31MF

Mechanical Air Cleaner

Installation and Operating Instructions

NOTE:

Read the entire instruction before starting the installation.

SAFETY CONSIDERATIONS

Installation and service of heating and air conditioning equipment
can be hazardous due to system pressure and gas and electrical
components. Only trained and qualified personnel should install,
repair or service heating and air conditioning equipment.

Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. All other operations must
be performed by trained service personnel. When working on
heating and air conditioning equipment, observe precautions in the
literature, tags, and labels attached to or shipped with the unit and
other safety precautions that may apply.

Follow all safety codes. Wear safety glasses and work gloves.
Read these instructions thoroughly and follow all warnings or
cautions attached to the unit. Consult local building codes for
special installation requirements.

Recognize safety information. This is the safety-alert symbol

.

When you see this symbol on the unit or in instructions and
manuals, be alert to the potential for personal injury.

Understand the signal word—DANGER, WARNING, or CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies hazards that could
result in personal injury or death. CAUTION is used to identify
unsafe practices, which would result in minor personal injury or
product and property damage.

INTRODUCTION

The Model 31MF High-Efficiency Mechanical Air Cleaner is
designed for installation in the return-air duct of any forced-air
heating and/or cooling system. It is designed for use in systems
with airflow up to 2000 cfm. For higher airflows, additional units
may be required.

The Model 31MF is a mechanical air cleaner incorporating 78 sq
ft of glass microfiber filter media to clean the air circulated
through it with a low pressure drop. (See Table 1.)

Table 1—Air Cleaner Resistance

RESISTANCE

(IN. WC)

AIRFLOW

(CFM)

.03

600

.05

800

.07

1000

.10

1200

.13

1400

.16

1600

.20

1800

.24

2000

INSTALLATION

Step 1—Install Air Cleaner Cabinet in Return-air System

Turn OFF the electrical supply to the furnace before begin-
ning installation.

1. Remove and discard existing furnace filter(s).

2. Referring to Fig. 2 and 3 for air cleaner dimensions and typical

installations, determine best installation location of air cleaner.

NOTE:

A 26-in. clearance must be allowed for removal of the

media frame assembly from the air cleaner cabinet.

3. Using standard practices, remove a section of return-air duct

to allow installation of air cleaner cabinet.

4. Install air cleaner in duct opening, providing an airtight seal to

duct with necessary materials.

NOTE:

For systems with a right side return-air duct, rotate the air

cleaner 180° for proper installation. Remove and reinstall the front
access panel in an upright position. (See Fig. 3 for typical
installations.)

Fig. 1—Model 31MF Mechanical Air Cleaner

A90321

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

4

Tab

7a 9a

PC 101

Catalog No. 533-132

Printed in U.S.A.

Form 31MF-2SI

Pg 1

12-91

Replaces: 31MF-1SI

Summary of Contents for 31MF

Page 1: ...nd property damage INTRODUCTION The Model 31MF High Efficiency Mechanical Air Cleaner is designed for installation in the return air duct of any forced air heating and or cooling system It is designed for use in systems with airflow up to 2000 cfm For higher airflows additional units may be required The Model 31MF is a mechanical air cleaner incorporating 78 sq ft of glass microfiber filter media ...

Page 2: ...t airflow gage by rotating range adjustment plug until ball hovers at tip of lower arrow See Fig 4 When the air cleaner media begins to become clogged and dirty the ball will move up the gage When the ball is in the red range shown on the condition indicator card the air cleaner should be serviced Step 3 Install Filter Media in Air Cleaner Cabinet NOTE These instructions should also be followed wh...

Page 3: ...c pleat spacers being careful to insert one support finger between each pleat Press the pleat spacers down firmly to fully engage guide pin at each end See Fig 6 6 Slide assembled media frame into air cleaner cabinet Be sure airflow arrow on media frame is in same direction as arrow in cabinet Plastic pleat spacers are always on downstream side of filter media Attach outer cover and tighten thumb ...

Page 4: ...9011 Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 7a 9a PC 101 Catalog No 533 132 Printed in U S A Form 31MF 2SI Pg 4 12 91 Replaces 31MF 1SI ...

Reviews: