background image

5

• Caulk and bolt standing seam and install the roof cleat.

See Fig. 8.

• Check all splits to ensure proper bolting and caulking.

• Check all splits to ensure that all electrical and piping

connections are correct and complete.

Reassembly

of

Stacked

Unit

Horizontal

Splits —

For a unit is split both vertically and horizontally,

complete the assembly of the lower section first. Next join the

upper sections to the lower sections.
• Caulk underneath  clips, behind lifting lugs, and behind

upper base channel.

• Wherever possible, secure base anchor clips in bolt

holes.

• Check all splits to ensure proper bolting and caulking.

• Check all splits to ensure that all electrical and piping

connections are correct and complete.

• If equipment is not properly installed, the cabinet will

leak air under pressure or water may leak into the cabinet

from the split joint.
For units wider than any split section’s airway length, re-

movable lifting lugs are provided along the width of unit. After

closely positioning the split, remove the inner lifting lugs.

During final bolting, a come-along or hand-operated winch can

be used to tighten the space between unit sections.

Trapping Drains —

All condensate drain connections

and floor drains must be trapped on the job site by others. Im-

proper drain trapping can cause the drain pan to flood and po-

tentially damage the air-handling unit and surrounding facili-

ties. Improperly trapping a drain can result in a flooded drain

pan and potential water damage to the unit and other building

facilities.

See Fig. 9 for condensate drain trap sizing.

Connecting Ducts —

When connecting flanged ducts

directly to the casing, use self-tapping sheet metal screws. For

duct connections to collar-type openings, use s-cleats or over-

lapping joints. To prevent air leakage and eliminate system per-

formance problems, caulk around all duct connections to form

tight seals.

Connecting Rain Hoods —

Be sure to allow adequate

clearance to doors and other openings on the unit. Use sheet

metal screws to fasten the hood or hoods to the casing of the air

handling units. Caulk around the hood flange, then carefully re-

move any excess caulking.

Electrical Installation —

All wiring shall be installed

in accordance with the requirements of the authorities having

jurisdiction. Do not cut holes in the bottom of outdoor units, as

the bottom of the unit has been made waterproof.  Both field

wiring and internal wiring diagrams are included in the control

cabinet of the unit. The power requirements are indicated on

the unit nameplate. Where field wiring of the control circuit is

required, take care to size the field wiring for a maximum 10%

voltage drop. The VA rating of the transformer can be

assumed to be the maximum load. The disconnect must be

mounted properly and adequately grounded. All field wiring

outside the electrical enclosure must be rigid or flexible con-

duit. Reconnect all disconnected wiring on the units that were

split in 2 or more sections for shipment.

Observe the following precautions:

• When connecting a power supply to a three-phase motor,

take care that the three-phase wiring provides the correct

motor and blower rotation.

• Replacement wiring must be equivalent to original wire

size.

• It is recommended that, when interior lighting and con-

venience outlets are provided, they should be wired to a

separate power supply.

• In all cases the unit must be properly grounded and all

electrical connections should be checked and tightened if

required before starting up the equipment.

• See field-wiring diagram for requirements for shielded or

twisted wire for solid-state devices.

• When cutting holes in the control panel or unit for con-

duit penetration, make sure conduit penetrations are

sealed to be air and water tight.

• Lock all latches on the electrical and control panels.

CAULKING

a39-4467

Fig. 7 — Caulking Roof Exterior Seams

a39-4466

Fig. 8 — Bolt Standing Seam, Install Roof Cleat

Summary of Contents for 39CCN

Page 1: ...switch before working on or near heaters Failure to follow these warnings could lead to personal injury or death WARNING CHECK the assembly and component weights to be sure that the rigging equipment can handle them safely Note also the centers of gravity and any specific rigging instructions CHECK for adequate ventilation so that fumes will not migrate through ductwork to occupied spaces when wel...

Page 2: ...tance of insulation with a Megger meter or a resistance meter The insulation resistance kV rating 1 Megohom Whenever possible store equipment indoors in a dry area and protect the fan shaft bearings and fan wheel from dust and corrosion If outdoor storage is necessary be sure to close latches on all access doors to prevent potential water and air leakage Unit should be placed on a level surface Av...

Page 3: ... static pressure This unit is designed for installation on a level surface or suspended on a level plane Follow SMACNA Sheet Metal and Air Conditioning Contractors National Association guidelines for sup ply return exhaust duct connections and minimal duct obstruction clearances Air Handler Unit Pad The foundation and floor should be level shim when necessary rigid and strong enough to support the...

Page 4: ...n from chemicals in the airstream COOLING COILS CHILLED WATER DIRECT EXPAN SION GLYCOL Cooling coils are constructed of copper tube with corrugated fins Maximum operating pressure is 150 psig An IAQ 304SS indoor air quality 304 stainless steel condensate drain pan is located under the coil with drain and vent connections Do not block the air vent this may result in poor coil performance Inlet line...

Page 5: ...tions to form tight seals Connecting Rain Hoods Be sure to allow adequate clearance to doors and other openings on the unit Use sheet metal screws to fasten the hood or hoods to the casing of the air handling units Caulk around the hood flange then carefully re move any excess caulking Electrical Installation All wiring shall be installed in accordance with the requirements of the authorities havi...

Page 6: ...ting SERVICE Monthly 1 Check supply air filters and clean or replace as required 2 Check the cooling coil condensate drain pan for proper draining and clean if necessary 3 Fan bearings with grease fittings need to be lubricated Bearings that do not have grease fittings are permanently sealed and do not require lubrication Check submittal data for types of bearings used a Fans ship from the factory...

Page 7: ...n stretching and a mismatched set of belts 2 Do not allow belt to bottom out in sheave 3 Tighten belts by turning motor adjusting jackscrews Turn each jackscrew an equal number of turns 4 Equalize belt slack so that it is on the same side of belt for all belts Failure to do so may result in uneven belt stretching 5 Tension new drives at the maximum deflection force recommended Table 3 On current p...

Page 8: ...es of operation Used belts should be maintained at the value as indicated in the chart Used Belt tensions should be used for the 8 hour and subsequent checks If the belt span was measured in centimeters then use the kilograms of force values for comparison NOTE The ratio of deflection to belt span is 1 64 in either unit of measurement Whenever possible jog start for a few revolutions or prefer abl...

Page 9: ...8 0 20 0 200 850 851 1500 30 4 25 6 45 2 38 0 3V 3VX 2 2 2 4 1000 2500 2501 4000 3 3 2 9 4 9 4 3 2 65 3 65 1000 2500 2501 4000 3 6 3 0 5 1 4 4 4 2 3 8 6 2 5 6 4 12 6 90 1000 2500 2501 4000 4 9 4 4 7 3 6 6 5 3 4 9 7 9 7 3 5V 5VX 4 4 6 7 500 1749 1750 3000 3001 4000 10 2 8 8 5 6 15 2 13 2 8 5 7 1 10 9 500 1749 1750 3000 3001 4000 12 7 11 2 18 9 16 7 14 8 13 7 22 1 20 1 11 8 16 0 500 1749 1750 3000 3...

Page 10: ...mps _____ Other UNIT FAN _____ Visually inspect wheel and fan rotation _____ Inertia base is fitted _____ Shipping tie downs are removed _____ Seismic restraints are set up _____ There are no impairments to free isolation _____ The flex power line to fan motor does not interfere with isolation _____ Check belt tension _____ Check flex connection on fan _____ Check VAV variable air volume devices a...

Page 11: ...ere is no over torquing _____ Actuators have been power operated through cycle to verify operation GENERAL _____ Entire cabinet has been visually checked and repairs made if necessary _____ Access doors have been checked for free movement and complete closure _____ All seams are sealed _____ Verify that there are no air leaks with running fan _____ Check interior of unit for loose or damaged insul...

Page 12: ...e right to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53390017 01 Printed in U S A Form 39CC 1SI Pg 12 1 15 Replaces New Carrier Corporation 2015 ...

Reviews: