Basic Control
NORMAL OPERATION
Table 24 —Cooling Operation
Table 25 —Heating Operation
NOTE:
Heating operation is not functional at an outdoor air temperature of 77°F or more.
LEGEND:
INV – Inverter
SV – Solenoid Valve
COMPONENT
NORMAL OPERATION
REMARK
Compressor (INV)
Capacity demand control
To build pressure difference
Outdoor Unit fan (FAN)
Cooling fan control
-
4-Way Valve
OFF
-
Electronic Expansion Valve (EEV)
Discharge temperature control
Adjust refrigerant flow rate to protect compressor
Fast Oil Return Valve (SV4)
17 minutes OFF then 3 minutes ON
-
Hot Gas Bypass Valve (SV5)
OFF
-
Spraying Liquid Valve (SV6)
Discharge temperature protection control
-
COMPONENT
NORMAL OPERATION
REMARK
Compressor (INV)
Capacity demand control
To build pressure difference
Outdoor Unit fan (FAN)
Heating fan control
-
4-Way Valve
ON
-
Electronic Expansion Valve (EEV)
Discharge temperature control
Adjust refrigerant flow rate to protect compressor
Fast Oil Return Valve (SV4)
17 minutes OFF then 3 minutes ON
-
Hot Gas Bypass Valve (SV5)
OFF
Open based on conditions at startup stage (after defrosting
and oil return operation)
Spraying Liquid Valve (SV6)
Discharge temperature protection control
-