background image

13

Unit Positioning —

The unit can be mounted on the

floor for vertical application with return air entering the face of
the unit and supply air discharging vertically through the top of
the unit. The unit can also be applied in a horizontal arrange-
ment with return air entering horizontally and the supply air
discharging horizontally. When applying the unit in a horizon-
tal arrangement, ensure the condensate drain pan is located at
the bottom center of the unit for adequate condensate disposal.
See Fig. 4 for condensate connections for each unit position.

Typical positioning and alternate return air locations are

shown in Fig. 4. Alternate return air locations can be used by
moving the unit panel from the alternate return air location to
the standard return air location. Refer to overhead suspension
accessory drawing (Fig. 5) for preferred suspension technique.
The unit needs support underneath to prevent sagging.

Unit Isolation —

Where extremely quiet operation is

essential, install isolators between floor and base of unit, or
between ceiling and top section of unit.

Be sure that unit is level and adequately supported. Use

channels at front and sides of unit for reference points when
leveling.

Refrigerant

and

Chilled

Water

Piping

Access —

The 40RM Series units come with standard

knockouts for refrigerant and chilled water piping. These
knockouts are located on both sides of the unit for installation
flexibility. The standard knockouts provide sufficient access to
the unit’s coils for all 40RM and some 40RMQ units, however,
for 40RMQ016,028 and 40RMS units, additional holes must
be field-fabricated to accommodate the piping. See Fig. 6 for
the positions and dimensions of the additional access holes re-
quired for these units, including hole diameters and drilling
dimensions. Recommended access hole use is also listed for all
units. Note that Fig. 6 shows the access holes on the control-
box side of the unit; this is the side of the unit with the coil
headers, so it is used most often for piping access.

Refrigerant Piping —

See Tables 1A, 1B, 1D, 1E for

refrigerant pipe connection sizes. For ease in brazing, it is rec-
ommended that all internal solder joints be made before unit is
placed in final position.

The 40RM and 40RMQ direct-expansion units have inter-

nal factory-installed thermostatic expansion valves (TXVs),
distributors, and nozzles for use with R-22. See Table 2 for part
numbers. Knockouts are provided in the unit corner posts for
40RM and 40RMQ008 and 012 refrigerant piping. The
40RMQ016,024 and 028 units requires additional field-
fabricated piping access holes. See Fig. 6, which also lists rec-
ommended knockouts and access holes to use for each 40RM
and 40RMQ unit size. Recommended fittings are listed in
Table 3.

The sensor bulb capillary tubes must be routed from the

TXVs inside the unit through one of the piping access holes.
Clamp the TXV sensor bulb on a vertical portion of the suction
line, outside the unit. See Fig. 7.
NOTE: Be sure to remove the styrofoam shipping pad from
the TXV. Verify that it has been removed. See Fig. 3.

The 40RM Series evaporator coils have a face-split design.

Ensure that lower circuit of coil is first on/last off when
connected to the condensing unit and/or system controls. See
Fig. 8.

External TXV equalizer connections are provided and

factory-brazed into the coil suction manifolds.

If suction line must be horizontal, clamp bulb to suction line

at least 45 degrees above bottom, at approximately the
4 o’clock or 8 o’clock position. See Fig. 9.
NOTE: The 40RMQ units are supplied with factory-installed
thermostatic expansion valves and check valve bypasses. No
extra piping connections or kits are required to install the
40RMQ with a 38AQ, 38ARQ, or 38AQS condensing unit in a
heat pump system, however, some field-supplied components
may be required. See the following two sections.
HEAT PUMP SYSTEM PIPING — Addition of a liquid so-
lenoid valve (LLSV) is recommended. The LLSV must be a
bi-flow type suited for use in heat pump systems. Refer to the
38AQ, ARQ, AQS literature for recommended component
part numbers. Wire the solenoid valve in parallel with the com-
pressor contactor coil.

The LLSV must be installed at the outdoor unit with the

flow arrow pointed toward the outdoor unit (in-flow direction
for the heating mode.)
38ARQ DUPLEX/40RMQ024 HEAT PUMP SYSTEM
PIPING — Two 38ARQ012 heat pump condensing units may
be connected in a duplex arrangement with the 40RMQ024.
See Fig. 10. Ensure that the lower circuit of the 40RMQ coil is
the first on/last off by connecting to the “A” condensing unit
and by configuring the controls so that the “A” condensing unit
is the first on/last off.
38ARQ012/38AQS016 DUPLEX/40RMQ028 HEAT PUMP
SYSTEM PIPING — One 38ARQ012 and one 38AQS016
heat pump condensing unit may be connected in a duplex
arrangement with the 40RMQ028. See Fig. 10. The
40RMQ028 has a 60/40 face split coil. Ensure that the larger
coil section (connection “B”, Fig. 8) is connected to the
38QAS016 and the smaller coil section is connected to the
38AQS012. In addition, ensure that the lower circuit of the
40RMQ coil is the first on/last off by connecting to the “A”
condensing unit and by configuring (see 38ARQ,AQS installa-
tion instructions for more information) the controls so that the
“A” condensing unit is the first on/last off.
FILTER DRIER REQUIREMENTS FOR HEAT PUMP
SYSTEMS — The 38ARQ and 38AQS units do not include
filter driers. Filter driers must be field-supplied and field-
installed. The filter driers used with these systems must be
bi-flow types suited for use in heat pump applications. Refer to
the 38AQ,ARQ,AQS literature for recommended component
part numbers. See Fig. 11 for filter drier quantity and location
information.

IMPORTANT: Do NOT attempt to install unit with return
air entering top panel of unit. Condensate will not drain
from unit.

IMPORTANT:

Do

not

bury

refrigerant

piping

underground.

IMPORTANT: Never attach the sensor to the suction
manifold. Do NOT mount the sensor on a trapped portion
of the suction line.

LEGEND

Fig. 4 — Typical Unit Positioning

Accessory Line

Alternate Air Intake and Discharge

Air Intake and Discharge

Summary of Contents for 40RM007

Page 1: ...pment can be hazardous due to system pressures electrical components and equipment location elevated structures etc Only trained qualified installers and service mechanics should install start up and...

Page 2: ...unit for service clearance and airflow For units equipped with an economizer refer to the accessory installation instructions for additional clearance requirements Be sure floor wall or ceiling can su...

Page 3: ...5 0 DIRECT EXPANSION COIL Enhanced Copper Tubes Aluminum Sine Wave Fins Max Working Pressure psig 435 Face Area sq ft 6 67 8 33 10 0 13 25 17 67 19 88 24 86 29 83 No of Splits 1 1 2 2 2 2 2 2 No of C...

Page 4: ...Fins Max Working Pressure psig 435 Face Area sq ft 8 33 10 0 19 88 19 88 24 86 No of Splits 1 2 2 2 2 No of Circuits per Split 15 9 18 18 24 16 Split Type Percentage Face 50 50 Face 60 40 Rows Fins i...

Page 5: ...r Tubes Aluminum Sine Wave Fins Max Working Pressure psig 435 Face Area sq ft Upper 8 3 9 0 9 9 8 3 8 3 11 0 12 4 15 5 Face Area sq ft Lower 5 5 8 3 8 3 12 4 12 4 Rows Fins in 3 15 STEAM COIL Max Work...

Page 6: ...27 DIRECT EXPANSION COIL Enhanced Copper Tubes Aluminum Sine Wave Fins Max Working Pressure kPag 2999 Face Area sq m 0 62 0 77 0 93 0 93 1 64 1 85 2 30 2 77 No of Splits 1 1 2 2 2 2 2 2 No of Circuit...

Page 7: ...orking Pressure kPag 2999 Face Area sq m 0 77 0 93 1 85 1 85 2 30 No of Splits 1 2 2 2 2 No of Circuits per Split 15 9 18 18 24 16 Split Type Percentage Face 50 50 Face 60 40 Rows Fins m 3 591 4 591 4...

Page 8: ...g Pressure kPag 2999 Face Area sq m Upper 0 77 0 84 0 91 0 77 0 77 1 02 1 15 1 44 Face Area sq m Lower 0 51 0 77 0 77 1 15 1 15 Rows Fins m 3 591 3 591 3 591 3 591 3 591 3 591 3 591 3 591 STEAM COIL M...

Page 9: ...762 mm Local codes or jurisdiction may prevail 4 Liquid piping not supplied by Carrier 5 Duct flange is factory supplied and field installed 6 40RMS units may require alternate or addi tional field fa...

Page 10: ...Local codes or jurisdiction may prevail 4 Liquid piping not supplied by Carrier 5 Duct flange is factory supplied and field installed 6 40RMQ016 024 and 40RMS units may require alternate or additional...

Page 11: ...Left Side 2 ft 6 in 762 mm Local codes or jurisdiction may prevail 4 Liquid piping not supplied by Carrier 5 Duct flange is factory supplied and field installed 6 40RMQ028 and 40RMS may require altern...

Page 12: ...ve 60 Hz 028 size and 50 Hz 016 028 sizes WD Painted Alternate Motor and High Static Drive Packaging 1 Standard Domestic 3 Standard Export Revision Number 0 Original Nominal Capacity Tons kW 007 6 21...

Page 13: ...7 NOTE Be sure to remove the styrofoam shipping pad from the TXV Verify that it has been removed See Fig 3 The 40RM Series evaporator coils have a face split design Ensure that lower circuit of coil...

Page 14: ...14 NOTE Dimensions in are millimeters Fig 5 Preferred Suspension Technique UNIT SIZES 007 012 UNIT SIZES 014 024 UNIT SIZES 028 034 OVERHEAD SUSPENSION ACCESSORY...

Page 15: ...2 6 0 152 4 10 5 266 7 40RMQ016 024 028 3 5 6 7 11 8 28 6 11 8 28 6 13 4 44 5 3 25 82 6 6 125 155 6 10 38 263 7 40RMS028 034 5 6 7 8 21 2 63 5 21 2 63 5 21 2 63 5 21 2 63 5 6 0 152 4 9 625 244 5 13 38...

Page 16: ...r to Carrier System Design Manual for details 2 All wiring must comply with the applicable local and national codes 3 Wiring and piping shown are general points of connection guides only and are not i...

Page 17: ...2 C10 2 C15 40RMQ028 2 TDEBX11 2 1655 20 3 16 2 E15 40RM034 3 Row 4 Row 2 TDEBX16 2 TDEBX16 2 1126 2 1126 18 1 4 24 3 16 2 C12 2 C17 UNIT ACCESS HOLE NO CONNECTION TYPE CIRCUIT FITTINGS REQUIRED in 4...

Page 18: ...8 Street Elbow 5 8 Nipple 13 8 L 5 8 Long Radius Elbow 3 Liquid Upper 5 8 Street Elbow 5 8 Nipple 111 2 L 5 8 Long Radius Elbow 4 Suction Upper 11 8 Nipple 55 8 L 11 8 Long Radius Elbow 11 8 Nipple 13...

Page 19: ...d in Table 3 To access 40RMS coil vents and drains remove the unit side panel over the coil header Vent and drain plugs are on the top and bottom of header respectively See the Service section for inf...

Page 20: ...unit panels Observe all local sanitary codes As shipped the unit s condensate drain pan is NOT sloped towards the drain connection The pan slope must be changed to pitch towards the side of the unit...

Page 21: ...ring the mo tor mark the motor specifying 208 v or 230 v operation replac ing the 460 v sticker information on the units corner post Fan motors are factory installed on all units Indoor fan contactors...

Page 22: ...18 632 2 0 1 49 2 4 3 0 15 230 3 50 207 253 2 9 2 16 7 5 9 4 15 400 3 50 360 440 2 9 2 16 3 4 4 3 15 40RM 40RMS 014 208 230 3 60 187 253 2 9 2 16 7 5 9 4 15 460 3 60 414 506 2 9 2 16 3 4 4 3 15 575 3...

Page 23: ...4 15 400 3 50 360 440 2 9 2 16 3 4 4 3 15 40RMS 010 208 230 1 60 187 253 2 4 1 79 11 0 13 8 20 208 230 3 60 187 253 2 9 2 16 7 5 9 4 15 460 3 60 414 506 2 9 2 16 3 4 4 3 15 575 3 60 518 632 3 0 2 24...

Page 24: ...transmission of unit vibration If the duct blocks off the unit s access panel provide a slip joint in the ductwork to permit removal for servicing OUTDOOR AIR INLET CONNECTION Connect outdoor air inle...

Page 25: ...ooling heating system leaks Checking of all electrical connections Most unit service can be performed by removing one or both of the unit s side panels Coil cleaning or removal or insu lation cleaning...

Page 26: ...rtical and horizontal adjust ment Adjust belt s for correct deflection by loosening motor plate mounting bolts moving motor plate assembly forward or back and retightening bolts Press down on belt wit...

Page 27: ...ection methods follow Circulate hot water within the water coil s supply main or supplementary space heating Close off supply lines to unit and open a union or field supplied drain valve in the return...

Page 28: ...nd tilting them out of the filter track See Fig 15 and 26 4 Reverse the procedure to install new filters To install new filters in larger units that have 2 fans follow the preceding steps but use the...

Page 29: ...1 8 13 8 13 8 230 3 50 and 400 3 50 Speed rpm 1425 1425 1425 1425 1425 1425 1425 1425 1425 Hp 2 4 2 4 2 4 2 9 2 9 2 9 5 0 7 5 10 0 Frame NEMA 56Y 56Y 56Y 56Y 56Y 56Y 184T S213T S215T Shaft Dia in 5 8...

Page 30: ...00 3 50 Speed r s 23 75 23 75 23 75 23 75 23 75 23 75 23 75 23 75 23 75 Shaft kW 1 79 1 79 1 79 2 16 2 16 2 16 3 73 5 60 7 46 Frame NEMA 56Y 56Y 56Y 56Y 56Y 56Y 184T S213T S215T Shaft Dia mm 15 9 15 9...

Page 31: ...Pulley Flange 19 6 19 6 19 6 19 7 19 1 19 1 15 3 13 1 13 1 MAX FULL TURNS FROM CLOSED POSITION 5 5 5 5 5 5 6 6 6 SHAFTS CENTER DISTANCE in 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 1...

Page 32: ...0 1200 1200 1200 1200 1100 1100 Change per 1 2 Turn of Moveable Motor Pulley Flange 24 6 28 7 28 7 28 7 19 4 18 4 19 4 16 7 16 7 MAX FULL TURNS FROM CLOSED POSITION 5 5 5 5 6 6 6 6 6 SHAFTS CENTER DIS...

Page 33: ...3 16 4 Max Allowable Speed r s 20 0 20 0 20 0 20 0 20 0 20 0 20 0 18 3 18 3 Change per 1 2 Turn of Moveable Motor Pulley Flange 0 328 0 360 0 360 0 360 0 352 0 278 0 255 0 255 0 255 MAX FULL TURNS FR...

Page 34: ...N 5 5 5 5 5 5 6 6 6 SHAFTS CENTER DISTANCE in 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 9 12 10 99 6 67 9 43 6 67 9 43 UNIT 40RM 007 40RM 40RMQ 40RMS 008 40RMS 010 40RM 4...

Page 35: ...13 8 MAX FULL TURNS FROM CLOSED POSITION 5 5 5 6 5 6 6 6 6 SHAFTS CENTER DISTANCE in 10 44 12 32 10 44 12 32 10 44 12 32 9 16 10 99 9 16 10 99 9 16 10 99 8 16 10 02 6 67 9 43 6 67 9 43 UNIT 40RM 007...

Page 36: ...0 340 0 395 0 317 0 252 0 340 0 210 0 210 MAX FULL TURNS FROM CLOSED POSITION 5 5 5 5 5 6 5 6 6 SHAFTS CENTER DISTANCE mm 265 313 265 313 265 313 265 313 265 313 232 279 232 279 169 240 169 240 UNIT...

Page 37: ...535 0 99 623 1 31 704 1 69 775 2 08 838 2 47 896 2 86 5 700 550 1 23 587 1 37 664 1 71 740 2 11 809 2 55 872 2 99 929 3 43 6 250 596 1 59 630 1 74 700 2 09 770 2 51 837 2 97 899 3 45 955 3 94 016 4 50...

Page 38: ...51 1131 3 92 1181 4 32 4 300 925 2 73 980 3 11 1034 3 52 1084 3 92 1135 4 35 1184 4 78 5 000 950 3 26 1002 3 67 1052 4 09 1101 4 53 1148 4 98 1190 5 44 5 700 981 3 88 1031 4 33 1079 4 79 1125 5 25 116...

Page 39: ...4 10 38 0 98 11 73 1 26 12 91 1 55 13 97 1 84 14 93 2 13 2690 9 16 0 92 9 79 1 02 11 07 1 27 12 33 1 58 13 48 1 90 14 53 2 23 15 48 2 56 2950 9 93 1 18 10 50 1 30 11 66 1 56 12 83 1 87 13 95 2 22 14 9...

Page 40: ...92 19 68 3 22 2030 15 41 2 04 16 34 2 32 17 24 2 62 18 07 2 92 18 92 3 24 19 73 3 56 2360 15 84 2 43 16 70 2 74 17 54 3 05 18 35 3 38 19 14 3 71 19 83 4 06 2690 16 36 2 89 17 19 3 23 17 98 3 57 18 75...

Page 41: ...70 811 2 04 871 2 39 5 000 514 0 92 556 1 06 641 1 39 718 1 76 786 2 14 847 2 52 903 2 91 5 700 575 1 32 612 1 47 686 1 82 759 2 23 825 2 66 884 3 09 939 3 52 6 250 624 1 71 657 1 87 725 2 24 793 2 66...

Page 42: ...3 750 912 2 39 971 2 76 1028 3 14 1083 3 54 1135 3 95 1185 4 36 4 300 928 2 75 982 3 13 1036 3 53 1087 3 94 1138 4 37 1187 4 81 5 000 956 3 30 1007 3 71 1056 4 13 1104 4 56 1151 5 00 1196 5 46 5 700...

Page 43: ...10 68 1 04 11 96 1 31 13 09 1 60 14 11 1 88 15 05 2 17 2690 9 59 0 99 10 20 1 10 11 44 1 36 12 64 1 66 13 74 1 98 14 74 2 30 15 65 2 63 2950 10 40 1 28 10 96 1 39 12 09 1 67 13 21 1 98 14 27 2 33 15 2...

Page 44: ...06 17 13 2 34 18 04 2 64 18 91 2 94 19 75 3 25 2030 15 46 2 05 16 37 2 33 17 26 2 63 18 12 2 94 18 96 3 26 19 78 3 59 2360 15 94 2 46 16 78 2 77 17 60 3 08 18 40 3 40 19 18 3 73 19 94 4 07 2690 16 51...

Page 45: ...CTORY SUPPLIED PRESSURE DROP SI Bhp Brake Horsepower Input to Fan ESP External Static Pressure UNIT AIRFLOW Cfm PRESSURE DROP in wg 40RM 007 1 800 0 05 2 400 0 08 3 000 0 11 40RM 40RMQ 40RMS 008 2 250...

Page 46: ...ue or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 534 00003 Printed in U S A Form 40RM 23SI Pg 46 12 04 Replaces 40RM 22SI Book 1 4...

Page 47: ...RMINALS including main power supply TIGHT Y N _____ HAVE OUTDOOR UNIT CRANKCASE HEATERS BEEN ENERGIZED FOR 24 HOURS Y N ______ INDOOR UNIT HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE...

Page 48: ...___________________________________________________________________________________________ ______________________________________________________________________________________________________ _____...

Reviews: