4-2. Operation section

Push each button to select a desired operation.

• The control saves commands in memory and after the initial setting, there is no need for any additional 

settings unless changes are desired. The air conditioner can be operated by pushing the 

 button.

1

 button (Temperature set button)

Adjusts the set point.
Select the desired set point by pushing 

TEMP. 

 

or TEMP. 

.

2

 button (Timer set button)

Use to setup the timer.

3

 button (Filter reset button)

Resets “

” display after cleaning filter.

4

 button (Test button)

Use only for service. 
(During normal operation, do not use this button.)

5

 button

When the button is pushed, the operation starts, and it 
stops by pushing the button again.
When the operation has stopped, the operation lamp and 
all the displays disappear.

6

Operation lamp

Green light illuminates when unit is on.
Although it flashes when operating the protection device 
or an error occurs.

7

 button (Operation mode button)

Selects desired operation mode.

8

 button (Fan speed button)

Selects the desired Fan speed.

9

 button (Ventilation button)

Not available.
• “

” is displayed on the remote controller when this 

button is pushed.

10

 button (Power save operation)

Use to initiate power saving mode.

11

 button (Unit / Louver select button)

Selects a unit number (left) and louver number (right).

UNIT:

 

Selects an indoor unit when adjusting wind direction 
multiple indoor units are controlled with one remote 
controller.

LOUVER: 
Selects a louver when setting wind direction 
adjustment independently.

12

 button (Swing / Louver direction 

button)

Selects automatic swing or setting the louver 
direction.

OPTION:

Remote controller sensor

Usually the temperature sensor of the indoor unit senses the 
temperature. The temperature on the surrounding of the 
remote controller can also be sensed.
For details, contact the dealer from which you have 
purchased the air conditioner.

8

6

4

3

2

7

10

12

1

11

4-3. Correct usage

When the air conditioner is used for the first time or when the setting is changed, follow the steps below. Settings are saved in 
memory and are displayed anytime the unit is turned on by pushing the 

 button.

Preparation

• When the circuit breaker is turned on, the partition lines are displayed on the remote controller.

* After the circuit breaker is turned on, the remote controller does not accept any commands for approx. 

1 minute, this is not a failure.

REQUIREMENT

When the air conditioner is re-powered after it has not been used for a long period, turn on the circuit breaker at least 12 hours 
before starting the air conditioner.

Start

1

Push

 

 

button.

The operation lamp illuminates, and the operation 
starts.

2

Select an operation mode with the “

” 

button.

One push of the button, and the display changes 
in the order shown below.

3

Select fan speed with “

” button.

One push of the button, and the display changes 
in the order shown below.

• When fan is in “

Auto”, fan speed is 

adjusted based on difference between set point 
and room temperature.

• The temperature sensor detects the return air 

temperature at the indoor unit, which differs 
from the room temperature depending on the 
installation condition.
Set point is a target of room temperature. 
(

 “Auto” is not selectable in the Fan 

mode.)

4

Select the set point temperature by pushing 
the “TEMP. 

” or “TEMP. 

” buttons.

Stop

Push

 

 

button.

The operation lamp goes off, and the operation stops.
In the Cool, Dry, or Auto (cooling) mode, the fan runs 
for 10 minutes (or more) for self clean operation.

NOTE

Auto Changeover

• When in Auto Mode, the unit selects the operating mode (cooling or fan only) based on the user set point temperature.
• If the Auto mode is uncomfortable, you can select the desired conditions manually.

Cooling

• If there is a demand for cooling, unit will start approximately 1 minute after mode is selected.

When restarting the operation after stop

When the unit is attempted to restart immediately after it was stopped, the unit can not start for approx. 3 minutes this is to 
protect the compressor.

SET

TIME

TIMER SET

TEST

FILTER

RESET

TEMP.

CL

FAN

SAVE

SWING/FIX

VENT

MODE

ON / OFF

UNIT  LOUVER

4

n

a

F

y

r

D

o

t

u

A

Cool

      Auto

High

Med.

Low

24-EN

23-EN

1115350208_EN-TH.indb   12

1115350208_EN-TH.indb   12

3/29/2559 BE   6:54 PM

3/29/2559 BE   6:54 PM

Summary of Contents for 40TSV0131UP

Page 1: ...4 way Cassette type 40TSV0131UP 40TSV0181UP 40TSV0241UP 40TSV0361UP 40TSV0401UP 1115350208 English Portugu s Owner s Manual 1 English Espa ol 23 For commercial use 1115350208_EN TH indb Cover1 111535...

Page 2: ...hildren with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person resp...

Page 3: ...he refrigerant handling and piping work involved in installation relocation and removal has the quali cations pertaining to this refrigerant handling and piping work as stipulated by the local laws an...

Page 4: ...Since there is high voltage inside the unit you may get electric shock when removing the cover and main unit Use of a stand more than 50 cm high to clean the filter of the indoor unit or to carry out...

Page 5: ...r being used for a long time Leaving them such condition may result in the unit s falling down and causing injury Do not leave flammable sprays or other flammable materials near the air conditioner an...

Page 6: ...fan speed When you select AUTO the fan speed is automatically adjusted according to the room temperature You can also manually select the desired fan speed from among five settings LOW LOW MED MED HI...

Page 7: ...ts Press the Hi POWER button to start and press it again to stop the operation 7 PRESET display Indicated when memorizing the preferred operation mode or when it has been memorized Also this icon is i...

Page 8: ...aving a slight gap between the wall and the screw head and hang the remote controller by inserting the screw head into the specified position on the back 3 4 Signal receiving unit The signal receiving...

Page 9: ...ed temperature The fan speed display indicates The OPERATION lamp green on the signal receiving unit lights and operation starts after approximately 3 minutes Stop START STOP button Press this button...

Page 10: ...leep and start it again in the morning when you wake up or you return home Example To stop the air conditioner and start it again next morning Setting combined TIMER 1 Press the OFF TIMER button to ad...

Page 11: ...on is reserved Hi POWER mode is not available for group control When Hi POWER is transmitted to the Header indoor unit the receiving sound is heard but the Hi POWER mode will not be performed Please c...

Page 12: ...nder to clean the air filter 10 Fan speed display The selected fan speed mode is displayed 11 Set temperature display The selected set temperature is displayed 12 Power saving mode display Limits comp...

Page 13: ...low the steps below Settings are saved in memory and are displayed anytime the unit is turned on by pushing the button Preparation When the circuit breaker is turned on the partition lines are display...

Page 14: ...0 hours Total 34 hours r e m i t n O r e m i t f f O Repeat Off timer No display Off Off On Number of days Time 4 5 Power saving mode Case with wired remote controller The power saving mode saves ener...

Page 15: ...r How to set up the louver direction 1 Push during operation The louver direction changes for every push of the button In COOL DRY operation Direct the louver adjustment plate of up down wind directio...

Page 16: ...e to keep the indoor unit clean The self clean time varies with the cooling dry Auto cooling operation time as follows is displayed on the remote controller during self clean operation The operation l...

Page 17: ...te controllers for the respective air conditioners when the 2 air conditioners are closely installed Wireless remote controller B setup 1 Push the temporary operation button to start the air condition...

Page 18: ...the louvers 4 Push the button 5 Push the button to finish the setting 2 1 4 5 3 Swing setup code Swing of louvers 0001 Standard swing Factory default g n i w s l a u D 2 0 0 0 g n i w s e l c y C 3 0...

Page 19: ...1 2 Unit No 1 3 Unit No 1 4 1 0001 2 0002 3 0003 5 0005 4 0004 0001 0005 Louver position code Louver No 03 01 02 04 Refrigerant pipe Drain pipe Electrical control box Releasing the louver lock Set 000...

Page 20: ...or units of the air conditioner in use be cleaned and maintained regularly to ensure efficient operation of the air conditioner When the air conditioner is operated for a long time periodic maintenanc...

Page 21: ...Turn on the power switch if it is off The air conditioner is in the ON timer operation Cancel the timer operation The batteries of the remote controller have been exhausted Replace the batteries The L...

Page 22: ...for initial 3 minutes after the main power switch circuit breaker is turned on for re starting the air conditioner Auto restart operation This air conditioner is equipped with an Automatic restarting...

Page 23: ...ar a chemicals factory or in a place subject to combustion emissions Corrosion may be generated on the aluminum fin and copper pipe of the heat exchanger Do not install the air conditioner near an obs...

Page 24: ...1 8 1 25 2 27 3 27 3 1 27 3 2 28 3 3 29 3 4 29 3 5 30 4 33 4 1 33 4 2 34 4 3 34 4 4 35 4 5 35 5 36 6 37 7 38 8 A B 38 9 39 10 41 11 42 12 43 13 44 1115350208_EN TH indb 23 1115350208_EN TH indb 23 3...

Page 25: ...e servicing CAUTION High temperature parts You might get burned when removing this panel CAUTION Do not touch the aluminum fins of the unit Doing so may result in injury CAUTION BURST HAZARD Open the...

Page 26: ...6 TH 5 TH 25 1 OFF OFF 50 OFF OFF ON OFF ON OFF ON 1115350208_EN TH indb 25 1115350208_EN TH indb 25 3 29 2559 BE 6 54 PM 3 29 2559 BE 6 54 PM...

Page 27: ...8 TH 7 TH EN TH TH 26 3 9 10 Q 1115350208_EN TH indb 26 1115350208_EN TH indb 26 3 29 2559 BE 6 54 PM 3 29 2559 BE 6 54 PM...

Page 28: ...1 1 2 3 MODE A Auto Cool Dry Fan only A 4 30 C 17 C 5 FAN AUTO 5 LOW LOW MED MED HIGH 5 LOW LOW MED MED Dry AUTO 6 SWING SWING 7 FIX 8 OFF 9 ON 10 SET 11 CLR 12 Hi POWER Cool 1115350208_EN TH indb 27...

Page 29: ...Cool Dry Fan only 3 17 C 30 C Fan only 4 AUTO 5 LOW LOW MED MED HIGH Dry 5 6 Hi POWER High Power Hi POWER 7 P 8 Q X 1 2 2 R03 AAA X 2 R03 AAA 1 1 3 2 X Q AM 0 00 ON OFF 2 1 1 ON OFF ON OFF 1 10 2 1115...

Page 30: ...14 TH 13 TH 29 Q ON OFF 3 2 1 1 CLOCK 2 ON OFF ON OFF 1 10 3 3 3 Q 8 8 1 2 6 15 Q 3 4 1 36 2 3 4 5 6 1115350208_EN TH indb 29 1115350208_EN TH indb 29 3 29 2559 BE 6 54 PM 3 29 2559 BE 6 54 PM...

Page 31: ...ool Fan only 3 FAN ONLY 4 FAN LOW LOW MED MED HIGH 3 FAN ONLY X 10 Q X 2 3 1 1 2 MODE Dry 3 3 X 10 Q X 2 3 1 4 1 2 MODE A 3 4 FAN LOW LOW MED MED HIGH 3 X 10 1115350208_EN TH indb 30 1115350208_EN TH...

Page 32: ...X ON OFF 2 3 1 1 ON OFF 10 1 2 3 15 30 X W 1 OFF 2 ON 3 W 1 ON 2 OFF 3 X W 1 ON 2 OFF 3 4 3 3 X X ON OFF OFF ON OFF timer 3 1115350208_EN TH indb 31 1115350208_EN TH indb 31 3 29 2559 BE 6 54 PM 3 29...

Page 33: ...WER high power operation 1 X 1 Hi POWER Hi POWER Hi POWER X 1 Hi POWER Hi POWER Hi POWER Hi POWER Q 1 1 PRESET 3 P Q ON OFF 1 1 SLEEP 1 3 5 9 1115350208_EN TH indb 32 1115350208_EN TH indb 32 3 29 255...

Page 34: ...22 TH 21 TH 33 4 8 4 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 01 02 03 04 20 1 1 1115350208_EN TH indb 33 1115350208_EN TH indb 33 3 29 2559 BE 6 54 PM 3 29 2559 BE 6 54 PM...

Page 35: ...TH 23 TH EN TH TH 34 4 2 1 2 3 4 5 6 7 8 9 10 11 12 4 3 Q 1 12 1 2 3 Auto Auto 4 Cool Dry Auto 10 Auto Auto 1 3 1115350208_EN TH indb 34 1115350208_EN TH indb 34 3 29 2559 BE 6 54 PM 3 29 2559 BE 6 54...

