ATTENTION: Once the motor pulley opening or closing 
has been set, check that the setscrews have been correctly 
tightened.

ELECTRICAL CONNECTIONS

WARNING: To prevent electrical shock or equipment 
damage, make sure disconnects are open before electrical 
connections are made. If this action is not taken, personal 
injury may occur.

NOTE: The power supply for the units has to be in accor-
dance with applicable standards and laws, the low voltage 
directive, etc.

• 

Connect the power supply for the complete system 
(outdoor unit and indoor unit) via the 38UQZ outdoor 
unit (see Fig. 3).

• 

Consult the wiring diagram supplied with the unit, that 
shows all power connections between the 38UQZ out-
door unit and the 40ALZ indoor unit and the general 
power supply to the system.

• 

The connection cables between the units must not be 
lighter than the flexible Neoprene-covered cable (type 
H0 RN-F), with an appropriate wire section for the 
supply to the 40ALZ unit.

• 

The power of the optional electric heater of the indoor 
unit is supplied via the main disconnect switch of the 
38UQZ unit (see Fig. 1).

Fig. 23 - general unit power supply

Legend

Q1:  Main unit power supply disconnect switch.

 

Located in the outer panel of the 38UQZ unit.

F1:  Field-installed fuses.

•   Route all cables through the conduits in the 38UQZ 

units to the terminals of the main disconnect switch 
(see unit wiring diagram).

•   Voltage to the unit must be within 10% of the nominal 

given in the electrical data table with a maximum phase 
imbalance of %. Contact your local power company 
for correction of an incorrect line voltage.

•   Take special care when making the earth connection. 

This is the first cable to be connected, and it must be 
longer than the live cables.

•  

Operation of the unit on improper line voltage consti-
tutes abuse and is not covered by the Carrier warranty.

IMPORTANT: To ensure the correct unit power supply it 
is necessary first to determine the wire section. The unit 
electrical data (see Table 2 - Electrical Data) and the line 
length (max. admissible voltage loss 5%) must be taken 
into consideration.

If the indoor unit includes an electric heater, this must be 
taken into consideration when sizing the system power 
supply cable (38UQZ-40ALZ) and the isolator switch 
and fuses.

•   Never operate a unit if the voltage imbalance exceeds 

10%. The following formula must be used to determine 
the percentage of voltage imbalance.

Voltage imbalance % =

Largest deviation from average voltage

Average voltage

example:

 Nominal supply: 400-3-0

AB =  404 V
BC =  399 V
AC =  394 V   

 

 

Average voltage =  404 + 399 + 394  =  399 = 400 V
 

3

Determine maximum deviation from average voltage:

AB =  404 - 400 = 4
BC =  400 - 399 = 1
AC =  400 - 394 = 6

Largest deviation is 6 volts. Percentage voltage imbalance 
is therefore:

  6 

x 100 = 1. %

400

• 

The cables marked 

1

 from the 40ALZ indoor units 

are run to the 38UQZ outdoor unit control box for 
connection to the fan motor, and in the case of the 
optional electric heater also cables marked 

2

.

Summary of Contents for 38UQZ016

Page 1: ...he Eurovent Certification Programme Products are as listed in the Eurovent Directory of Certified Products 38UQZ 016 020 024 40ALZ 016 020 024 Split System Air to Air Heat Pumps Installation Operation and Maintenance Instructions ...

Page 2: ...ATION 14 38UQZ outdoor units 14 40ALZ indoor units 16 ELECTRICAL CONNECTIONS 19 REFRIGERANT LINE CONNECTIONS 20 Connection between units 20 Refrigerant piping design 21 Pipe diameter calculation procedure 21 REFRIGERANT CHARGE 23 OIL RECHARGE 24 START UP 24 Initial checks 24 UNIT COMPONENTS 25 DESCRIPTION OF UNIT PROTECTION DEVICES 25 OPERATING LIMITS 25 GENERAL MAINTENANCE 26 Servicing recommenda...

Page 3: ...o C Entering air temp o C Leaving air temp o C Leaving air temp o C Pressure drop air kPa Pressure drop air kPa Discharge air pressure Pa Discharge air pressure Pa Fan motor input Ph 1 Volts Fan motor input Ph 1 Volts Ph 2 Volts Ph 2 Volts Ph 3 Volts Ph 3 Volts SAFETY DEVICE SETTING 38UQZ UNIT High pressure switch cut out kPa cut in kPa Low pressure switch cut out kPa cut in kPa Step controller cu...

Page 4: ...C db Based on an outdoor air temperature of 6 C wb and an indoor air entering temperature of 21 C db The refrigerant charge is for the complete system 38UQZ and 40ALZ but excludes the refrigerant connection lines Table 2 Electrical data 38UQZ 40ALZ 016 020 024 Nominal supply V ph Hz 230 3 50 400 3 50 230 3 50 400 3 50 230 3 50 400 3 50 Voltage range V 207 253 360 440 207 253 360 440 207 253 360 44...

Page 5: ... 5 8 4 Cable entry 5 Main disconnect switch 6 Control box 7 Front access panel 8 Side acces panel both sides 9 Heat echangers 0 Compressors Fans Fig 1 38UQZ dimensions mm Plan view When designing an installation always use up to date drawings available from your local Carrier office Side view Rear view ...

Page 6: ...nt and right side view Detail A Electrical connections Refrigerant line connections Access panel Outlet Hot water coil connections accessory option Air inlet Standard drain ø 23 See detail A Rear and left side view Note The air discharge can be changed from horizontal to vertical see page 17 When designing an installation always use up to date drawings available from your local Carrier office Dime...

Page 7: ...8UQZ 016 024 Required service space for the removal of the air filter and the fans in case of a breakdown Clearance should be the same as the unit width 1000 500 500 600 600 40ALZ all sizes Air filter removal Air filter removal 500 ...

Page 8: ...oordinates mm approx 38UQZ 016 024 40ALZ all sizes 3 38UQZ 016 020 024 XG 1060 1060 1070 YG 300 340 380 ZG 280 320 400 Measured from point 3 40ALZ 016 020 024 XG 1620 1625 1870 YG 230 230 230 ZG 520 520 520 Measured from point 3 ...

Page 9: ...ion kg approx 38UQZ 016 024 40ALZ Air filters 3 1 5 4 6 Point 38UQZ 016 020 024 1 180 210 221 2 180 210 221 3 29 33 36 4 29 33 36 5 31 34 38 6 31 34 38 Point 40ALZ 016 020 024 1 43 46 53 2 47 51 53 3 100 104 110 4 100 104 109 ...

Page 10: ...er input kW 40ALZ 016 high pressure option Available static pressure Pa Air flow l s Power input kW Indoor fan speed Curve Pulley position Standard r s High pressure option r s 0 Closed 17 78 21 42 1 1 17 21 20 74 2 2 16 51 19 89 3 3 15 88 19 14 4 4 15 23 18 35 Factory setting 2 16 51 19 89 ...

Page 11: ...pressure option r s 0 Closed 20 73 24 11 1 1 20 15 23 43 2 2 19 62 22 82 3 3 19 02 22 12 4 4 18 48 21 49 Factory setting 2 5 19 32 22 47 Available static pressure Pa Available static pressure Pa Air flow l s Air flow l s Power input kW Power input kW 40ALZ 020 high pressure option ...

Page 12: ... pressure option r s 0 Closed 20 42 23 67 1 1 19 91 23 08 2 2 19 37 22 45 3 3 18 87 21 87 4 4 18 28 21 19 Factory setting 4 18 28 21 19 Available static pressure Pa Available static pressure Pa Power input kW Power input kW Air flow l s Air flow l s 40ALZ 024 high pressure option ...

Page 13: ...equipment damage make sure disconnects are open before electrical connections are made If this action is not taken personal injury may occur Before performing service or maintenance operations on the unit turn off the main power switch to the outdoor unit 38UQZ Electrical shock could cause personal injury During unit operation some of the refrigerant circuit elements could reach a temperature in e...

Page 14: ...and return air For minimum clearances between the units and walls or roofs see Figs 8 9 and 10 Fig 8 38UQZ 016 024 Rigging hook FRONT VIEW PLAN VIEW Supply air Return air 38UQZ models Fig 7 FLOOR Return air ROOF Control box Return air Table 3 Minimum clearances mm A C 500 Free There must not be any obstacle ceiling or roof near the unit If several units are installed close to each other in the sam...

Page 15: ...nimum clearances between units mm 38UQZ A B C 016 024 500 700 500 Installation on the ground 38UQZ units can be positioned on the floor of a patio on the ground or on a lawn If installed on the ground or on the lawn they should be mounted on a 100 mm high concrete base that is 100 mm larger than the base unit on all four sides Return air Return air Return air Return air PLAN VIEW PLAN VIEW Return ...

Page 16: ...ANT Units must be installed in accordance with applicable local national and European installation and safety standards and regulations 40ALZ indoor units These units have been designed for indoor installation connected to supply and return air ducts When selecting the installation site observe the following points Ensure that the condensate water collected in the drain pan is correctly evacuated ...

Page 17: ...itioning unit air discharge 40ALZ Supply air Return air Return air Supply air Return air Supply air Return air Return air Supply air Legend 1 Side access panel 6 Drive belt s 2 Rear discharge panel 7 Roof panel 3 Top panel 8 Fan pulley 4 Angle iron to attach fan to base 9 Base 5 U bracket Condensate drainage 40ALZ units are supplied with a condensate drain pan with two drain pipes outside diameter...

Page 18: ...aft and align with the motor using a ruler making sure that it is parallel to the belt see Fig 21 2 Tighten the fan pulley setscrews To adjust the belt tension loosen the motor mounting plate bolts and slide the motor mounting plate until the belt is tight 3 Belt tension see Fig 22 The minimum belt deflection is 10 mm when the force shown in Fig 22 is applied Fig 22 Legend 1 Fixed flange 2 Setscre...

Page 19: ...gram Voltage to the unit must be within 10 of the nominal given in the electrical data table with a maximum phase imbalance of 2 Contact your local power company for correction of an incorrect line voltage Take special care when making the earth connection This is the first cable to be connected and it must be longer than the live cables Operation of the unit on improper line voltage consti tutes ...

Page 20: ...am accom panying the unit and the thermostat installation instruction NOTE Refer to the applicable thermostat installation manuals for each model refrigerant line connections Connection between units The 38UQZ outdoor units must be connected with the 40ALZ indoor units with refrigerant grade copper pipes for correct operation For each compressor in the 38UQZ outdoor unit a pipe for refrigerant gas...

Page 21: ...d ascen ding in heat pump mode and is calculated as explained later Indoor unit above the outdoor unit Fig 26 For heat pump units this type of installation limits the height difference between the units and the discharge line speed is approximately half of the suction line speed The suction line flow is descending in cooling mode so that the oil flow is not so problematic The most unfavourable con...

Page 22: ...nd it is checked if the diameter applies to the suction line if this is descending The suction and discharge lines must comply with the following points Maximum admissible pressure loss for the total length 20 kPa 3 psi Minimum velocity in ascending sections 6 m s Horizontal or descending sections the velocity can be between 4 and 6 m s Maximum line velocity 15 m s The horizontal sections must hav...

Page 23: ...ting the refrigerant lines carefully follow the steps below Remove the nitrogen holding charge from the refrige rant circuits Use silver alloy rod for soldering purposes and ensure that this work is done in a nitrogen atmosphere Check the pipes for leaks before welding the joint to the unit pipes Once these connections have been made carry out another leak test refrigerant charge The 38UQZ and 40A...

Page 24: ...dered refrigerant lines and that the refrigerant and oil charges are correct Check the 40ALZ drain connection and that the water is drained correctly Ensure that the unit is level and well supported Check for proper fan rotation direction Check the condition of the ductwork in case damage has occurred during installation The air filter should be clean and in place All the panels should be fitted a...

Page 25: ...n the 38UQZ unit control box High pressurestat This protects the unit against excessive condensing pressure The high pressurestat has factory fixed non adjustable settings To check see section Initial checks Low pressurestat This protects the 40ALZ units against excessive low pressure in the evaporator or in the refri gerant lines It is not operational in heat pump mode The low pressurestat has fa...

Page 26: ...compressor and the unit Ensure that no faulty contacts exist in the terminal blocks contactor boards etc Make sure that all the electrical connections are properly tightened and that all the electrical components contactors relays etc are firmly secured to the corresponding rails Pay special attention to the condition of the connecting cables between the control elements and the electrical box and...

Page 27: ...rwise the new compressor will also be damaged In order to remove the acid proceed as follows a Thoroughly clean the refrigerant circuit using dry nitrogen in the opposite direction to the refrigerant flow or another cleaning element Also carefully clean the separate parts of the refrigerant circuit Install anti acid filters in the liquid line Solder the refrigerant lines Evacuate the lines and cha...

Page 28: ...Spain Manufacturer reserves the right to change any product specifications without notice Printed in the Netherlands FINAL RECOMMENDATIONS The unit you have purchased has undergone strict quality control procedures before leaving the factory All components including the control systems and electrical equipment etc are certified by our Quality Control Depart ment and tested under the harshest possi...

Reviews: