background image

FOR SERVICING ONLY — To speed up the 5-minute anti-
short cycle, a temporary jumper may be placed between ter-
minals T1 and T6 of the control module.

This jumper must be removed after servicing is com-
plete. Failure to remove this jumper is considered abu-
sive treatment and will void the Carrier warranty.

Bypass Relay (BPR) —

All units are equipped with a

BPR located in the control section of the control box. See
Fig. 9A or 9B. The function of the BPR is to provide a 2-minute
bypass of the LPS at start-up, and to energize the unload-
er(s) at start-up to provide unloaded compressor starting. Two
minutes after the compressor starts, the BPR completes its
function and is no longer active in the control circuit until
the next restart of the unit.

Time-Delay Relay (TDR) (50 Hz Only) —

This solid-

state delay-on-make relay is factory set for a 1-second delay.
The number 1 dip switch is set to the ON position, and all
the other dip switches are set to the OFF position. Once the
control relay (CR) is energized, the compressor contactor C1
is powered, and the first set of compressor windings is en-
ergized. After the 1-second time delay, contactor C1A is pow-
ered and the second set of compressor windings is energized
(part-wind start).

Sequence of Operation —

When space thermostat

calls for cooling, the no. 1 condenser fan and compressor
start after CM initial time delay of 3 (

1

2/–1) seconds. If an

optional airflow switch is used, compressor and no. 1 con-
denser fan will not start until sufficient indoor airflow has
closed the switch. After 3 seconds the compressor starts and
the liquid line solenoid valve for solenoid drop control opens.
The crankcase heater is deenergized. If the head pressure reaches
260 psig (1792 kPa) the second condenser fan starts. Fan
no. 3 (38AKS044 only) starts if outdoor ambient air rises
above 80 F (26.7 C).

If cooling demand is low, suction pressure at the com-

pressor drops. As the pressure drops, the compressor un-
loads 2 banks of cylinders as required. If cooling demand is
high and 2-stage operation is used, the second stage of the
thermostat activates the capacity control liquid line solenoid
which activates the second stage evaporator coil. The com-
pressor cylinders load or unload in response to compressor
suction pressure to meet evaporator load.

Two minutes after compressor starts, the BPR timer is deen-

ergized and the LPS bypass is deactivated. If the LPS trips
during the first 2 minutes of operation, the compressor will
remain operational. If the LPS trips after 2 minutes, the com-
pressor operation is interrupted, and the compressor cannot
restart until the 5-minute CM anti-short cycle timer expires.

As the space cooling load is satisfied, the second stage of

the thermostat opens, and closes the field-supplied capacity
control liquid line solenoid valve to deactivate the second
stage coil. The compressor adjusts the number of active cyl-
inders to meet the new load. When the space temperature is
satisfied, the first stage of the thermostat opens and the con-
trol relay and the BPR open. This closes the solenoid drop
control valve. The compressor stops and the crankcase heater
is energized, preventing refrigerant from migrating to the com-
pressor during the off cycle (solenoid drop refrigerant con-
trol). The CM anti-short cycling timer is energized and runs
for approximately 5 minutes. During this time, the compres-
sor is not able to restart.

Complete Unit Stoppage

CAUSES — Interruption of supplied power, compressor over-
temperature protection, or open HPS causes compressor
stoppage.
RESTART — The unit recycles and restarts automatically
under the CM when power is restored. Stoppage by HPS, or
compressor circuit breaker requires manual resetting of the
control circuit. To restart the CM timer when HPS is tripped,
it is necessary to interrupt power to the unit, restarting the
CM logic. It is necessary to manually reset the compressor
circuit breaker at the unit.

If LPS is not closed within 2 minutes after compressor

starts, the compressor locks out and the outdoor fans con-
tinue to run. It stays locked out for 5 minutes until the CM
anti-short cycle timer expires. After 5 minutes, the LPS is
bypassed by the BPR (winter start control). It remains jum-
pered for 2 minutes. Because the LPS is jumpered, the com-
pressor restarts and runs for the 2-minute time period. At
the end of this 2 minutes, if the LPS has still not closed, the
compressor is again locked out. The outdoor fans continue
to run as long as there is a call for cooling. Automatic reset
of the LPS causes the CM to recycle so that the compressor
can start.

If sufficient compressor oil pressure has not been built within

2 minutes after the compressor starts, the unit is completely
deenergized until the oil pressure switch is manually reset at
the unit.

If unit or circuit stoppage occurs more than once due to
any safety device, the trouble should be corrected be-
fore any attempt to restart.

SERVICE

Turn off all power to unit before proceeding.

Access for Servicing (See Fig. 13)

COMPRESSOR SECTION — The compressor compart-
ment has 2 side access panels and one front door for ser-
vicing, providing access to compressor, all components of
the refrigerant system, electrical controls, and control box.
After opening front door there is an inner cover that must be
removed for access to control box (except 208/230-v and
460-v units).

OIL PRESSURE SAFETY SWITCH — Switch is manually
reset, and accessed by removing the side access panel on the
left side of the unit (as viewed from the compressor end).
See Fig. 13. The OPS is found in the compressor junction
box. Open the compressor circuit breaker prior to removing
the compressor junction box cover in order to access the OPS.
The liquid line service valve can be found behind the side
access door on the right side of the unit (as viewed from the
compressor end).

CONDENSER SECTION — Condenser fan motors and fans
can be serviced by removal of outlet grilles or side panels.
If a fan motor is serviced, be sure the wire fan guard is in
place over each fan before starting unit. See Fig. 14 for proper
fan adjustment. Tighten fan hub securely on motor shaft with
setscrew which bears against the key. Be sure to replace Per-
magum and rubber cap over end of motor shaft to protect
against moisture causing fan to rust on shaft.

17

Summary of Contents for 38AKS028

Page 1: ...ntenance func tions such as cleaning coils All other operations should be performed by trained service personnel When working on the equipment observe precautions in the literature and on tags stickers and labels attached to the equipment Follow all safety codes Wear safety glasses and work gloves Keep quenching cloth and fire extinguisher nearby when brazing Use care in handling rigging and setti...

Page 2: ...ice Oil Charge for Carrier approved oil NOTE Circuit breaker is in main power circuit Table 1B Physical Data SI UNIT 38AKS 028 034 044 COMPRESSOR Reciprocating Semi Hermetic No Type 1 06E9265 1 06E9275 1 06E9299 No Cyls ea Speed R s 60 50 Hz 6 29 2 24 3 Capacity Steps 3 Oil Charge L 9 4 9 4 9 0 Oil Pressure Switch kPa Set Points Cutout 41 4 6 13 8 Differential Cut in 96 5 Max Crankcase Heater watt...

Page 3: ... side condenser and liquid line of the system during the off cycle Refrigerant migration is minimized Factory supplied liquid line solenoid valve connecting sizes are 7 8 in 22 2 mm ODF for inlet and 7 8 in 22 2 mm ODM for outlet Failure to properly install liquid line solenoid at the in door unit as described without Carrier authorization may VOID warranty Filter Drier and Moisture Indicator Ever...

Page 4: ... Manual at design tons and equiva lent length for 2 F 1 1 C loss If reading falls be tween 2 sizes on chart choose the smaller pipe size Suction piping for the high velocity section should be selected for about 0 5 F 0 3 C friction loss If a 2 F 1 1 C loss is allowed for the entire suction line 1 5 F 0 8 C is left for the balance of the suction line and it should be sized on that basis Check that ...

Page 5: ...T 38AKS LENGTH OF INTERCONNECTING PIPING FT M 16 25 4 9 7 6 26 50 7 9 15 2 51 75 15 5 22 8 76 100 23 2 30 5 101 200 30 8 60 9 L S L S L S L S L S 028 7 8 15 8 7 8 21 8 7 8 21 8 7 8 21 8 7 8 21 8 034 7 8 21 8 7 8 21 8 7 8 21 8 11 8 25 8 11 8 25 8 044 7 8 21 8 7 8 21 8 11 8 25 8 11 8 25 8 11 8 25 8 L Liquid Line S Suction Line IMPORTANT Requires a double suction riser if evaporator is below condensi...

Page 6: ... from above If necessary correct direc tion of fan rotation by interchanging any 2 power input wires at disconnect switch Affix crankcase heater decal located in installer s packet to unit disconnect switch Table 3 Electrical Data 60 HZ UNIT 38AKS UNIT COMPRESSOR FAN MOTORS Volts 3 Ph 60 Hz Supplied MCA MOCP Fuse ICF RLA LRA FLA ea Qty Min Max 028 500 200 600 100 208 230 380 460 575 187 342 414 51...

Page 7: ...ge 1 cooling and terminal on TB3 See Fig 8 for typical field wiring This is in the 24 v cir cuit Wires must be run in conduit with ground wire 4 Transformer Connections See unit wiring label dia gram notes 1 and 2 located behind compressor compart ment end access door IMPORTANT Ensure power to the crankcase heater is always on except when servicing the unit If cir cuit breaker inside unit shuts do...

Page 8: ...NOTES 1 There must be minimum 2440 mm 8 ft clear air space above unit 2 The approximate operating weight of the unit is 50 AND 60 HZ UNIT WT Lb WT Kg 38AKS028 1650 748 38AKS028C 1804 818 38AKS034 1803 818 38AKS034C 2009 911 3 A C in the model number indicates unit has factory installed copper coil 8 ...

Page 9: ...0 mm 8 ft clear air space above unit 2 The approximate operating weight of the unit is 50 HZ AND 60 HZ UNIT WT Lb WT Kg 38AKS044 2437 1106 38AKS044C 2745 1246 Fig 7 Dimensional Drawing 38AKS044 3 A C in the model number indicates unit has factory installed copper coil 9 ...

Page 10: ...compliance with all applicable codes 2 All field interlock contacts must have minimum rat ing of 180 va pilot duty plus capacity required for field installed equipment All field interlock con tacts in the 24 v control circuit must have minimum rating of 70 va pilot duty plus capacity required for field installed equipment 3 For internal unit wiring reference wiring book or unit wiring label diagra...

Page 11: ...reaker CR Control Relay CM Control Module EQUIP Equipment FC Fan Contactor Fig 9A Component Arrangement 60 Hz FM Fan Motor FU Fuse GND Ground LLSV Liquid Line Solenoid Valve NEC National Electrical Code U S A TB Terminal Block TRAN Transformer LEGEND 11 ...

Page 12: ...ker CR Control Relay CM Control Module EQUIP Equipment FC Fan Contactor FM Fan Motor FU Fuse GND Ground LLSV Liquid Line Solenoid Valve NEC National Electrical Code U S A TB Terminal Block TDR Time Delay Relay TRAN Transformer Fig 9B Component Arrangement 50 Hz 12 ...

Page 13: ... short cycle feature of the control module CM Charge System Actual start up should be done only under supervision of a qualified refrigeration mechanic Re fer to charging charts See Fig 10 12 for the particular unit being charged Mea sure pressure at the liquid line service valve being sure a Schrader depressor is used if required Also measure liquid line temperature as close to the liquid service...

Page 14: ...Fig 10 38AKS028 Charging Chart 50 60 Hz 14 ...

Page 15: ...Fig 11 38AKS034 Charging Chart 50 60 Hz 15 ...

Page 16: ...Fig 12 38AKS044 Charging Chart 50 60 Hz 16 ...

Page 17: ...s the solenoid drop control valve The compressor stops and the crankcase heater is energized preventing refrigerant from migrating to the com pressor during the off cycle solenoid drop refrigerant con trol The CM anti short cycling timer is energized and runs for approximately 5 minutes During this time the compres sor is not able to restart Complete Unit Stoppage CAUSES Interruption of supplied p...

Page 18: ...FC CM CR1 TRAN1 TB2 C1 COMPRESSOR END CONTROL PANEL REMOVED OIL PRESSURE SAFETY SWITCH COMPRESSOR END LEFT SIDE ACCESS DOOR JUNCTION BOX COVER REMOVED LIQUID LINE SERVICE VALVE COMPRESSOR END RIGHT SIDE ACCESS DOOR Fig 13 38AKS Unit with Access Panels Removed 18 ...

Page 19: ...aders are factory set see Table 1A or 1B but may be field adjusted Number 1 unloader is on cylinder bank on same side of compressor as terminal box CONTROL SET POINT The control set point cylinder load point is adjustable from 0 to 85 psig 0 to 586 kPag To adjust turn control set point adjustment nut Fig 15 clock wise to its bottom stop In this position set point is 85 psig 586 kPag Then turn adju...

Page 20: ...out Cut in 426 7 2937 48 320 20 2206 138 27 3 186 21 44 5 303 34 Winter Start Control Bypass relay timer bypasses low pressure switch for 2 minutes on unit start up Head Pressure Control Control maintains ad equate discharge pressure under low ambient temperature con ditions See Table 5 FAN CYCLING These 38AKS units have standard pro vision for fully automatic intermediate season head pressure con...

Page 21: ... is overcharged 4 Reclaim charge as needed UNIT OPERATES TOO LONG OR CONTINUOUSLY 1 Low refrigerant charge 1 Add refrigerant 2 Control contacts fused 2 Replace control 3 Air in system 3 Purge and evacuate system 4 Partially plugged expansion valve or filter drier 4 Clean or replace SYSTEM IS NOISY 1 Piping vibration 1 Support piping as required 2 Compressor noisy 2 Check valve plates for valve noi...

Page 22: ...e All programs include a video cassette and or slides and a companion booklet Use these for self teaching or to conduct full training sessions For a free Service Training Material Catalog STM call 1 800 962 9212 Ordering instructions are included Copyright 1994 Carrier Corporation Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and with...

Page 23: ... Y N INDOOR UNIT HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE Y N ARE PROPER AIR FILTERS IN PLACE Y N HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT Y N DO THE FAN BELTS HAVE PROPER TENSION Y N PIPING ARE LIQUID LINE SOLENOID VALVE S LOCATED AT THE EVAPORATOR COIL AS REQUIRED Y N HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR CONDENSER EVAPORATOR TXVs Thermostatic Expansio...

Page 24: ... EVAP ENTERING AIR WB TEMP EVAP LEAVING AIR DB TEMP EVAP LEAVING AIR WB TEMP COMPRESSOR AMPS L1 COMPRESSOR AMPS L2 COMPRESSOR AMPS L3 CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES ARE THE SIGHT GLASSES SHOWING OIL LEVEL AT 1 8 TO 1 3 FULL Y N NOTES Copyright 1994 Carrier Corporation Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and wit...

Reviews: