background image

3

It is mandatory to use spreader bars for larger units with lift-

ing lugs or slings for smaller units to prevent damage to the

casing of the units by rigging equipment. Only qualified rig-

ging personnel should operate lift equipment.

Units can be lifted with forklifts as long as the forks are

40 inches and the end tips contact the bottom of the intermedi-

ate supports of the base rail. Additionally, a fork lift may be

used to lift small subassemblies or individual sections, but the

forks must reach the other side of the base rail. See Fig. 3.

To avoid damaging the air-handling unit, always lift in an

upright position, and never move or lift unit from a sideways or

upside-down position. 

Use extreme caution when moving an

air-handling unit with a forklift

.

SPLIT UNITS — Split units less than 102 in. may be shipped

loosely assembled. Disassembly is required, with each section

being lifted individually. The “loosely assembled” split sec-

tions are affixed using a minimum number of bolts for transit

and cannot be lifted while fastened together. Use all lifting lugs

to avoid unit damage and/or personal injury.

Clearance Requirements —

As required by the state,

city or the national electrical code (NEC or CEC), the service

space between the face of any electrical enclosure and wall or

obstruction must be 42 inches minimum.

Sufficient clearances are also needed to open doors and in-

stall piping and ductwork. Airflow through the louvers of

hoods cannot be obstructed in any way. The distance between

the louver and any facing wall must be equal to the horizontal

width of the louver.

Space around the unit must allow easy removal of the ac-

cess panels and parts such as the fan wheels, motors and belt

guards. To facilitate removal of coils, fan shaft, and fan wheel,

allow a minimum clearance equal to the width of the unit on

one side.

INSTALLATION

• The services of qualified field services personnel are

required for safe and proper installation of this equip-

ment.

• Do not operate this unit outside the listed nameplate rat-

ings for flow or static pressure.

• This unit is designed for installation on a level surface or

suspended on a level plane.

• Follow SMACNA (Sheet Metal and Air Conditioning

Contractors’ National Association) guidelines for sup-

ply/return/exhaust duct connections and minimal duct

obstruction clearances.

Air Handler Unit Pad —

The foundation and floor

should be level (shim when necessary), rigid, and strong

enough to support the  weight  of  the  entire  unit.    It  is  the

installer’s responsibility to secure the unit to the unit pad in ac-

cordance with all applicable building and earthquake codes.

After the unit has been installed, the base rail should be in-

spected for paint damage from chains in the tie down brackets,

use of the lifting lugs and fastening the unit down. This damage

must be repaired by cleaning down to bare metal and applying

two heavy coats of matching paint to stop corrosion and rust.

Ceiling Suspended Units —

Ceiling suspended units

must be supported from the base. To fully support the unit, four

or more suspension points are required. The casing is not a sup-

port component. The exact number of support points is func-

tion of the unit length and weight. Please refer to submittal

drawings for lift locations. The installer is responsible for in-

stalling in accordance with applicable building and earthquake

codes. See Fig. 4.

Roof Curb —

Roof curbs are shipped either fully welded

or in split sections. Bolt together if roof curb is bolted construc-

tion. Follow this procedure to assemble roof curb, if required:

1. Arrange the 4 perimeter sidewalls so that pre-drilled holes

are aligned. Drive bolt each corner securely (bolts provid-

ed). 

2. Drive bolt the remaining support members using the pre-

drilled holes and provided drive bolts. Turn out the flang-

es before fastening. See Fig. 5.

3. Line up the assembled curb with the roof openings.

Square up the curb by measuring the diagonal distance

between opposite corners and adjust until the distances

are equal. Level the curb.

4. Install the foam rubber seal strip atop the installed curb.

This provides an airtight seal and isolates the roof from

vibration.

FORKS

a39-4461

Fig. 3 — Forklift

a39-4460

Fig. 4 — Suspension Mounting

SIDEWALL

PRE-DRILLED HOLES
(BOLTS SHIPPED LOOSE)

a39-4464

Fig. 5 — Roof Curb Assembly

Summary of Contents for 39CCN

Page 1: ...switch before working on or near heaters Failure to follow these warnings could lead to personal injury or death WARNING CHECK the assembly and component weights to be sure that the rigging equipment can handle them safely Note also the centers of gravity and any specific rigging instructions CHECK for adequate ventilation so that fumes will not migrate through ductwork to occupied spaces when wel...

Page 2: ...tance of insulation with a Megger meter or a resistance meter The insulation resistance kV rating 1 Megohom Whenever possible store equipment indoors in a dry area and protect the fan shaft bearings and fan wheel from dust and corrosion If outdoor storage is necessary be sure to close latches on all access doors to prevent potential water and air leakage Unit should be placed on a level surface Av...

Page 3: ... static pressure This unit is designed for installation on a level surface or suspended on a level plane Follow SMACNA Sheet Metal and Air Conditioning Contractors National Association guidelines for sup ply return exhaust duct connections and minimal duct obstruction clearances Air Handler Unit Pad The foundation and floor should be level shim when necessary rigid and strong enough to support the...

Page 4: ...n from chemicals in the airstream COOLING COILS CHILLED WATER DIRECT EXPAN SION GLYCOL Cooling coils are constructed of copper tube with corrugated fins Maximum operating pressure is 150 psig An IAQ 304SS indoor air quality 304 stainless steel condensate drain pan is located under the coil with drain and vent connections Do not block the air vent this may result in poor coil performance Inlet line...

Page 5: ...tions to form tight seals Connecting Rain Hoods Be sure to allow adequate clearance to doors and other openings on the unit Use sheet metal screws to fasten the hood or hoods to the casing of the air handling units Caulk around the hood flange then carefully re move any excess caulking Electrical Installation All wiring shall be installed in accordance with the requirements of the authorities havi...

Page 6: ...ting SERVICE Monthly 1 Check supply air filters and clean or replace as required 2 Check the cooling coil condensate drain pan for proper draining and clean if necessary 3 Fan bearings with grease fittings need to be lubricated Bearings that do not have grease fittings are permanently sealed and do not require lubrication Check submittal data for types of bearings used a Fans ship from the factory...

Page 7: ...n stretching and a mismatched set of belts 2 Do not allow belt to bottom out in sheave 3 Tighten belts by turning motor adjusting jackscrews Turn each jackscrew an equal number of turns 4 Equalize belt slack so that it is on the same side of belt for all belts Failure to do so may result in uneven belt stretching 5 Tension new drives at the maximum deflection force recommended Table 3 On current p...

Page 8: ...es of operation Used belts should be maintained at the value as indicated in the chart Used Belt tensions should be used for the 8 hour and subsequent checks If the belt span was measured in centimeters then use the kilograms of force values for comparison NOTE The ratio of deflection to belt span is 1 64 in either unit of measurement Whenever possible jog start for a few revolutions or prefer abl...

Page 9: ...8 0 20 0 200 850 851 1500 30 4 25 6 45 2 38 0 3V 3VX 2 2 2 4 1000 2500 2501 4000 3 3 2 9 4 9 4 3 2 65 3 65 1000 2500 2501 4000 3 6 3 0 5 1 4 4 4 2 3 8 6 2 5 6 4 12 6 90 1000 2500 2501 4000 4 9 4 4 7 3 6 6 5 3 4 9 7 9 7 3 5V 5VX 4 4 6 7 500 1749 1750 3000 3001 4000 10 2 8 8 5 6 15 2 13 2 8 5 7 1 10 9 500 1749 1750 3000 3001 4000 12 7 11 2 18 9 16 7 14 8 13 7 22 1 20 1 11 8 16 0 500 1749 1750 3000 3...

Page 10: ...mps _____ Other UNIT FAN _____ Visually inspect wheel and fan rotation _____ Inertia base is fitted _____ Shipping tie downs are removed _____ Seismic restraints are set up _____ There are no impairments to free isolation _____ The flex power line to fan motor does not interfere with isolation _____ Check belt tension _____ Check flex connection on fan _____ Check VAV variable air volume devices a...

Page 11: ...ere is no over torquing _____ Actuators have been power operated through cycle to verify operation GENERAL _____ Entire cabinet has been visually checked and repairs made if necessary _____ Access doors have been checked for free movement and complete closure _____ All seams are sealed _____ Verify that there are no air leaks with running fan _____ Check interior of unit for loose or damaged insul...

Page 12: ...e right to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53390017 01 Printed in U S A Form 39CC 1SI Pg 12 1 15 Replaces New Carrier Corporation 2015 ...

Reviews: