1-7
62-10630
1.2 COMPRESSOR REFERENCE DATA
Model
TM 16
06VM306
06VM307
Displacement
163 cc
113 cc
130 cc
No. Cylinders
6
2
2
Weight
7 kg
37 kg
47 kg
Oil Charge
250 ml
1200 ml
1200 ml
Approved oil
POE -- Mobil Arctic EAL 68 (Carrier Part Number 46-60002-02)
1.3 REFRIGERATION SYSTEM DATA
a. Defrost Timer
Automatic triggering or at present intervals :
0, auto, 1h, 2h, 3h, 4h, 5h, 6h
b. Defrost Termination Thermostat
Opens at: 48
_
¦
5
_
F (9
_
¦
3
_
C)
Closes at: 37
_
¦
5
_
F (3
_
¦
3
_
C)
c. High Pressure Switch (HP1)
Cutout at : 465
¦
10 psig (32 bar)
Cut-in at : 360
¦
10 psig (25 bar)
d. Condenser Pressure Switch (HP2)
Cutout at : 245
¦
10 psig1 (7 bar)
Cut-in at : 320
¦
10 psig (22 bar)
e. Standby High Pressure Switch (HP3)
Cutout at : 430
¦
10 psig (30 bar)
Cut-in at : 360
¦
10 psig (25 bar)
f. Refrigerant charge
Refer to Table 1-1.
g. Compressor Pressure Regulating Valve (CPR)
Setting; 36
¦
1 psig (2.5 bar)
h. Thermostatic Expansion Valve
Type:
50S
= TES 2/ Orifice n
_
4/ MOP 75 psi (5.1 bar)
40S
= TES 2/ Orifice n
_
3/ MOP 75 psi (5.1 bar)
Superheat setting = 7
¦
1
_
F(4
_
C ) at 0
_
F ( -20
_
C) box
temperature.
i. Low Pressure Switch (LP)
Cutout at : -2.9 psig
¦
3 psi (-0.2 bar)
Cut-in at : 14.5 psig
¦
3 psi (1 bar)
j. Quench Valve (BPV)
Opens at: 260
_
F (127
_
C )
Closes at: 212
_
F (105
_
C)
1.4 ELECTRICAL DATA
a. Evaporator Fan Motors
Bearing Lubrication
Factory Lubricated
Horse Power
0.1 kw
Operating Amps
7 to 9 amps
Speed
2100 rpm (rated)
b. Standby Compressor Speed
-- 1740 rpm -- 60 hz