Fig. 3—38BRC036–060 208/230v, 3 Phase, 60 Hertz

A98016

FACTORY POWER WIRING

FACTORY CONTROL WIRING

FIELD CONTROL WIRING

FIELD POWER WIRING

COMPONENT CONNECTION

FIELD SPLICE

JUNCTION

CONT

CONTACTOR

CAP

CAPACITOR (DUAL RUN)

*CH

CRANKCASE HEATER

*CHS

 CRANKCASE HEATER SWITCH

COMP

COMPRESSOR

*CTD

COMPRESSOR TIME DELAY

*HPS

HIGH PRESSURE SWITCH

IFR

INDOOR FAN RELAY

*LLS

LIQ. LINE SOLENOID VALVE

*LPS

LOW PRESSURE SWITCH

OFM

OUTDOOR FAN MOTOR

* MAY BE FACTORY OR FIELD INSTALLED.

1.

Symbols are electrical representation only.

2.

Compressor and fan motor furnished with inherent thermal protection.

3.

To be wired in accordance with National Electric N.E.C. and local codes.

4.

N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS.

5.

Use copper conductors only. Use conductors suitable for at least 75

°

C (167

°

F).

6.

Connection for typical cooling only thermostat, for other arrangements see installation
instructions.

7.

If indoor section has a transformer with a grounded secondary, connect the
grounded side to the BRN lead.

8.

If any of the original wire, as supplied must be replaced, use the same or equivalent wire.

9.

Check all electrical connections inside control box for tightness.

10. Do not attempt to operate unit until service valves have been opened.
11. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to

equalize between high and low side before starting.

12. It is imperative to connect 3Ø field power to unit with correct phasing. wrong phasing will

cause reverse rotation of scroll compressor which will result in reduced current draw,
elevated noise level and improper operation. If rotation is reversed, simply interchange any
two of the three power connections on field side.

324475-101 REV. A

CONT

OFM

BRN

BLK

208/230 3Ø

POWER

SUPPLY

GND

EQUIP

L1

L3

13

23

VIO

*LPS

YEL

* CTD

*HPS

INDOOR BLOWER MOTOR

EXTERNAL

POWER

SUPPLY

24 V

(NOTE #3)

INDOOR THERMOSTAT

(NOTE #6)

R

G

Y

BRN

BLU

YEL

BLU

*LLS

BLK

BLK

LOGIC

T1

T3

T2

C
R

11

21

T2

T1

T3

BLK

YEL

YEL

BLK

YEL

CAP

COMP

* CH

BLU

IFR

L2

BLU

RED or BLK

RED or BLK

BRN

CONT

L1

11

21

*CH

EQUIP

GND

OFM

CONT

23

13

L3

*LPS

* CTD

*HPS

*LLS

IFR

THERMOSTAT

INDOOR

Y

G

R

C

R

EXTERNAL POWER SUPPLY 24 V

LOGIC

T1

T3

T2

T2

T1

T3

COMP

CAP

L2

CONT

-LEGEND-

-NOTES-

1. Compressor damage may occur if system is overcharged.
2. This unit is factory charged with R-22 in accordance with the amount shown

on the rating plate. The charge is adequate for most systems using matched 
coils and tubing not over 15 feet long. The best performance will be achieved 
when the unit operates with a suction gas superheat at the compressor inlet 
of 5 

°

F at normal rating conditions of the air conditioning and 

refrigeration 

institute (ARI). This chart may be used to approximate the charge if ARI 
rating conditions cannot be obtained.  ARI rating conditions are equivalent 
to DOE test "A" conditions. See product data literature for required indoor 
air flow rates and for use of line lengths over 15 Ft.

3. Carefully relieve  refrigerant pressure within this unit before final disposal.