background image

To prevent compressor damage DO NOT bury more than 36
in. of refrigerant tubing. If ANY tubing is buried, provide 6
in. vertical rise at service valve.

To prevent damage to unit or service valves observe the
following:
• Use a brazing shield.
• Wrap service valves with wet cloth or use a heat sink
material.

Outdoor units may be connected to indoor section using accessory
tubing package or field-supplied refrigerant grade tubing of correct
size and condition. For tubing requirements beyond 50 ft (15.24m),
consult Long-Line Application Guideline which is available from
your local distributor.

NOTE:

In some cases noise in the living area has been traced to

gas pulsations from improper installation of equipment.

INSTALLATION RECOMMENDATIONS

1. Locate unit away from windows.

2. Ensure that vapor and liquid tube diameters are appropriate to

capacity of unit. (See Table 1.)

3. Run refrigerant tubes as directly as possible by avoiding

unnecessary turns and bends.

4. Leave some slack between structure and unit to absorb

vibration.

5. When passing refrigerant tubes through the wall, seal opening

with RTV or other pliable silicon-based caulk. (See Fig. 4.)

6. Avoid direct tubing contact with water pipes, ductwork, floor

joists, wall studs, floors, and walls.

7. Do not suspend refrigerant tubing from joists and studs with a

rigid wire or strap which comes in direct contact with tubing.
(See Fig. 4.)

8. Ensure that tubing insulation is pliable and completely sur-

rounds vapor tube.

9. When necessary, use hangar straps which are 1 in. (25mm)

wide and conform to shape of tubing insulation. (See Fig. 4.)

10. Isolate hangar straps from insulation by using metal sleeves

bent to conform to shape of insulation.

If refrigerant tubes or indoor coil is exposed to atmosphere, it must
be evacuated to 500 microns to eliminate contamination and
moisture in the system.

OUTDOOR UNIT CONNECTED TO FACTORY-APPROVED
INDOOR UNIT — Outdoor unit contains correct system refriger-
ant charge for operation with indoor unit of same size when
connected by 15 ft (4.55m) of field-supplied or factory-accessory
tubing. Check refrigerant charge for maximum efficiency.

Table 1—Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters

UNIT SIZE

LIQUID

VAPOR

Connection Dia.

Tube Dia.

Connection DIia.

Vapor Dia.

In.

mm

In.

mm

In.

mm

In.

mm

024

3/8

9.53

3/8

9.53

5/8

15.88

5/8

15.88

036

3/8

9.53

3/8

9.53

3/4

19.05

3/4

19.05

048

3/8

9.53

3/8

9.53

7/8

22.23

7/8

22.23

060

3/8

9.53

3/8

9.53

7/8

22.23

1-1/8

28.58

NOTES: 1. Tube diameters are for lengths up to 50 ft (15.24m). For tubing lengths greater than 50 ft (15.24m), consult Long-Line Application Guideline.
2. Do not apply capillary tube indoor coils to these units.

Fig. 4—Piping Installation

A94330

INSULATION

VAPOR TUBE

LIQUID TUBE

OUTDOOR WALL

INDOOR WALL

LIQUID TUBE

VAPOR TUBE

INSULATION

CAULK

Avoid contact between tubing and structure.

NOTE:

THROUGH THE WALL

HANGER STRAP

(AROUND VAPOR

TUBE ONLY)

JOIST

1

 MIN

(25 mm)

SUSPENSION

Fig. 5—Service Valve with Sweat Adapter Tube

A94029

PISTON  BODY

PISTON

PISTON  RETAINER

SWEAT/FLARE  ADAPTER

3

Summary of Contents for 38YCX

Page 1: ...k Equipment and Job Site UNPACK UNIT Move to final location Remove carton taking care not to damage unit INSPECT EQUIPMENT File claim with shipping company prior to installation if shipment is damaged...

Page 2: ...8 460 4 14 3 8 365 1 5 8 15 88 33 15 16 862 0 036 30 762 0 6 1 2 165 1 23 1 2 596 9 20 508 0 3 4 19 05 39 15 16 1014 4 048 30 762 0 6 1 2 165 1 23 1 2 596 9 20 508 0 7 8 22 23 33 15 16 862 0 060 30 7...

Page 3: ...e and completely sur rounds vapor tube 9 When necessary use hangar straps which are 1 in 25mm wide and conform to shape of tubing insulation See Fig 4 10 Isolate hangar straps from insulation by using...

Page 4: ...ordance with existing electrical codes Failure to follow this warning can result in an electric shock fire or death NOTE Use No 18 AWG American Wire Gage color coded insulated 35 C minimum wires If th...

Page 5: ...R G THERMOSTAT W2 L E C R G ODTS2 ODTS1 BLU VIO SYSTEMS WITH TWO OUTDOOR THERMOSTATS A97053 HEAT PUMP E L O O Y Y SYSTEMS WITHOUT OUTDOOR THERMOSTAT FB4ASX FAN COIL W2 W2 W2 C C C R R G THERMOSTAT R G...

Page 6: ...ed with a time delay relay circuit the blower runs an additional 90 sec to increase system efficiency Heating On a call for heating the thermostat makes circuits R Y and R G If phasing is correct circ...

Page 7: ...n heating mode allowing frost to accumulate on outdoor coil 4 After a few minutes in heating mode liquid line temperature should drop below closing point of defrost thermostat ap proximately 30 F NOTE...

Page 8: ...31 38ycxc3si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 5a 5a PC 101 Catalog No 003 88...

Reviews: