background image

Product Data

40MB*F / 38MAQ

Floor Console Ductless Split System

Sizes 09 to 12

INDUSTRY LEADING

FEATURES / BENEFITS

A PERFECT BALANCE BETWEEN

BUDGET LIMITS, ENERGY SAVINGS AND

COMFORT.

The 38/40MBF series ductless split systems are a matched

combination of an outdoor condensing unit and an indoor fan coil

unit connected only by refrigerant tubing and wires.
The fan coil is mounted on the floor, against the wall. This

selection of fan coils permits creative solutions to design problems

such as:

S

Add--ons to current space (an office or family room
addition)

S

Special space requirements

S

When changes in the load cannot be handled by the
existing system.

S

When adding air conditioning to spaces that are heated
by hydronic or electric heat and have no ductwork.

S

Historical renovations or any application where
preserving the look of the original structure is essential.

The ideal compliment to your ducted system when it is

impractical or prohibitively expensive to use ductwork.
These compact indoor fan coil units take up very little space in the

room and do not obstruct windows. The fan coils are attractively

styled to blend with most room decors. Advanced system

components incorporate innovative technology to provide reliable

cooling performance at low sound levels.

Summary of Contents for 38MAQB09 Series

Page 1: ...mily room addition S Special space requirements S When changes in the load cannot be handled by the existing system S When adding air conditioning to spaces that are heated by hydronic or electric heat and have no ductwork S Historical renovations or any application where preserving the look of the original structure is essential The ideal compliment to your ducted system when it is impractical or...

Page 2: ...oor units service and maintenance expense is reduced due to easy to use cleanable filters In addition these floor console systems have extensive self diagnostics to assist in troubleshooting BUILT IN RELIABILITY Ductless split system indoor and outdoor units are designed to provide years of trouble free operation The floor console indoor units include protection against freeze up and high evaporat...

Page 3: ... B Q MAXIMUM NUMBER OF FAN COIL UNITS THAT CAN BE CONNECTED TO THE OUTDOOR UNIT B 1 1 SYSTEM TYPE Q HEAT PUMP NOT USED OUTDOOR UNIT 38 MA 3 09 38 OUTDOOR UNIT MA MODEL VOLTAGE 3 208 230 1 60 NOMINAL CAPACITY 09 3 4 TON 12 1 TON UNIT TYPE OUTDOOR UNIT Use of the AHRI Certified TM Mark indicates a manufacturer s participation in the program For verification of certification for individual products g...

Page 4: ...Of Service And Maintenance Cleanable Filters S Diagnostics S Liquid Line Pressure Taps S Application Flexibility Condensate Pumps A Crankcase Heater S Basepan Heater S Legend S Standard A Accessory INDOOR UNITS Fig 1 Condensate Pump Accessory On floor console fan coils the condensate pump has a lift capability of 12 ft 3 6 m on the discharge side with the pump mounted in the fan coil or 6 ft 1 8 m...

Page 5: ...7 210 Width in mm 27 56 700 27 56 700 Depth in mm 23 62 600 23 62 600 Weight Net Lb kg 32 41 14 7 32 41 14 7 DIMENSIONS OUTDOOR Fig 3 Outdoor unit MODEL W in mm D in mm H in mm L1 in mm L2 in mm OPERATING WEIGHT lb kg 9K 12K 32 0 810 12 2 310 22 0 558 20 9 530 11 4 290 82 5 37 4 ...

Page 6: ...6 CLEARANCES INDOOR Fig 4 Indoor Unit Clearance CLEARANCES OUTDOOR A D B Air outlet Air inlet C E Fig 5 Clearances Outdoor UNIT Minimum Value in mm A 24 609 B 24 609 C 24 609 D 4 101 E 4 101 ...

Page 7: ...Design Pressure PSIG 550 550 Metering Device EEV EEV Charge Lb 2 76 2 76 Outdoor Coil Face Area Sq Ft 9 2 9 2 No Rows 2 2 Fins per inch 21 21 Circuits 4 4 Indoor Coil Face Area sq ft Sq Ft 2 1 2 1 No Rows 2 2 Fins per inch 19 19 Circuits 2 2 Compressor Type Hermetic Rotary DC Inverter Compressor Model ASM98D1UFZA ASM108D1UFZA Oil Type VG74 VG74 Oil Charge Fl Oz 12 5 12 5 Rated Current RLA 5 3 5 7 ...

Page 8: ... 6F 7C 39 2F 4C 32F 0C 24 8F 4C 19 4F 7C 17F 8C 5F 15C 0F 17C 4F 20C 09 208 230V 59F 15C TC 11 18 11 08 10 89 10 65 9 87 9 11 8 27 6 71 6 21 5 80 Input 0 73 0 79 1 04 1 01 0 96 0 9 0 84 0 8 0 79 0 78 COP 4 49 4 11 3 07 3 09 3 01 2 97 2 88 2 46 2 30 2 18 64 4F 18C TC 11 06 10 82 10 65 10 54 9 63 8 84 8 01 5 46 5 02 4 60 Input 0 78 0 8 1 08 1 03 0 98 0 94 0 9 0 82 0 81 0 80 COP 4 15 3 96 2 89 3 00 2...

Page 9: ...ne hole locations SUPPORT Adequate support must be provided to support the weight of all fan coils Refer to the Physical Data section for fan coil weights and the base unit dimensional drawings for the location of mounting brackets SYSTEM OPERATING CONDITIONS OPERATING RANGE Min Max F C Cooling Heating Outdoor DB 4 122 20 50 4 86 20 30 Indoor DB 63 90 17 32 32 86 0 30 Indoor WB 59 84 15 29 NON OPE...

Page 10: ...codes S Use copper conductors only with a 600 volt rating and double insulated copper wire CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation S Be sure to comply with local codes while running wire from indoor unit to outdoor unit S Every wire must be connected firmly Loose wiring may cause terminal to overheat or result in unit malf...

Page 11: ...er dBa L M H 46 47 50 44 51 55 Heating operation Indoor Sound Power dBa L M H 46 47 50 44 51 55 Outdoor sound power level dBa 65 66 ELECTRICAL DATA UNIT SIZE OPER VOLTAGE MAX MIN COMPRESSOR OUTDOOR FAN INDOOR FAN MCA MAX FUSE CB AMP V PH HZ RLA V PH HZ FLA HP W V PH HZ FLA HP W 9 253 187 208 230 1 60 5 3 208 230 1 60 3 0 053 40 208 230 1 60 0 21 0 027 20 15 15 12 5 7 3 0 053 40 0 21 0 027 20 15 15...

Page 12: ...current Amps 0 21 0 21 Rated HP HP 0 027 0 027 Speed rev min 730 680 580 520 730 680 580 520 Rated RPM rev min 1062 1062 Max input W 66 6 66 6 Outdoor fan material AS AS Type ZL 421 117 8 3K ZL 421 117 8 3K Diameter inch 16 6 16 6 Height inch 4 6 4 6 Outdoor fan motor Model WZDK40 38G W 1 WZDK40 38G W 1 Phase DC DC FLA 3 3 Type 0 42 0 42 Insulation class E E Safe class IPX0 IPX0 Input W 46 46 Outp...

Page 13: ...1 5VDC Connection of the Switch board CN16 Output 320VDC Connection of the Fan high voltage CN20 Output 5VDC Connection of the Net module CN23 Output 1 12VDC Connection of the Remote switch OUTDOOR UNIT CONTROL BOARD OUTDOOR UNIT CODE PART NAME CN31 Output Pin5 6 12V Pin1 Pin4 Pulse waveform 0 12V CN21 Input Pin3 4 3 3V Pin2 0V Pin1 Pin5 0 3 3V CN22 Input Pin1 3 3V Pin2 0 3 3V CN37 Output 230VAC H...

Page 14: ...of 1_F or 1_C and have 46_F Heating Mode Heating Setback The wireless remote controller shall have the ability to act as the temperature sensing location for room comfort The unit shall have the following functions as a minimum 1 An automatic restart after power failure at the same operating conditions as at failure 2 A timer function to provide a minimum 24 hour timer cycle for system Auto Start ...

Page 15: ... air through the outdoor coil 2 Outdoor fan motors shall be totally enclosed single phase motors with class E insulation and permanently lubricated ball bearings Motor shall be protected by internal thermal overload protection 3 Shaft shall have inherent corrosion resistance 4 Fan blades shall be non metallic and shall be statically and dynamically balanced 5 Outdoor fan openings shall be equipped...

Page 16: ...p D 7310 W Morris St D Indianapolis IN 46231 Edition Date 11 15 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 38 40MBF 03PD Replaces 38 40MBF 02PD ...

Reviews: