical orientation Drawing applies...

Page 37: ...VIEW DETAIL A NOTES 1 Not all components shown for clarity 2 This drawing applies to 1500 cfm units only 3 Remove shaft motor and coupling prior to bearing removal 4 Refer to Fig 24 and 31 for motor...

Page 38: ...nto frames assembly 2 Tighten the four 5 16 in nuts retaining coil section to frame 3 Reconnect electric heat wiring in electric heat control box 4 Reconnect wiring to low limit thermostat 5 Replace t...

Page 39: ...LECTRICAL BOX MOTOR MOTOR COUPLING SETSCREW ACCESS DISCHARGE AIR TEMPERATURE SENSOR OPENING RETURN AIR TEMPERATURE SENSOR OPENING FRONT COIL BAFFLE NOTES 1 Unit shown in vertical orientation Drawing a...

Page 40: ...24 15 Ensure that motor shaft is perpendicular to motor blower endplate Tighten 5 16 in motor mount Fig 28 Item 7 Fig 29 Item 2 Fig 30 Item 2 nut Fig 28 Item 3 Fig 29 Item 5 Fig 30 Item 6 and bolt Fig...

Page 41: ...move shaft motor and coupling prior to removing bearing Refer to Removal and Re installation instructions 4 Install sleeve bearing with oil cup facing up and towards the rear of the assembly 5 Refer t...

Page 42: ...for clarity 2 Items no 7 10 and associated hardware not required for 40UV UH150 Refer to Fig 26 for 40UV UH150 in board bearing replacement 3 Install motor with capacitor facing up 4 Install sleeve b...

Page 43: ...tems no 8 11 and associated hardware not required for 40UV UH150 Refer to Fig 26 for 40UV UH150 in board bearing replacement 3 Install motor with electrical connections facing front of assembly 4 Inst...

Page 44: ...0 063 125 032 FAN SHAFT COUPLING MOTOR SHAFT FACE OF MOTOR FLUSH WITH FACE OF INSULATION MOTOR PSC BLOWER SECTION FRONT VIEW SHAFTED END FACE COUPLING INSIDE FACE COUPLING FACE MOTOR BEARING FACE NOT...

Page 45: ...em 10 Fig 30 Item 11 Attach to bearing bracket using hex nuts and bolts Align oil cup port with matching cutout in bearing bracket 9 Use 7 16 in socket to slide replacement bearing Fig 28 Item 14 Fig...

Page 46: ...PERATURE LIMIT SWITCH SEE NOTES 2 3 SEE CAUTION CAUTION DO NOT CHANGE LIMIT SWITCH CAPILLARY TUBE LOCA TION LIMIT SWITCHES MAY NOT FUNCTION PROPERLY LEGEND 1 Insulation 2 Left Blower Section End 3 Blo...

Page 47: ...motor shroud sheet metal cover Fig 28 Item 6 Fig 30 Item 4 using two 5 16 in hex nuts if using ECM motor Align window with receptacles on motor Motor control module could overheat and fail if oper at...

Page 48: ...l 4 Replace 1 4 in head screws attaching OA actuator to damper shaft OR attaching locking quadrant assembly to damper shaft Replace OA actuator or locking quadrant assembly 5 Replace the two 1 4 in he...

Page 49: ...COIL BAFFLE DISCHARGE AIR TEMPERATURE SENSOR OPENING MOTOR COUPLING SETSCREW ACCESS MOTOR MOTOR ELECTRICAL BOX COIL SECTION DAMPER SECTION BLOWER SECTION DAMPER SECTION KICKPLATE NOTES 1 Unit shown in...

Page 50: ...to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53400048 01 Printed in U S A Form 40UV UH 11SI Pg 50 8 18 Replaces 40UV U...

Page 51: ...IS EXPANSION VALVE BULB PROPERLY INSTALLED AND INSULATED PIPING CHECKLIST IS EXPANSION VALVE BULB PROPERLY INSTALLED AND INSULATED IS UNIT PIPING CORRECTAND INSULATED TO PREVENT CONDENSATION ARE THE C...

Page 52: ...ge at any time specifications or designs without notice and without incurring obligations Catalog No 04 53400048 01 Printed in U S A Form 40UV UH 11SI Pg CL 2 8 18 Replaces 40UV UH 10SI Carrier Corpor...

Reviews: