![Carrier 38QHC009D8S Series Service Manual Download Page 51](http://html1.mh-extra.com/html/carrier/38qhc009d8s-series/38qhc009d8s-series_service-manual_2560745051.webp)
49
10.2.10 Inverter compressor drive error diagnosis and solution(P4)
Error Code
P4
Malfunction decision
conditions
An abnormal inverter compressor drive is detected by a special
detection circuit, including communication signal detection,
voltage detection, compressor rotation speed signal detection
and so on.
Supposed causes
●
Wiring mistake
●
IPM malfunction
●
Outdoor fan ass’y faulty
●
Compressor malfunction
●
Outdoor PCB faulty
Trouble shooting:
Check the wiring between main PCB
and compressor
Correct the connection or replace
the wires and connectors.
Yes
No
Check the IPM
No
Yes
Replace the IPM board or replace
the main PCB
Check the outdoor fan and the
outdoor unit ventilation
No
Please refer to the solution of
【
Fan
Speed Has Been Out Of Control
】
malfunction
Yes
Check the compressor resistance
values
No
Replace the compressor.
Yes
Replace the outdoor main PCB
Summary of Contents for 38QHC009D8S Series
Page 1: ...QHC R32 Inverter Series Service Manual R32...
Page 12: ...10 For 42QHC009D8S For 42QHC012D8S For 42QHC018D8S...
Page 13: ...11 For 42QHC024D8S...
Page 23: ...21 8 Wiring Diagram 8 1 Indoor Unit 42QHC009D8S 42QHC012D8S 42QHC018D8S 42QHC024D8S...
Page 24: ...22 8 2 Outdoor Unit 38QHC009D8S 38QHC012D8S...
Page 25: ...23 38QHC018D8S 38QHC024D8S...