background image

If ANY refrigerant tubing is buried, provide a 6 in. vertical
rise at service valve. Refrigerant tubing lengths up to 36 in.
may be buried without further special consideration. Do not
bury lines for lengths over 36 in.

To prevent damage to unit or service valves observe the
following:
• Use a brazing shield
• Wrap service valves with wet cloth or use a heat sink
material.

Outdoor units may be connected to indoor section using accessory
tubing package or field-supplied refrigerant grade tubing of correct
size and condition. For tubing requirements beyond 50 ft, substan-
tial capacity and performance losses can occur. Following the
recommendations in the Application Guideline and Service
Manual — Residential Split-System Air Conditioners and Heat
Pumps Using Puron® Refrigerant will reduce these losses. Refer
to Table 1 for field tubing diameters. Refer to Table 2 for
accessory requirements.

No buried-line applications greater than 36 in.

If refrigerant tubes or indoor coil are exposed to atmosphere, they
must be evacuated to 500 microns to eliminate contamination and
moisture in the system.

OUTDOOR UNIT CONNECTED TO FACTORY-APPROVED
INDOOR UNIT

Outdoor unit contains correct system refrigerant charge for opera-
tion with ARI rated indoor unit with highest sales volume when
connected by 15 ft of field-supplied or factory-accessory tubing.
Check refrigerant charge for maximum efficiency.

INSTALL LIQUID-LINE FILTER DRIER

Installation of filter drier in liquid line is required.

Refer to Fig. 6 and install filter drier as follows:

1. Braze 5-in. connector tube to liquid service valve. Wrap filter

drier with damp cloth.

2. Braze filter drier between connector tube and liquid tube to

indoor coil. Flow arrow must point towards indoor coil.

REFRIGERANT TUBING

Connect vapor tube to fitting on outdoor unit vapor service valves.
Connect liquid tube to filter drier. (See Fig. 6 and Table 1.) Use
refrigerant grade tubing.

SWEAT CONNECTION

To avoid valve damage while brazing, service valves must be
wrapped in a heat-sink material such as a wet cloth.

Service valves are closed from factory and ready for brazing. After
wrapping service valve and filter drier with a wet cloth, braze
sweat connections using industry accepted methods and materials.
Consult local code requirements. Refrigerant tubing and indoor
coil are now ready for leak testing. This check should include all
field and factory joints.

EVACUATE REFRIGERANT TUBING AND INDOOR COIL

Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. The alternate
triple evacuation method may be used if the procedure outlined
below is followed. Always break a vacuum with dry nitrogen.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of
pulling a vacuum of 500 microns and a vacuum gage capable of
accurately measuring this vacuum depth. The deep vacuum
method is the most positive way of assuring a system is free of air
and liquid water. (See Fig. 7.)

Triple Evacuation Method

The triple evacuation method should only be used when vacuum
pump is only capable of pumping down to 28 in. of mercury
vacuum and system does not contain any liquid water. Refer to
Fig. 8 and proceed as follows:

1. Pump system down to 28 in. of mercury and allow pump to

continue operating for an additional 15 minutes.

2. Close service valves and shut off vacuum pump.

3. Connect a nitrogen cylinder and regulator to system and open

until system pressure is 2 psig.

4. Close service valve and allow system to stand for 1 hr. During

this time, dry nitrogen will be able to diffuse throughout the
system absorbing moisture.

5. Repeat this procedure as indicated in Fig. 8. System will then

be free of any contaminants and water vapor.

FINAL TUBING CHECK

IMPORTANT:

Check to be certain factory tubing on both indoor

and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal. Pay close
attention to feeder tubes, making sure wire ties on feeder tubes are
secure and tight.

Step 8—Make Electrical Connections

To avoid personal injury or death, do not supply power to unit
with compressor terminal box cover removed.

Be sure field wiring complies with local and national fire, safety,
and electrical codes, and voltage to system is within limits shown
on unit rating plate. Contact local power company for correction of
improper voltage. See unit rating plate for recommended circuit
protection device.

NOTE:

Operation of unit on improper line voltage constitutes

abuse and could affect unit reliability. See unit rating plate. Do not

Fig. 5—Position of Sensing Bulb

A81032

2  O'CLOCK

10  O'CLOCK

SENSING  BULB

STRAP

SUCTION  TUBE

8  O'CLOCK

4  O'CLOCK

7

8

 IN. OD &  SMALLER

LARGER  THAN 

 

7

8

 IN. OD

 

4

Summary of Contents for 38ESA

Page 1: ...erate at higher pressures than standard R 22 systems Do not use R 22 service equipment or com ponents on Puron equipment INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 Ensure that vapor and liquid tube...

Page 2: ...must be maintained Maintain a distance of 24 in between units Position so water snow or ice from roof or eaves cannot fall directly on unit Step 4 Operating Ambients The minimum outdoor operating ambient in cooling mode is 55 F and the maximum outdoor operating ambient in cooling mode is 125 F Step 5 Check Indoor AccuRater Piston and Install Piston Ring 38EZA Standard If unit is to be installed wi...

Page 3: ...revent damage to tubing 5 Using wire cutters cut equalizer tube off flush with vapor tube inside cabinet 6 Remove bulb from vapor tube inside cabinet 7 Braze equalizer stub tube closed Use protective barrier as necessary to prevent damage to drain pan IMPORTANT Route the equalizer tube of Puron TXV through suction line connection opening in fitting panel prior to replacing fitting panel around tub...

Page 4: ...ubing and indoor coil are now ready for leak testing This check should include all field and factory joints EVACUATE REFRIGERANT TUBING AND INDOOR COIL Never use the system compressor as a vacuum pump Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns The alternate triple evacuation method may be used if the procedure outlined below is fol...

Page 5: ...be Diameter Connection Diameter Tube Diameter Connection Diameter Tube Diameter 018 024 3 8 3 8 5 8 5 8 5 8 3 4 030 036 3 8 3 8 3 4 3 4 3 4 7 8 042 048 3 8 3 8 7 8 7 8 7 8 1 1 8 060 3 8 3 8 7 8 1 1 8 7 8 1 1 8 NOTES 1 Tube diameters are for lengths up to 50 ft For tubing lengths greater than 50 ft horizontal or greater than 20 ft vertical differential consult the Application Guideline and Service ...

Page 6: ...l Electrical Accessories Refer to the individual instructions packaged with kits or acces sories when installing Step 11 Start Up To prevent compressor damage or personal injury observe the following Do not overcharge system with refrigerant Do not operate unit in a vacuum or at negative pressure Do not vent refrigerant to atmosphere Recover during system repair or final unit disposal Do not disab...

Page 7: ...y relay circuit the indoor blower runs an additional 90 sec to increase system efficiency Step 12 Check Charge UNIT CHARGE Factory charge and charging method are shown on unit informa tion plate Charge Puron units using a commercial type metering device in manifold hose Charge refrigerant into suction line NOTE If superheat or subcooling charging conditions are not favorable charge must be weighed...

Page 8: ...on note superheat 7 Refer to Table 6 Find superheat temperature located in item 6 and suction pressure At this intersection note suction line temperature 8 If a unit has a higher suction line temperature than charted temperature add refrigerant until charted temperature is reached 9 If unit has a lower suction line temperature than charted temperature reclaim refrigerant until charted temperature ...

Page 9: ...3 55 57 59 10 45 47 49 51 53 55 57 59 61 12 47 49 51 53 55 57 59 61 63 14 49 51 53 55 57 59 61 63 65 16 51 53 55 57 59 61 63 65 67 18 53 55 57 59 61 63 65 67 69 20 55 57 59 61 63 65 67 69 71 22 57 59 61 63 65 67 69 71 73 24 59 61 63 65 67 69 71 73 75 26 61 63 65 67 69 71 73 75 77 28 63 65 67 69 71 73 75 77 79 30 65 67 69 71 73 75 77 79 81 32 67 69 71 73 75 77 79 81 83 34 69 71 73 75 77 79 81 83 85...

Page 10: ...CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 C SEE NOTE 2 G A97367 24 VAC HOT 24 VAC COM R C G W W1 Y Y2 R C C CARRIER NON PROGRAMMABLE THERMOSTAT MODEL AC FA FB FC FD FF FX FAN COIL AIR CONDITIONER SEE NOTE 2 G W2 HEAT STAGE 1 COOL STAGE 1 INDOOR FAN A97594 24 VAC HOT R G W W1 Y Y2 O W2 R W2 C B S1 S2 CARRIER PROGRAMMABLE THERMOSTAT MODEL AC FA FB FC FD FF FX FAN COIL AIR CONDITIONER G Y1 W...

Page 11: ...AN COIL AIR CONDITIONER G Y1 W2 L INDOOR FAN HEAT STAGE 1 COOL STAGE 1 NOT USED 24 VAC COM NOT USED NOT USED NOT USED OPTIONAL OUTDOOR SENSOR CONNECTION C Y1 O C SEE NOTE 2 J2 JUMPER J1 JUMPER A97597 WIRING DIAGRAM NOTES 1 CARRIER THERMOSTAT WIRING DIAGRAMS ARE ONLY ACCURATE FOR MODEL NUMBERS TSTAT _______ 2 WIRING MUST CONFORM TO NEC OR LOCAL CODES 3 SOME UNITS ARE EQUIPPED WITH PRESSURE SWITCH E...

Page 12: ...riers with rated working pressures less than 600 psig Do not install a suction line filter drier in liquid line POE oils absorb moisture rapidly Do not expose oil to atmosphere Poe oils may cause damage to certain plastics and roofing materials Wrap all filter driers and service valves with wet cloth when brazing A factory approved liquid line filter drier is required on every unit Do not use an R...

Reviews: