Pressure on Service Port (Cont)
Table 19 — Heating Chart (R410A)
Fig. 44 — Heating Chart
°F(°C)
ODU(DB/WB)
IDU(DB)
57/53
(13.89/11.67)
47/43
(8.33/6.11)
37/33
(2.78/0.56)
27/23
(-2.78/-5)
17/13
(-8.33/-10.56)
0/-2
(-17/-19)
-17/-18
(-27/-28)
BAR
55(12.78)
30.3
28.5
25.3
22.8
20.8
18.5
16.5
65(18.33)
32.5
30.0
26.6
25.4
23.3
20.5
19.0
75(23.89)
33.8
31.5
27.8
26.3
24.9
21.5
20.0
PSI
55(12.78)
439
413
367
330
302
268
239
65(18.33)
471
435
386
368
339
297
276
75(23.89)
489
457
403
381
362
312
290
MPa
55(12.78)
3.03
2.85
2.53
2.28
2.08
1.85
1.65
65(18.33)
3.25
3.00
2.66
2.54
2.33
2.05
1.90
75(23.89)
3.38
3.15
2.78
2.63
2.49
2.15
2.00
0
0.5
1
1.5
2
2.5
3
3.5
4
55
65
75