![Carrier 33CSSN3-FC Owner'S Manual Download Page 25](http://html.mh-extra.com/html/carrier/33cssn3-fc/33cssn3-fc_owners-manual_2563997025.webp)
About Advanced Features & Operation
24
SINGLE SETPOINT BEHAVIOR -
When configured for Single Setpoint operation
(step
#2, page 10)
, the degree icon will blink when the large number is displaying room
temperature and will remain solid when displaying the heating or cooling setpoint.
In the Auto mode the deadband is enforced both above and below the setpoint. To
avoid short cycling, a deadband of at least two degrees is recommended
(step #6,
page 12)
. To display the room temperature press and hold the MODE button for two
seconds. Release the MODE button to return to the normal display.
Auxiliary Input Control and Multiple HVAC Control
Potential Phasing Problems
When using the auxiliary input (CK1 & R) or controlling multiple HVAC units with a
single thermostat, it is possible to encounter transformer phasing problems that will
interfere with thermostat operation. Connecting transformers that are not phased
correctly may result in a direct short, which could damage transformers and/or the
thermostat. Phasing problems are likely if the units share a common ground with
secondary grounded transformers.
SOLUTION:
If possible, phase all HVAC units together. If phasing is impractical,
isolation relays may be used to isolate the transformers. To isolate the auxiliary
input, use a separate transformer for the auxiliary control device, usually a time clock.
Connect the device to an isolation relay coil. Connect one set of isolated contacts to
each thermostat at
CK1
and
R
. See diagram A.
Diagram A- Auxiliary Control
110vac
Isolation Relay
Coil
CK 1
R
Thermostat
CK 1
R
Thermostat
CK 1
R
Thermostat
Additional relays may be used. Relay coils must be wired in parallel.
CAUTION
WARNING
Summary of Contents for 33CSSN3-FC
Page 1: ...Owner s Manual ...