![Carrier 38MAQB09 Series Product Data Download Page 11](http://html1.mh-extra.com/html/carrier/38maqb09-series/38maqb09-series_product-data_2560695011.webp)
11
AIR FLOW DATA
SYSTEM SIZE
9
12
Indoor (CFM)
High
280
280
Medium
250
250
Low
220
220
Outdoor (CFM)
945
945
SOUND PRESSURE
SYSTEM SIZE
9
12
Cooling operation Indoor Sound
Pressure
dBa (L/M/H)
37/38/41
34/41/45
Heating operation Indoor Sound
Pressure
dBa (L/M/H)
37/38/41
34/41/45
Outdoor sound pressure level
dBa
55.5
56
SOUND POWER
SYSTEM SIZE
9
12
Cooling operation Indoor Sound
Power
dBa (L/M/H)
46/47/50
44/51/55
Heating operation Indoor Sound
Power
dBa (L/M/H)
46/47/50
44/51/55
Outdoor sound power level
dBa
65
66
ELECTRICAL DATA
UNIT
SIZE
OPER. VOLTAGE
MAX / MIN*
COMPRESSOR
OUTDOOR FAN
INDOOR FAN
MCA
MAX FUSE CB
AMP
V---PH---HZ
RLA
V---PH---HZ
FLA
HP
W
V---PH---HZ
FLA
HP
W
9
253 / 187
208---230/1/60
5.3
208---230/1/60
3
0.053
40
208---230/1/60
0.21 0.027
20
15
15
12
5.7
3
0.053
40
0.21 0.027
20
15
15
*Permissible limits of the voltage range at which the unit will operate satisfactorily
LEGEND
FLA -- Full Load Amps
LRA -- Locked Rotor Amps
MCA -- Minimum Circuit Amps
RLA -- Rated Load Amps