background image

18

START-UP

Make the following checks and complete the Start-Up

Checklist on page CL-1 before system start-up. Also refer to

the condensing unit Installation, Start-Up and Service Instruc-

tions for system start-up instructions and refrigerant charging

methods.

1. Check condensate drainage system:

a. Remove grille and frame from the unit.

b. On the opposite side of the drain connection, insert

a water bottle up into the fan coil unit and fill drain

pan. Refer to Fig. 22. Water must flow steadily; if

not, check the pipe slope or inspect for any pipe

restrictions.

2. Make sure that all wiring connections are correct and

that they are tight.

3. Check that all barriers, covers, and panels are in place.

Ensure that the filters and return-air grilles have been

installed and that the discharge louvers are positioned

correctly.

After Extended Shutdown — 

If the system has been

turned off for more than 12 hours and a crankcase heater is be-

ing used, turn on the indoor and outdoor unit disconnect

switches to supply power to the system for 12 hours BEFORE

starting the system.

Seasonal Changeovers — 

When changing heat pump

system from cooling to heating or heating to cooling, or before

starting cooling only system after it has been out of use for the

winter season, perform the following steps BEFORE starting

the system:

1. Inspect and clean the outdoor unit, particularly the

coil.

2. Clean or replace the air filters in the indoor unit.
3. Clean the indoor unit drain pan and drain pipe, and

remove any obstructions. 

4. If the outdoor unit is equipped with a crankcase heater,

turn on indoor and outdoor unit disconnect switches to

supply power to the system 12 hours before starting

the system.

Adjusting Airflow

AUTOMATIC AIR SWEEP — All  units  are  equipped  with

an air sweep feature which directs the airflow louvers up and

down to provide optimum room air circulation. The air sweep

function can be controlled by the toggle switch located on the

lower right corner of the unit. If using a thermostat with an air

sweep switch, see Fig. 20 and 21 for wiring modifications.

Operating Mode Memory — 

 After the system is

turned off or after a power failure, the system remains in the

last operating mode selected. When the system is turned back

on, or when power is automatically restored, operation contin-

ues in the same operating mode as when the system shut down.

Automatic  Operation  (Auto.)  Mode  — 

 If auto.

mode is selected, the system automatically switches over the

operating mode from heating to cooling, or from cooling to

heating (heat pump system only) depending on the selected

temperature. Auto. mode also controls fan speed if not manual-

ly overridden.
NOTE: Between the cooling cycle and the heating cycle there

is a neutral zone of approximately 2° F above and 2° F below

the selected temperature when only the fan is operating.

Operating  Sequence  — 

 Ceiling-suspended fan coil

units have a relay board which controls system operation in re-

sponse to a room thermostat. The user may manually select any

one of 3 fan speeds for unit operation. Ceiling-suspended sys-

tems may be equipped with an accessory power ventilation kit

and/or condensate pump.
FAN OPERATION — Fan coils are capable of 3-speed opera-

tion. See thermostat instructions for fan speed selection. When

the fan(s) is operating in medium or high speed and the unit is

equipped with the power ventilation kit, the ventilation fan will

operate to provide fresh air.
COOLING MODE OPERATION — When  the  room  ther-

mostat senses a demand for cooling, the fan coil relay board is

energized. The indoor fan(s) will start in the selected speed (if

it is not already operating). The reversing valve (heat pump

only) will energize for cooling operation. 

The internal condensate pump (if so equipped) runs when-

ever the reversing valve is energized (heat pump only) and/or

the unit is in cooling. As long as the condensate float switch

and freeze protection thermostat are closed, the cooling relays

in the fan coil unit will close. This energizes the compressor

and outdoor fan in the outdoor unit. The compressor will con-

tinue to operate until the room thermostat is satisfied. When the

cooling demand is satisfied, the compressor and outdoor fan

will stop. If the system is in the AUTO. position, the indoor fan

will stop with the compressor. If the unit has the accessory ven-

tilation kit, the ventilation fan will operate whenever the indoor

fan is set for medium or high speed.
HEAT PUMP OPERATION — When  the  room  thermostat

senses a demand for heating the indoor fan will start in the

selected speed (if not already operating), and the reversing

valve will not be energized. The internal condensate pump (if

supplied) and freeze protection thermostat are not operated

during heating operation. The control relay (CR2) closes, and

the compressor and outdoor fan are energized through the de-

frost board (DFB), which is located in the outdoor unit. The

microprocessor logic in the DFB is energized when the com-

pressor starts, and the defrost timer runs. Once every 90 min-

utes (factory default setting) of compressor run time, the DFB

logic checks the defrost thermostat (DFT). If the DFT is open,

the unit continues in heating operation. If the DFT is closed, the

DFB switches the unit to defrost mode. The timing on the DFB

may be set at either 30, 50, or 90 minutes.
DEFROST (Heat Pump Only) — The  DFB  energizes  the

RVS (reversing valve solenoid), and the reversing valve

switches to the cooling position. The K1 relay on the DFB

opens and the outdoor fan stops. The W2 contact on the DFB is

also energized, which in turn energizes the defrost relay on the

fan coil relay board, turns off the electric heater and stops the

indoor fan.

The DFB logic checks the 10-minute defrost timer and the

DFT. If the DFT opens in less than 10 minutes, the DFB

switches the unit back to normal heating operation. If the DFT

remains closed, the DFB switches the unit back to heating op-

eration after 10 minutes. When the DFB changes back to heat-

ing mode, the RVR (reversing valve relay) is deenergized and

the reversing valve switches back to heating operation. Both

the outdoor and indoor fans come back on, and if necessary, the

electric heater also turns on.
SYSTEM SAFETIES  — The system is equipped with the

following safety devices to protect system components:

Indoor coil freeze protection thermostat — If a coil temper-

ature of 28 F or lower is sensed, the compressor and outdoor

fan will be shut down until the coil temperature exceeds 28 F.

The indoor fan will continue to run.

Condensate float switch (units equipped with accessory

condensate pump, cooling cycle only) — If the level of con-

densate in the drain pan rises too high, the condensate float

switch will turn the system off.

Never operate unit without a filter or with grille removed;

damage to the unit or personal injury may result.

Summary of Contents for 40QA024-060

Page 1: ...PERATE FRESH AIR INSTALLATION OPTION 20 Ventilation Air Accessory 20 TROUBLESHOOTING 20 START UP CHECKLIST CL1 CL 2 SAFETY CONSIDERATIONS Installing and servicing air conditioning equipment can be haz...

Page 2: ...field supplied for connection of the indoor and outdoor units refrigerant piping condensate drain piping thermostat power and control wiring For some applications a fresh air intake power vent fan and...

Page 3: ...CITY tons 11 2 2 3 3 4 5 NOMINAL SIZE Btuh 18 000 24 000 30 000 36 000 48 000 60 000 OPERATING WEIGHT lb 108 108 117 117 149 179 MOISTURE REMOVAL WEIGHT Pints Hr 4 0 7 3 6 0 9 0 13 0 14 5 FINISH GM Mo...

Page 4: ...3 4 5 NOMINAL SIZE Btuh 18 000 24 000 30 000 36 000 48 000 60 000 OPERATING WEIGHT lb 110 110 119 119 151 181 MOISTURE REMOVAL WEIGHT Pints Hr 4 0 7 3 6 0 9 0 13 0 14 5 FINISH GM Motorhome White with...

Page 5: ...119 4 1013 16 1493 4 57 8 1368 4 91 2 1459 2 11 2 648 048 149 151 5 119 16 1817 5 65 8 1692 5 101 4 1783 1 97 8 555 3 31 16 992 060 179 181 7 8 2336 7 3 2211 7 65 8 2302 1 115 8 601 4 119 16 1512 NOT...

Page 6: ...T CONCRETE SLAB Install hang ing bolts with expansion anchor TO MOUNT UNIT 1 Remove mounting bracket and reinstall the 2 hex head bolts factory supplied into each side of indoor unit as shown in Fig 6...

Page 7: ...een the structure and the unit to absorb vibrations d A piston is shipped in the factory installed meter ing device body Fig 13 with the indoor unit Use Tables 4A 4C to verify that you have the requir...

Page 8: ...pipe with nylon wire tie passing through hole Fig 15 NOTE Do not fasten nylon wire ties tight enough to deform the insulation as this affects its performance 5 Insulate condensate drain line s that a...

Page 9: ...Fig 11 Hanging Fan Coil Unit Field supplied Fig 12 Routing Wires Over Piping NOTE Teflon Seal must face toward the outdoor heat pump unit Fig 13 AccuRater Metering Device at Service Valve Bypass Type...

Page 10: ...lectrical data is the same for both the 24 000 Btuh 024 unit and the 024 unit that has been field reconfigured for 18 000 Btuh Refer to Before Installation section on page 3 for reconfiguration detail...

Page 11: ...ues 2 All wiring must comply with the applicable local and national codes 3 Liquid line need not be insulated cooling only units 4 Wiring and piping shown are general points of connection guides only...

Page 12: ...mostat Operating Instructions Mount thermostat to a wall in the occupied space using 2 field supplied screws Locate the thermostat in an area that is not subjected to drafts or direct sunlight through...

Page 13: ...nections must be made to the outdoor unit for it to operate as a system with the indoor unit Route 5 wires of field supplied 18 gage AWG thermostat cable between the low voltage terminal block of the...

Page 14: ...FLAT THERMOSTAT FLATSTAT CARRIER COOLING ONLY HEAT COOL 53DFS250 FS SLIMLINE THERMOSTAT CARRIER HEAT PUMP COOLING ONLY HEAT COOL 53DFS250 SL 5 1 1 PROGRAMMABLE THERMOSTAT CARRIER COOLING ONLY HEAT CO...

Page 15: ...te as a sys tem with the indoor unit Route 2 wires of field supplied 18 gage AWG American Wire Gage thermostat cable between the low voltage terminal block of the fan coil unit and the blue and brown...

Page 16: ...16 Fig 20 Cooling System Wiring Diagram...

Page 17: ...17 Fig 21 Heat Pump Wiring Diagram...

Page 18: ...gh speed and the unit is equipped with the power ventilation kit the ventilation fan will operate to provide fresh air COOLING MODE OPERATION When the room ther mostat senses a demand for cooling the...

Page 19: ...Maintenance procedures for the outdoor units are in the individual unit installation instructions To avoid the possibility of electric shock before performing any cleaning and maintenance operations...

Page 20: ...Mode button until either COOL or HEAT is dis played as desired 4 Adjust thermostat set point to desired room tempera ture If system starts within a few minutes service may not be necessary If system...

Page 21: ...t Cool Properly Air filter s in indoor unit is dirty or needs to be replaced Clean or replace air filter s Temperature is set too high or too low Reset temperature to desired comfort setting using the...

Page 22: ...ent discussed in this manual including Unit Familiarization Maintenance Installation Overview Operating Sequence A large selection of product theory and skills programs are available using popular vid...

Page 23: ...CR BREAKER BEEN PROVIDED ____________ ARE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY ____________ IS THE DISCONNECT SWITCH INSTALLED WITHIN SIGHT OF THE UNIT ____________ IS THE LOW VOLTAGE...

Page 24: ...ATION OUTDOOR UNIT MODEL NO SERIAL NO INDOOR UNIT MODEL NO SERIAL NO ACCESSORIES __________________________________________________________________________________ PISTONS 38HDC and 38QRC SYSTEMS ONLY...

Reviews: