38CKP 50 Hz

Air Conditioning Unit

Installation and Start-Up Instructions

NOTE:

Read the entire instruction manual before starting the

installation.

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.

Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions thor-
oughly and follow all warnings or cautions included in literature
and attached to the unit. Consult local building codes and National
Electrical Code (NEC) for special requirements.

Recognize safety information. This is the safety-alert symbol

.

When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.

Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies hazards which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.

Before installing, modifying, or servicing system, main elec-
trical disconnect switch must be in the OFF position. There
may be more than 1 disconnect switch. Lock out and tag
switch with a suitable warning label. Electrical shock can
cause personal injury or death.

INTRODUCTION

These are the Installation and Start-Up Instructions for the
38CKP—50 Hz Air Conditioning Unit.

INSTALLATION

Step 1—Check Equipment and Job Site

UNPACK UNIT

Move to final location. Remove carton, taking care not to damage
unit.

INSPECT EQUIPMENT

File claim with shipping company prior to installation if shipment
is damaged or incomplete. Locate unit-rating plate on unit service

panel. (See Fig. 2.) It contains information needed to properly
install unit. Check rating plate to be sure unit matches job
specifications.

Step 2—Install on a Solid, Level Mounting Pad

If conditions or local codes require the unit be attached to pad,
tie-down bolts should be used and fastened through knockouts
provided in unit base pan. Refer to unit-mounting pattern in Fig. 2
to determine base-pan size and knockout-hole location.

When installing, allow sufficient space for airflow clearance,
wiring, refrigerant piping, and service. Allow 30-in. (762mm)
clearance to service end of unit and 48 in. (1219mm) above unit.

For proper airflow, a 6-in. (152mm) clearance on 1 side of unit and
12 in. (305mm) on all remaining sides must be maintained.
Maintain a distance of 24 in. (610mm) between air conditioners.
Position so water, snow, or ice from roof or eaves cannot fall
directly on unit.

On rooftop applications, locate unit 6 in. (152mm) above roof
surface. Where possible, place unit above a load-bearing wall.
Arrange supporting members to adequately support unit and
minimize transmission of vibration to building. Consult local
codes governing rooftop applications.

Step 3—Replace Indoor AccuRater® Piston, if Required

Check indoor coil piston to see if it matches the required piston
shown on outdoor unit rating plate. If it does not match, replace
indoor coil piston with piston shipped with the outdoor unit. The
piston shipped with outdoor unit is correct for any approved indoor
coil combination.

Fig. 1—Model 38CKP

A97005

Visit www.carrier.com

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

4

Tab

3a 2a

PC 101

Catalog No. 003-80022

Printed in U.S.A.

Form 38CKP-C1SI

Pg 1

10-04

Replaces: New

Summary of Contents for 38CKP

Page 1: ...or death INTRODUCTION These are the Installation and Start Up Instructions for the 38CKP 50 Hz Air Conditioning Unit INSTALLATION Step 1 Check Equipment and Job Site UNPACK UNIT Move to final location...

Page 2: ...rm to shape of tubing insulation See Fig 3 10 Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation If refrigerant tubes or indoor coil is exposed to atmo...

Page 3: ...it rating plate Do not install unit in system where voltage or phase imbalance may fluctuate above or below permissible limits NOTE Use copper wire only between disconnect switch and unit NOTE Install...

Page 4: ...alves Do not vent refrigerant to atmosphere Recover during system repair or final unit disposal 1 Fully back seat open liquid and vapor tube service valves 2 Unit is shipped with valve stem s front se...

Page 5: ...owner Explain system operation and periodic maintenance requirements outlined in manual Frequency of maintenance may vary depending on geographic areas such as coastal applications which require more...

Page 6: ...UNIT ONE STAGE COOLING HEATING ACCESSORY LIQUID LINE SOLENOID NOTES 1 Wiring must conform to local codes 2 LLS required on some units See specific unit instructions 3 Transformer required is 24 v 40...

Page 7: ...7...

Page 8: ...IN 46231 Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 3a 2a PC 101 Catalog No 003 80022...

Reviews: