background image

15

Fig. 6 — Preferred Suspension Technique

Refrigerant Piping

See Tables 1-for refrigerant pipe connection sizes. For ease in

brazing, it is recommended that all internal solder joints be made

before unit is placed in final position.

The 40RU direct-expansion units have internal factory-installed

thermostatic expansion valves (TXVs), distributors, and nozzles

for use with R-410A. See Table 10 for part numbers. Knockouts

are provided in the unit corner posts for 40RU refrigerant piping.

See Fig. 7, which also lists recommended knockouts and access

holes to use for each 40RU unit size. Recommended fittings are

listed in Table 11.

The sensor bulb capillary tubes must be routed from the TXVs in

-

side the unit through one of the piping access holes. Clamp the

TXV sensor bulb on a vertical portion of the suction line, outside

the unit. (See Fig. 8.)

Refrigerant and Chilled Water Piping Access 

The 40RU Series units come with standard knockouts for refriger

-

ant and chilled water piping. These knockouts are located on both

sides of the unit for installation flexibility. The standard knockouts

provide sufficient access to the unit’s coils for all 40RUA*07, 08,

12, 14, and 16 and 40RUQ*07, 08, and 12 units. 40RUQ*16 units,

as well as 40RUS*08, 12, 14, and 16 units require additional holes

that  must  be  field-fabricated  to  accommodate  the  piping.  See

Fig. 7 for the positions and dimensions of the additional access

holes required for 40RUQ*16 and 40RUS units. Recommended

access hole use is also listed for all units. Note that

 

Fig. shows

the access holes on the control-box side of the unit; this is the side

of the unit with the coil headers, so it is used most often for piping

access.

NOTE: Be sure to remove the styrofoam shipping pad from the

TXV. Verify that it has been removed. (See Fig. 4.)

The 40RU Series evaporator coils have a face-split design. Ensure

that lower circuit of coil is first on/last off when connected to the

condensing unit and/or system controls. (See Fig. 9.)

External  TXV  equalizer  connections  are  provided  and  factory-

brazed into the coil suction manifolds.

If suction line must be horizontal, clamp bulb to suction line at

least 45 degrees above bottom, at approximately the 4 o’clock or

8 o’clock position. (See Fig. 10.)

NOTE: Dimensions in [   ] are millimeters.

UNIT SIZES 07 - 12

OVERHEAD SUSPENSION ACCESSORY

UNIT SIZES 14 - 16

IMPORTANT: Never attach the sensor to the suction manifold.

Do NOT mount the sensor on a trapped portion of the suction

line.

Summary of Contents for 40RU 07-16

Page 1: ...performed by trained service personnel When working on air conditioning equipment observe precautions in the literature tags and labels attached to the unit and other safety precautions that may apply...

Page 2: ...1 2 ft 762 mm Right Side 3 1 2 ft 1067 mm Left Side 2 1 2 ft 762 mm For units equipped with an economizer refer to the accessory installation instructions for additional clearance requirements Be sur...

Page 3: ...only 4 Example 0 R U A A 1 2 A 1 A 6 0 A 0 A 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Packaging 0 Standard Future Use A Standard Cabinet Paint 0 None 1 Painted Future Use A Standard Revision Num...

Page 4: ...4 Fig 2 Dimensions Sizes 07 12...

Page 5: ...5 Fig 2 Dimensions Sizes 07 12 cont...

Page 6: ...6 Fig 3 Dimensions Size 14 and 16...

Page 7: ...7 Fig 3 Dimensions Size 14 and 16 cont...

Page 8: ...12 16 Split Type Percentage Face 50 50 Face 50 50 Face 50 50 Rows Fins in 4 15 4 15 4 15 4 15 4 15 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 1 1 8 1 1 1 8 2 1 1 8 2 1 1 8 2 1 1 8 DX Co...

Page 9: ...ts per Split 12 15 9 12 16 Split Type Percentage Face 50 50 Face 50 50 Face 50 50 Rows Fins m 4 591 4 591 4 591 4 591 4 591 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 1 1 8 1 1 1 8 2 1...

Page 10: ...Split 15 12 12 9 10 Split Type Percentage Face 50 50 Face 50 50 Rows Fins in 3 15 4 15 4 15 4 15 4 15 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 1 1 8 1 1 1 8 1 1 1 8 2 1 1 8 2 1 1 8 D...

Page 11: ...9 10 Split Type Percentage Face 50 50 Face 50 50 Rows Fins m 3 591 4 591 4 591 3 591 4 591 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 1 1 8 1 1 1 8 1 1 1 8 2 1 1 8 2 1 1 8 DX Coil Liqu...

Page 12: ...3 15 PIPING CONNECTIONS Quantity Size in Chilled Water In 1 1 3 8 ODF 1 1 3 8 ODF 1 1 3 8 ODF 2 1 3 8 ODM 2 1 3 8 ODM Chilled Water Out 1 1 3 8 ODF 1 1 3 8 ODF 1 1 3 8 ODF 2 1 3 8 ODM 2 1 3 8 ODM Stea...

Page 13: ...3 591 3 591 3 591 3 591 PIPING CONNECTIONS Quantity Size in Chilled Water In 1 1 3 8 ODF 1 1 3 8 ODF 1 1 3 8 ODF 2 1 3 8 ODM 2 1 3 8 ODM Chilled Water Out 1 1 3 8 ODF 1 1 3 8 ODF 1 1 3 8 ODF 2 1 3 8...

Page 14: ...suspension technique The unit needs support underneath to prevent sagging Unit Isolation Where extremely quiet operation is essential install isolators be tween floor and base of unit or between ceili...

Page 15: ...s coils for all 40RUA 07 08 12 14 and 16 and 40RUQ 07 08 and 12 units 40RUQ 16 units as well as 40RUS 08 12 14 and 16 units require additional holes that must be field fabricated to accommodate the p...

Page 16: ...ZE 8 GA 1 1113 12 3 16 1 G5 40RUA 08 4 Row 1 BBIZE 6 GA 1 1136 15 1 4 1 G5 40RUQ 08 4 Row 1 BBIZE 8 GA 1 1113 12 3 16 1 G5 40RUA 12 4 Row 2 BBIZE 4 GA 2 1135 9 1 4 2 G3 40RUQ 12 4 Row 2 BBIZE 5 GA 2 1...

Page 17: ...ng Radius Elbow 1 1 8 Nipple 12 L 1 1 8 Long Radius Elbow 40RUQ 12 1 Suction Lower 2 1 1 8 Street Elbow 2 Liquid Lower 5 8 Street Elbow 5 8 Nipple 5 1 2 L 5 8 Long Radius Elbow 3 Liquid Upper 5 8 Stre...

Page 18: ...le 7 L 1 3 8 Long Radius Elbow 7 Supply Upper 1 3 8 Long Radius Elbow 1 3 8 Nipple 11 3 4 L 1 3 8 Long Radius Elbow Table 11 Fitting Requirements cont UNIT ACCESS HOLE NO CONNECTION TYPE CIRCUIT FITTI...

Page 19: ...commended knockouts and access holes to use for each 40RUS unit size To size design and install chilled water piping consult the Carrier System Design manual See Fig 11 for an example of a typical in...

Page 20: ...static pressure created by fans preventing complete drainage Conditions will worsen as filters become dirty Install clean out plugs in trap Pitch drain line downward to an open floor drain or sump Pr...

Page 21: ...ontactor coil data Fig 14 Disconnect Switch and Unit Adjustment Slots Both Ends of Unit PVC Stub Unit Drain Connection WARNING Failure to follow this warning could result in personal injury or death D...

Page 22: ...40RUQ 16 208 230 3 60 187 253 3 7 2 76 10 2 13 0 20 460 3 60 414 506 3 7 2 76 4 8 6 0 15 575 3 60 518 632 3 0 2 24 3 8 5 0 15 Table 13 Electrical Data Alternate Motors Single Speed UNIT V PH Hz VOLTA...

Page 23: ...20 460 3 60 414 506 3 7 2 76 4 9 7 0 15 575 3 60 518 632 3 7 2 76 4 5 6 0 15 Table 15 Electrical Data Alternate Motors Two Speed UNIT V PH Hz VOLTAGE LIMITS FAN MOTOR POWER SUPPLY Hp kW FLA MINIMUM C...

Page 24: ...Size the Field Power Wiring between the heater TB1 and the 40RU indoor fan motor per NEC Article 430 28 1 or 2 depends on length of conduit between heater enclosure and 40RU power entry location Inst...

Page 25: ...on on the units corner post Fan motors are factory installed on all units Indoor fan contactors are located in the fan contactor box behind the side access panel See Fig 15 and 16 Wire the thermostat...

Page 26: ...using return air ductwork route return air duct to the unit s return air inlet near the filter rack using a canvas connection to prevent transmission of unit vibration If the duct blocks off the unit...

Page 27: ...27 Fig 18 Typical Fan Discharge Connections for Multiple Fan Units Fig 19 Duct Flange Installation...

Page 28: ...ntation When service is completed replace unit panels Panels Panels are fastened to unit frame with sheet metal screws Fan and coil compartment must be sealed tightly after service to prevent air from...

Page 29: ...Adjustment Loosen the 2 locking bolts holding the fan wheel hub to shaft See Fig 22 Position fan wheel in center of the fan housing and tight en locking bolts Clearance between wheel and housing shoul...

Page 30: ...ining water Reinstall plugs and side panel Alternative freeze protection methods follow Circulate hot water within the water coil s supply main or supplementary space heating Close off supply lines to...

Page 31: ...ical Manufacturers Association Table 19 Fan Motor Data 40RUA Q S Alternate Motor Single Speed English UNIT 40RUA Q 07 40RUA Q S 08 40RUS 10 40RUA Q S 12 40RUA S 14 40RUA Q S 16 208 230 1 60 Speed rpm...

Page 32: ...HZ 56HZ 56HZ Shaft Dia mm 15 9 22 2 22 2 22 2 22 2 22 2 NEMA National Electrical Manufacturers Association Table 22 Fan Motor Data 40RUA Q S Alternate Motor Single Speed SI UNIT 40RUA Q 07 40RUA Q S 0...

Page 33: ...ciency 40RUA S Two Speed Motor MOTOR HP EPACT MINIMUM MOTOR EFFICIENCY 2 4 80 0 2 9 86 5 3 7 83 6 5 0 89 5 89 5 EPACT Energy Policy and Conservation Act of 1992 Table 26 Fan Motor Data 40RUA S Standar...

Page 34: ...1 1 8 Table 30 Motor Efficiency 40RUQ Two Speed Motor MOTOR HP EPACT MINIMUM MOTOR EFFICIENCY 1 7 82 0 2 4 80 0 2 9 86 5 3 7 83 6 3 7 87 9 5 0 89 5 87 9 EPACT Energy Policy and Conservation Act of 199...

Page 35: ...SHAFTS CENTER DISTANCE IN 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 Table 34 Medium Static Drive Data 60 Hz English UNIT 40RUA Q 07 40RUA Q S 08 40RUS 10 40RUA Q S 12 40...

Page 36: ...1200 1200 Change per 1 2 Turn of Moveable Motor Pulley Flange 24 6 28 7 28 7 28 7 19 4 18 4 MAX FULL TURN FROM CLOSED POSITION 5 5 5 5 6 6 SHAFTS CENTER DISTANCE IN 10 44 12 32 10 44 12 32 10 44 12 3...

Page 37: ...0 20 0 20 0 20 0 20 0 20 0 Change per 1 2 Turn of Moveable Motor Pulley Flange 0 328 0 360 0 360 0 360 0 352 0 278 MAX FULL TURN FROM CLOSED POSITION 5 5 5 5 6 6 SHAFTS CENTER DISTANCE MM 265 313 265...

Page 38: ...0 0 97 833 1 08 2975 462 0 60 556 0 72 634 0 84 701 0 95 762 1 06 818 1 18 870 1 29 3400 527 0 80 612 0 93 684 1 06 748 1 18 806 1 30 860 1 41 910 1 53 3825 593 1 05 670 1 18 737 1 31 797 1 44 852 1 5...

Page 39: ...1 29 975 1 40 1018 1 50 1059 1 61 2975 919 1 40 965 1 51 1009 1 62 1050 1 73 1090 1 84 3400 957 1 64 1002 1 76 1044 1 87 1085 1 98 1124 2 10 3825 998 1 92 1041 2 04 1082 2 16 1122 2 27 1160 2 39 4250...

Page 40: ...00 7 70 0 45 9 27 0 54 10 57 0 63 11 68 0 71 12 70 0 79 13 63 0 88 14 50 0 96 1600 8 78 0 60 10 20 0 69 11 40 0 79 12 47 0 88 13 43 0 97 14 33 1 05 15 17 1 14 1800 9 88 0 78 11 17 0 88 12 28 0 98 13 2...

Page 41: ...3 0 88 15 52 0 96 16 25 1 05 16 97 1 12 17 65 1 20 1400 15 32 1 05 16 08 1 13 16 82 1 21 17 50 1 29 18 17 1 37 1600 15 95 1 23 16 70 1 31 17 40 1 40 18 08 1 48 18 73 1 57 1800 16 63 1 43 17 35 1 52 18...

Page 42: ...Fig 15 and 28 4 Reverse the procedure to install new filters To install new filters in larger units that have 2 fans follow the preceding steps but use the factory supplied filter hook to slide filter...

Page 43: ...ding main power supply TIGHT Y N ______________ HAVE OUTDOOR UNIT CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS Y N _________ INDOOR UNIT HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE...

Page 44: ...__ ____________ INDOOR UNIT ENTERING AIR DB TEMP ______________ ____________ INDOOR UNIT ENTERING AIR WB TEMP ______________ ____________ INDOOR UNIT LEAVINGAIR DB TEMP ______________ ____________ IND...

Reviews: