background image

Check Operation —

Verify operation of all safety con-

trols. Replace all service panels. Be sure that control panel
cover is closed tightly.

OPERATING SEQUENCE

Cooling —

When the first stage (TC1) of the cooling ther-

mostat closes, the timer starts. After approximately 3 sec-
onds, the timer activates the compressor and fan motor no.
1 contactor. When the liquid pressure builds to approxi-
mately 257 psig (1772 kPa), fan motor no. 2 is energized.

On demand for additional cooling capacity, the second stage

(TC2) of the cooling thermostat closes, energizing a field-
supplied liquid line solenoid (LLS) valve, which opens. This
increases the suction pressure, causing the compressor to op-
erate at higher capacity.

When fan switch is set at AUTO, the indoor-air fan cycles

with the compressor. When the switch is set at CONT, the
indoor-air fan runs continuously.

At shutdown, the Time Guard

t

II timer prevents the com-

pressor from restarting for approximately 5 minutes.

When installed, a field-supplied solenoid valve (wired in

parallel with the compressor contactor coil), shuts off the liq-
uid line to prevent refrigerant migration back to the com-
pressor during the off cycle.

Heating —

The heating thermostat (TH) energizes a field-

supplied relay which operates heating controls and ener-
gizes the indoor-fan relay. When the fan switch is set at AUTO,
the indoor-air fan cycles with the heating control. The indoor-
air fan runs continuously when the fan switch is set at CONT.

Fan Cycling —

Head pressure control is accomplished

by cycling the fans. The no. 2 fan responds to liquid line
pressure, cycling on at approximately 257 psig (1772 kPa)
and off at approximately 126 psig (869 kPa).

Winter Start Control (If Installed) —

When the com-

pressor starts, the control’s bypass timer contacts close for
150 seconds, thereby bypassing the low-pressure switch dur-
ing start-up. After 150 seconds, the bypass timer contacts
open and the low-pressure switch is restored to the safety
circuit.

SERVICE

Capacity Control —

A suction pressure-actuated un-

loader controls 2 cylinders and provides capacity control. Un-
loaders are factory set (see Tables 1A-1D), but can be field
adjusted as described in the 2 following sections.

CONTROL SET POINT (cylinder load point) is adjustable
from 0 to 85 psig (586 kPa). To adjust, turn control set point
adjustment nut (Fig. 12) clockwise to its bottom stop. In this
position, set point is 85 psig (586 kPa). Next, turn adjust-
ment counterclockwise to desired control set point. Every
full

turn

counterclockwise

decreases

set

point

by

7.5 psig (51.7 kPa).

PRESSURE DIFFERENTIAL (difference between cylinder
load and unload points) is adjustable from 6 to 22 psig (41.4
to 152 kPa). To adjust, turn pressure differential adjustment
screw (Fig. 12) counterclockwise to its back stop position.
In this position, differential is 6 psig (41.4 kPa). Next, turn
adjustment clockwise to desired pressure differential setting.
Every full turn clockwise increases differential by 1.5 psig
(10.3 kPa).

Head Pressure Control —

Fan cycling is a standard

feature. The no. 2 fan cycles in response to changes in liquid
pressure. The switch cycles the fan off at 126 ± 4 psig (869
± 28 kPa) as pressure decreases, and cycles it back on at 257
(+5, −0) psig (1772 [+103, −0] kPa).

Time Guard II Circuit —

Prevents short-cycling by pro-

viding a delay of approximately 5 minutes before restarting
compressor after shutdown from safety device action.

On start-up, the Time Guard II timer causes a delay of

approximately 3 seconds after thermostat closes.

On compressor shutdown, the timer recycles for approxi-

mately 5 minutes. During this time, the compressor cannot
restart.

Refer to Fig. 13 and to label diagram on unit.

Winter-Start Control (If Required) —

Install Ac-

cessory Package 38AE900021.

Crankcase Heater —

The heater prevents refrigerant

migration and compressor oil dilution during shutdown when-
ever compressor is not operating. It is wired into the control
circuit, and cycles with the compressor; the heater is off when
compressor is running, and on when compressor is off.

Both compressor service valves must be closed whenever

the crankcase heater is deenergized for more than 6 hours.
The crankcase heater is operable as long as the control cir-
cuit is energized.

Fig. 12 — Compressor Capacity Control Unloader

Fig. 13 — Timer Sequence Chart

13

Summary of Contents for 38AE012

Page 1: ...ety glasses and work gloves Keep quenching cloth and fire extinguisher nearby when brazing Use care in handling rigging and setting bulky equipment ELECTRIC SHOCK HAZARD Separate power sources main an...

Page 2: ...8AE012 13 8 in 35 38AE014 016 15 8 in 41 38AKS024 C 7 8 in 22 2 diameter knockout for control power D 2 in 50 8 diameter knockout for unit power NOTES 1 SERVICE AREAS Allow 3 ft 914 on both sides and...

Page 3: ...Compressor 2 No 1 Fan 6 Terminal Block 1 Unit Power 10 Low Pressure Switch 3 High Pressure Switch 7 Terminal Block 2 Control Power 11 Hot Gas Bypass Piping Stub 3 8 in ODM 4 Circuit Breakers 8 Wraparo...

Page 4: ...temperatures of 125 F for 38AE012 123 F for 38AE014 and 130 F for 38AE016 and 38AKS024 Table 1B Physical Data SI 60 Hz UNIT 38AE012 38AE014 38AE016 38AKS024 OPERATING WEIGHT kg 333 354 359 408 REFRIG...

Page 5: ...emperatures of 125 F for 38AE012 123 F for 38AE014 and 130 F for 38AE016 and 38AKS024 Table 1D Physical Data SI 50 Hz UNIT 38AE012 38AE014 38AE016 38AKS024 OPERATING WEIGHT kg 333 354 359 408 REFRIGER...

Page 6: ...and also refer to Part 3 of Carrier System Design Manual for design details and line sizing Refer to indoor installation instructions for addi tional information Table 3 Liquid Line Data UNIT MAXIMUM...

Page 7: ...ugh piping while brazing to prevent formation of copper oxide Install field supplied thermostatic expansion valve s in in door section If 2 thermostatic expansion valves are installed for 2 step cooli...

Page 8: ...80 50 20 0 74 38AE014 803 230 198 264 51 0 149 75 35 7 143 2 2 9 3 5 1 20 903 400 342 457 34 0 89 50 22 1 83 38AE016 803 230 198 264 66 9 206 100 47 9 200 2 2 9 3 5 1 20 903 400 342 457 43 0 121 60 2...

Page 9: ...ctrical power source must agree with unit nameplate rating 5 All service valves must be open 6 Crankcase heater must be firmly locked into the com pressor crankcase START UP To Start Unit Set thermost...

Page 10: ...Fig 9 38AE012 and 38AKS024 Charging Chart 10...

Page 11: ...Fig 10 38AE014 Charging Chart 11...

Page 12: ...Fig 11 38AE016 Charging Chart 12...

Page 13: ...ers and provides capacity control Un loaders are factory set see Tables 1A 1D but can be field adjusted as described in the 2 following sections CONTROL SET POINT cylinder load point is adjustable fro...

Page 14: ...r as required by location or outdoor air conditions Inspect coil monthly and clean as required Fins are not continuous through coil sections dirt and debris may pass through first section become trapp...

Page 15: ...rvice literature Contactor Closed 1 Compressor leads loose 1 Check connections 2 Motor windings open 2 See compressor service literature 3 Single phasing 3 Check for blown fuse Check for loose connect...

Page 16: ...control 3 Air in system 3 Purge and evacuate system 4 Partially plugged expansion valve or filter drier 4 Clean or replace SYSTEM IS NOISY 1 Piping vibration 1 Support piping as required 2 Compressor...

Page 17: ......

Page 18: ...l programs include a video cassette and or slides and a companion booklet Use these for self teaching or to conduct full training sessions For a free Service Training Material Catalog STM call 1 800 9...

Page 19: ...ONFIRM PROPER DRAINAGE Y N ARE PROPER AIR FILTERS IN PLACE Y N HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT Y N DO THE FAN BELTS HAVE PROPER TENSION Y N HAS CORRECT FAN ROTATION BEEN C...

Page 20: ...R DB dry bulb TEMP EVAP ENTERING AIR WB wet bulb TEMP EVAP LEAVING AIR DB TEMP EVAP LEAVING AIR WB TEMP COMPRESSOR AMPS L1 L2 L3 CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES ARE THE SIGHT GLASSES SHOW...

Reviews: