8
RETURN
AIR
SUBBASE
ACCESSORY
15 DIAMS
MIN
40RMQ024
UNIT
ELECTRIC
HEATER
ACCESSORY
24 V
CONTROL
WIRE
BULB CAPILLARY
TUBES
10 DIAMS
MIN
CONDENSATE
DRAIN
8 DIAMS
MIN
DISCONNECT
PER NEC
INSULATED
VAPOR LINE
FUSED
DISCONNECT
SWITCH*
FUSED
DISCONNECT
SWITCH*
SIGHT
GLASS*
FILTER
DRIER*
INSULATED
VAPOR LINE
LIQUID
LINE
CONDENSING
UNIT A
CONDENSING
UNIT B
LIQUID
LINE
LEGEND
* Field supplied.
NEC —
National Electrical Code (U.S.A.)
TXV
—
Thermostatic Expansion Valve
Piping
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design
Manual for details.
2. All wiring must comply with applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended for,
or to include, all details for a specific installation.
4. Filter driers must be bi-flow type suited for heat pump duty.
5. Condensing unit A should be the first on last off and be connected to the lower half of the coil.
6. Internal factory-supplied TXVs and check valves not shown.
Fig. 5B — Typical Piping and Wiring (38AQS With 40RMQ024,028)