 Page 24 

Indoor Unit 

Installation

 

 

 

 WARNING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.

Unscrew the cable clamp below the terminal 

block and place it to the side.

4.

Facing the back of the unit, remove the plastic 

panel on the bottom left-hand side.

ALL WIRING MUST BE PERFORMED 
STRICTLY IN ACCORDANCE WITH THE 
WIRING DIAGRAM LOCATED ON THE 
BACK OF THE INDOOR UNIT S FRONT 
PANEL .

5.  Feed the signal wire through this slot, from 

the back of the unit to the front.

6.  Facing the front of the unit, connect the wire 

according to the indoor unit’s wiring diagram, 

connect the u-lug and firmly screw each wire

to its corresponding terminal.

 CAUTION

DO NOT MIX UP LIVE AND NULL WIRES

This is dangerous, and can cause the air 

conditioning unit to malfunction.

7. 

After checking to make sure every connection

is secure, use the cable clamp to fasten the 

signal cable to the unit. Screw the cable clamp 

down tightly.

8. 

Replace the wire cover on the front of the 

unit, and the plastic panel on the back.

DRAIN HOSE MUST BE ON BOTTOM

Make sure that the drain hose is at the bottom 

of the bundle. Putting the drain hose at the  

top of the bundle can cause the drain pan 

to overflow, which can lead to fire or water 

damage.

DO NOT INTERTWINE SIGNAL CABLE WITH 

OTHER WIRES

While bundling these items together, do not 

intertwine or cross the signal cable with any 

other wiring.

2.

 

Using adhesive vinyl tape, attach the drain 

hose to the underside of the refrigerant pipes.

3.

  Using insulation tape, wrap the signal wire, 

refrigerant pipes, and drain hose tightly 

together. Double-check that all items are 

bundled.

DO NOT WRAP ENDS OF PIPING

When wrapping the bundle, keep the ends 

of the piping unwrapped. You need to access 

them to test for leaks at the end of the 

installation process (refer to 

Electrical Checks 

 

and Leak Checks 

section of this manual).

 NOTE ABOUT WIRING

 

 

 

 

 

 

THE WIRING CONNECTION PROCESS MAY
DIFFER SLIGHTLY BETWEEN UNITS AND 
REGIONS. 

Before passing the piping, drain hose, and the 

signal cable through the wall hole, you must 

bundle them together to save space, protect 

them, and insulate them(Not applicable in 
North America).

1. 

Bundle the drain hose, refrigerant pipes, and 

signal cable as shown below:

Indoor Unit

Space behind unit

Refrigerant piping

Drain hose

Signal wire

Insulation tape

Step 7: Wrappiping and cables

1.  O

pen front panel of the indoor unit.

2. 

Using a screwdriver, open the wire box cover 

on the right side of the unit, then open the 
termianl block cover. This will reveal the
terminal block. 

Wire box cover

Screw

Screw

Terminal block

cover

Cable clamp

Summary of Contents for 38QHP09E8S series

Page 1: ...Owner s Manual Installation Manual SPLIT TYPE ROOM AIR CONDITIONER 42QHP09E8S 38QHP09E8S 42QHP12E8S 38QHP12E8S...

Page 2: ......

Page 3: ...Owner s Manual Table of Contents Safety Precautions 03 Care and Maintenance 12 Troubleshooting 14 1 Indoor unit display 07 2 Operating temperature 08 3 Other features 09 4 Setting angle of airflow 10...

Page 4: ...Mount indoor unit 25 Outdoor Unit Installation 26 1 Select installation location 26 2 Install drain joint 27 3 Anchor outdoor unit 27 4 Connect signal and power cables 29 Refrigerant Piping Connectio...

Page 5: ...ike a burning smell immediately turn off the unit and disconnect the power Call your dealer for instructions to avoid electric shock fire or injury Do not insert fingers rods or other objects into the...

Page 6: ...rd to power the unit Do not share the electrical outlet with other appliances Improper or insufficient power supply can cause fire or electrical shock If connecting power to fixed wiring an all pole d...

Page 7: ...install the appliance to its support please read the information for details in indoor unit installation and outdoor unit installation sections For units that have an auxiliary electric heater do not...

Page 8: ...cal equipment should not be mixed with general household waste 2 2 2 2 2 2 When flammable refrigerant are employed appliance shall be stored in a well ventilated area where the room size corresponds t...

Page 9: ...C 54 F heating mode is turned on some units when fresh feature is turned on some units when ECO feature is activated some units when wireless control feature is activated some units Display Code Meani...

Page 10: ...2 F 15 C 30 C 5 F 86 F 0 C 50 C 32 F 122 F 0 C 52 C 32 F 126 F For special tropical models 0 C 52 C 32 F 126 F For special tropical models 15 C 50 C 5 F 122 F For models with low temp cooling systems...

Page 11: ...temperature 1hr 1hr Keep running SLEEP Operation Saving energy during sleep Heat mode 1 C 2 F per hour for the first two hours Cool mode 1 C 2 F per hour for the first two hours A guide on using the i...

Page 12: ...The wind flow follow people feature is only available for a single people area If press the SWING button on the remote control this feature will stops automatically 1 Press the SWING horizontal air f...

Page 13: ...l of the indoor unit and raise it until it clicks in place 2 Locate the MANUAL CONTROL button on the right hand side of the display box 3 Press the MANUAL CONTROL button one time to activate FORCED AU...

Page 14: ...posing it to direct sunlight 8 When dry re clip the air freshening filter to the larger filter then slide it back into the indoor unit 9 Close the front panel of the indoor unit Remove air freshening...

Page 15: ...If you plan not to use your air conditioner for an extended period of time do the following Clean all filters Turn on FAN function until unit dries out completely Turn off the unit and disconnect the...

Page 16: ...Troubleshooting Troubleshooting The unit changes from COOL HEAT mode to FAN mode The indoor unit makes noises A rushing air sound may occur when the louver resets its position A squeaking sound may o...

Page 17: ...customer service center Provide them with a detailed description of the unit malfunction as well as your model number Troubleshooting Troubleshooting When troubles occur please check the following po...

Page 18: ...oor heating performance The outdoor temperature is extremely low Use auxiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows are closed during use...

Page 19: ...Shape Quantity PC Need to be installed on the back of main air filter by the authorized technician while installing the machine Mounting plate fixing screw Remote controller Fixing screw for remote co...

Page 20: ...Mounting Plate Determine Wall Hole Position 1 2 3 Drill Wall Hole 4 12cm 4 75in 2 3m 90 55in 12cm 4 75in 15cm 5 9in Mount Indoor Unit STEP 8 Wrap Piping and Cable not applicable for some locations in...

Page 21: ...local and national standards The installation may be slightly different in different areas Wall Mounting Plate Power Cable Some Units Refrigerant Piping Signal Cable Remote Controller Drainage Pipe Lo...

Page 22: ...irect sunlight NOTE ABOUT WALL HOLE If there is no fixed refrigerant piping While choosing a location be aware that you should leave ample room for a wall hole see Drill wall hole for connective pipin...

Page 23: ...indoor end by about 5mm to 7mm 0 2 0 275in This will ensure proper water drainage 3 Place the protective wall cuff in the hole This protects the edges of the hole and will help seal it when you finis...

Page 24: ...ation to prevent condensation The refrigerant piping is inside an insulating sleeve attached to the back of the unit You must prepare the piping before passing it through the hole in the wall 1 Based...

Page 25: ...the compressor or any moving parts within the unit If the unit has an auxiliary electric heater it must be installed at least 1 meter 40in away from any combustible materials To avoid getting an elect...

Page 26: ...amage DO NOT INTERTWINE SIGNAL CABLE WITH OTHER WIRES While bundling these items together do not intertwine or cross the signal cable with any other wiring 2 Using adhesive vinyl tape attach the drain...

Page 27: ...re to the left and right hand sides of the unit The unit should not jiggle or shift 6 Using even pressure push down on the bottom half of the unit Keep pushing down until the unit snaps onto the hooks...

Page 28: ...wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind Strong wind If the unit is frequently exposed to heavy rain or sn...

Page 29: ...bber seal see Fig B do the following 1 Insert the drain joint into the hole in the base pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain j...

Page 30: ...led holes 5 Remove the nuts from expansion bolts and place outdoor unit on bolts 6 Put washer on each expansion bolt then replace the nuts 7 Using a wrench tighten each nut until snug WARNING WHEN DRI...

Page 31: ...nd the unit in accordance with local codes 6 Be sure to size each wire allowing several inches longer than the required length for wiring 7 Use lock nuts to secure the conduit tubes BEFORE PERFORMING...

Page 32: ...and injury Oblique Rough Warped 90 DO NOT DEFORM PIPE WHILE CUTTING Be extra careful not to damage dent or deform the pipe while cutting This will drastically reduce the heating efficiency of the unit...

Page 33: ...rs from falling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of the pipe Pipe Reamer Point down Step 3 Flare pipe ends Proper flaring is essential to achieve...

Page 34: ...0 76 0 78 23 2 23 7 0 91 0 93 18 20 180 200kgf cm 32 39 320 390kgf cm 49 59 490 590kgf cm 57 71 570 710kgf cm 67 101 670 1010kgf cm 9 52 0 375 12 7 0 5 16 0 63 19 0 75 1 Unscrew the cover from the pa...

Page 35: ...for at least 15 minutes or until the Compound Meter reads 76cmHG 10 Pa 2 3 4 5 5 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that...

Page 36: ...0Btu h and 24000Btu h ADDITIONAL REFRIGERANT PER PIPE LENGTH Connective Pipe Length m Air Purging Method Additional Refrigerant Standard pipe length Vacuum Pump N A Standard pipe length Vacuum Pump Li...

Page 37: ...ethod Using a soft brush apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit The presence of bubbles indicates a leak Leak Detector Method If using...

Page 38: ...pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take time during the Test Run to double check that all refrigerant pipe con...

Page 39: ......

Page 40: ...s are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website please...

Reviews: