CONNECTING ELECTRICAL WIRING (Cont.)
18-3 ELECTRICAL DATA
Split
System
Model
Starting
Current
(Note 1)
Nominal
System
Power
Supply
Electrical Consumption
Circuit
Breaker
Cooling
Heating
****
35 °C
*
46 °C
**
52 °C
***
Heat Pump
Amp V/Ph/Hz Amp Watt Amp Watt Amp Watt
Amp
Watt
Amp
53QHET12 35 220-240 5.6
1236 6.6 1484 7.1 1619 5.1 1050 16
53QHET18 58 220-240 8.9
1848 10.6 2282 11.5 2519 8.5 1745 20
53QHET24 68 220-240 12.1 2556 14.5 3056 16.1 3329 10.7 2345 25
Cool Only
Amp V/Ph/Hz Amp Watt Amp Watt Amp Watt
Amp
Watt Amp
53KHET12 35 220-240 5.7
1250 6.6 1470 7.1 1604
16
53KHET18 50 220-240 8.9
1882 10.8 2335 11.8 2582
20
53KHET24 68 220-240 12.1 2554 13.9 3056 15.0 3299
25
NOTES
1. Starting Current duration is usually less than 1 Second.
2. Operating Conditions.
* @ 35ºC db outdoor temperature :
27/19ºC db/wb Indoor Temperature. High air flow of indoor unit
** @ 46ºC db outdoor temperature :
29/19ºC db/wb Indoor Temperature. High air flow of indoor unit
*** @ 52ºC db outdoor temperature :
32/23ºC db/wb Indoor Temperature. High air flow of indoor unit
**** Standard operating conditions for heating
Indoor 20 °C DBT Outdoor 7/6 °C DBT/WBT High air flow of indoor unit