Carrier 30HWA Series Installation Instructions Download Page 2

Step 2 — Check Unit Disconnect Switch Amps

If unit is equipped with factory-installed 100- or 200-

amp non-fused disconnect switch, you must remove the dis-
connect switch 
before installing the accessory sound
enclosure.

To remove the switch, first disconnect the electrical con-

duit and wiring to the disconnect switch, then remove the 2
upper and 2 lower screws that support the switch. The dis-
connect is to be replaced after sound enclosure kit installa-
tion is completed; save removed screws. It is not necessary
to remove 30- and 60-amp non-fused disconnects (if equipped).

Step 3 — Modify 2 Insulated Basepan Assem-
blies For Upper Section —

Cut away part of 2 in-

sulated basepan assemblies (Item 1). See Fig. 3. These cut-
away areas permit the insulated basepan assembly to fit around
the control box conduit on one side, and around the suction
and discharge tubes on the other side. The remaining 2 in-
sulated basepan assemblies for the unit lower section do not
require any modification.

UNIT UPPER BASEPAN
WITH PRE-DRILLED
SCREW HOLES

CUT-AWAY
INSULATION
(SLOT 1)

PRE-DRILLED
SCREW HOLES

UPPER SUPPORT
ANGLE (ONE EA SIDE)

CUT-AWAY
INSULATION
(SLOTS 2 AND 3)

MODIFIED UPPER
SECTION INSULATED
BASEPANS (2)

SUCTION LINE

DISCHARGE LINE

LIQUID IN

LIQUID OUT

LIQUID IN

1

2

3

1

2

3

Fig. 1 — Installing Insulated Basepan Assemblies in Unit Upper Section

UNMODIFIED LOWER
SECTION INSULATED
BASEPANS (2)

LOWER SUPPORT
ANGLE (ONE EA SIDE)

PRE-DRILLED
SCREW HOLES

UNIT LOWER BASEPAN
WITH PRE-DRILLED
SCREW HOLES

Fig. 2 — Installing Insulated Basepan Assemblies in Unit Lower Section

Fig. 3 — Modifying Insulated Basepan Assemblies

for Upper Section

2

Summary of Contents for 30HWA Series

Page 1: ...ge for miss ing parts or shipping damage If damage is found or any part is missing file a claim with the shipper immediately See Table 1 Table 1 Accessory Package Contents ITEM DESCRIPTION PART NO QTY 1 Insulated Basepan Assembly perforated 30HW400027 4 2 Support Angle 30HW500020 4 3 Insulated Side Panel Assembly 357 8 x 263 4 in 911 x 679 mm 30HW400023 2 4 Insulated Front Rear Panel Assembly 30 x...

Page 2: ... cut away areas permit the insulated basepan assembly to fit around the control box conduit on one side and around the suction and discharge tubes on the other side The remaining 2 in sulated basepan assemblies for the unit lower section do not require any modification UNIT UPPER BASEPAN WITH PRE DRILLED SCREW HOLES CUT AWAY INSULATION SLOT 1 PRE DRILLED SCREW HOLES UPPER SUPPORT ANGLE ONE EA SIDE...

Page 3: ...anels to Unit Bottom Section IMPORTANT If you removed the factory installed 100 or 200 amp non fused disconnect switch described in Step 2 it must be mounted on the insulated side panel Item 3 using the pre drilled mounting holes located near the bottom center of the panel When mounting the panel be sure it is turned so that the mounting holes are toward the bottom of the panel Remount the disconn...

Page 4: ...NEL MOUNTED INSULATED SIDE PANEL 30 IN 762 mm 26 3 4 IN 679 mm Fig 6 Installing Insulated Front Rear Panels to Bottom Section Copyright 1993 Carrier Corporation Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 2 Tab 5c PC 903 Catalog No 563 003 Printed in U S A Form 30HW 2SI Pg 4 9 93 Replaces New ...