Page 36: ...5 30 24 1 168 7 0 5 23 5 1 24 2 0 5 30 0 5 23 5 1 24 168 23 5 1 34 2 1 24 10 34 3 4 5 4 5 Q 1 4 2 1 1 1 2 1 3 1 4 3 1 100 50 75 4 5 75 1115350208_EN TH indb 35 1115350208_EN TH indb 35 3 29 2559 BE 6...

Page 37: ...H EN TH TH 36 5 COOL Q 1 1 FIX FIX FIX FIX 1 1 SWING SWING SWING FIX SWING FIX FIX 10 Q 1 1 SWING 1 2 1 1 1 2 1 3 1 4 1115350208_EN TH indb 36 1115350208_EN TH indb 36 3 29 2559 BE 6 54 PM 3 29 2559 B...

Page 38: ...30 TH 29 TH 37 X 1 1 1 1 2 1 3 1 4 2 3 4 5 6 10 10 1 1 1 2 START STOP 1115350208_EN TH indb 37 1115350208_EN TH indb 37 3 29 2559 BE 6 54 PM 3 29 2559 BE 6 54 PM...

Page 39: ...32 TH 31 TH EN TH TH 38 7 1 2 8 A B 2 B 1 2 3 00 4 MODE B 00 B A A A B 00 1115350208_EN TH indb 38 1115350208_EN TH indb 38 3 29 2559 BE 6 54 PM 3 29 2559 BE 6 54 PM...

Page 40: ...34 TH 33 TH 39 9 Q 1 4 2 1 1 1 2 1 3 1 4 3 0001 0002 0003 0000 4 5 W W W 1115350208_EN TH indb 39 1115350208_EN TH indb 39 3 29 2559 BE 6 54 PM 3 29 2559 BE 6 54 PM...

Page 41: ...2 1 1 1 2 1 3 1 4 3 4 4 5 5 2 3 6 0001 0005 F1 CODE No 01 Q 0000 4 1 3 5 6 X 1 4 01 CODE No 2 1 1 1 2 1 3 1 4 3 CODE No 45 4 0000 0002 5 6 1115350208_EN TH indb 40 1115350208_EN TH indb 40 3 29 2559 B...

Page 42: ...38 TH 37 TH 41 10 X 1 2 2 START STOP ON OFF 3 1 2 3 3 1115350208_EN TH indb 41 1115350208_EN TH indb 41 3 29 2559 BE 6 54 PM 3 29 2559 BE 6 54 PM...

Page 43: ...40 TH 39 TH EN TH TH 42 11 ON OFF Low Fan Q 0 5 1115350208_EN TH indb 42 1115350208_EN TH indb 42 3 29 2559 BE 6 54 PM 3 29 2559 BE 6 54 PM...

Page 44: ...Q X X 4 1 4 01 CODE No CHECK Unit No 2 CODE No 01 04 3 W 12 W 3 3 3 W 3 W W 8 W W W W 12 W 15 C 46 C 21 C 32 C 15 C 24 C 80 1115350208_EN TH indb 43 1115350208_EN TH indb 43 3 29 2559 BE 6 54 PM 3 29...

Page 45: ...44 TH 43 TH EN TH TH 44 13 1 80 1115350208_EN TH indb 44 1115350208_EN TH indb 44 3 29 2559 BE 6 54 PM 3 29 2559 BE 6 54 PM...

Page 46: ...45 MEMO 1115350208_EN TH indb 45 1115350208_EN TH indb 45 3 29 2559 BE 6 54 PM 3 29 2559 BE 6 54 PM...

Page 47: ...46 EN TH MEMO 1115350208_EN TH indb 46 1115350208_EN TH indb 46 3 29 2559 BE 6 54 PM 3 29 2559 BE 6 54 PM...

Page 48: ...1115350208 1115350208_EN TH indb 47 1115350208_EN TH indb 47 3 29 2559 BE 6 54 PM 3 29 2559 BE 6 54 PM...

Reviews: