
43
Master Zone Maintenance Table —
The Master Zone
Maintenance Table (MZNMAINT) displays variables used by
the Linkage Coordinator zone controller when determining the
system mode (heat/cool/vent). It also indicates whether a by-
pass controller and an air source are being used and which zone
is the reference zone. The user may override cooling or heating
time guards from this table. See Table 17.
DESIRED SYSTEM MODE — This variable will display
the desired operating mode of the air source.
Desired
Operating Mode: Display Range
COOLING, HEATING,
FREECOOL,
PRES-
SURE, EVAC, OFF
Network Access Read only
SYSTEM MODE — This variable will display the current
system mode of the air source, if Linkage is available, or the
mode determined by the Linkage Coordinator using the prima-
ry air sensor, if available. If the primary air sensor has failed or
was not installed, the Linkage Coordinator will assume the
default mode of cooling.
System Mode:
Display Range
COOLING, HEATING,
FREECOOL,
PRES-
SURE, EVAC, OFF
Network Access Read only
AIR SOURCE DETECTED — This variable displays whether
the Linkage Coordinator zone controller has detected a
communicating air source at the address configured in the
Linkage Configuration Table.
Air Source
Detected:
Display Range
Yes/No
Network Access Read only
BYPASS CONTROLLER — This variable displays whether
the Linkage Coordinator zone controller has detected a com-
municating bypass controller as configured in the Linkage
Configuration Table.
Bypass
Controller:
Display Range
Yes/No
Network Access Read only
REFERENCE ZONE DEMAND — This variable displays
the demand of the reference zone. When occupied, the demand
will be a function of T56 bias and configured Occupied
Heating and Cooling set points. When in unoccupied mode, the
demand will be directly related to configured Unoccupied
Heating and Cooling set points.
The reference zone is re-determined on every scan of the
zone controllers which is at a one minute frequency.
Reference Zone
Demand:
Display Range
delta 0.00 to 99.9 F
Network Access Read only
REFERENCE ZONE # — This variable displays the number
of the zone whose heating or cooling needs are the greatest at
any time and that requires the same mode as the system.
For example, if the Desired System Mode is cooling, the
Reference Zone # is that mode that has the greatest cooling
need.
The zones are numbered such that the master zone is zone
number 1 and the zone that is one address below the master
zone is zone number 2 and so on to zone number 32. If the
master zone is at address 0, 118 then zone no. 2 is the zone
controller at address 0, 117 and zone no. 3 is the zone controller
at address 0, 116 and so on.
Reference Zone
Number:
Display Range
1 to 32
Network Access Read only
COOL MODE LOCK OUT — This variable displays whether
the system has been locked out of cooling mode. If this
decision is forced to
Yes
, the system may not go into cooling
mode regardless of how many zones are calling for cooling.
Cool Mode
Lock Out:
Display Range
Yes/No
Network Access Read/Write
AVERAGE COOL DEMAND — This variable displays the
average cooling demand of all occupied linked zones, taking
into consideration the size of each zone as configured in the
Terminal Service Configuration Table. This is so that the size
of a zone will be considered when comparing its demand to
other zones. If all zones are unoccupied then all zones will be
included in the calculation.
Average Cool
Demand:
Display Range
delta 0.00 to 99.9 F
Network Access Read Only
Table 17 — Master Zone Maintenance Table
DESCRIPTION
VALUE
UNITS
STATUS
FORCE
NAME
Desired System Mode
COOLING
NEXTMODE
System Mode
COOLING
LINKMODE
Air Source Detected?
Yes
AIRSOURC
Bypass Controller?
No
BYPASS
Reference Zone Demand
0.0
^F
REF_DMD
Reference Zone #
0
REF_ZONE
Cool Mode Lock Out?
No
C_LOCK
Average Cool Demand
0.0
^F
AVGC_DMD
Max Cool Demand
0.0
^F
MAXC_DMD
Max Cool Demand Zone
0
MAXCZONE
Cooling Time Guard
0.0
min
C_TGUARD
Time Guard Override
No
TG_OVRD
Heat Mode Lock Out?
No
H_LOCK
Average Heat Demand
0.0
^F
AVGH_DMD
Max Heat Demand
0.0
^F
MAXH_DMD
Max Heat Demand Zone
1
MAXHZONE
Heating Time Guard
0.0
min
H_TGUARD
Mode Reselect Time
0.0
min
RESELECT
Outdoor Air Temperature
0.0
dF
OAT
Summary of Contents for 3V VVT 33ZCVVTZC-01
Page 59: ......