9 - APPLICATION DATA
9.1 - Unit operating range
Evaporator
Minimum
Maximum
Evaporator entering water temperature
°C
6.8*
21
Evaporator leaving water temperature
°C
4**
15
Condenser (water-cooled)
Minimum
Maximum
Condenser entering water temperature
°C
20***
42
Condenser leaving water temperature
°C
25
45
Outside ambient operating temperature 30HXC
°C
6
40
Condenser (air-cooled)
Minimum
Maximum
Outdoor ambient operating temperature
°C
0
46
Available static pressure
kPa
0
Notes:
* For application requiring operation at less than 6.8°C, contact Carrier s.a. for unit
selection using the Carrier electronic catalog.
** For application requiring operation at less than 4°C, the units require the use of
antifreeze.
*** Water-cooled units (30HXC) operating at full load and below 20°C condenser entering
water temperature require the use of a head pressure control with analogue water control
valves (see paragraph on head pressure control).
In temporary operating modes (start-up and at part load) the unit can operate with a
condenser entering air temperature of 13°C.
9.2 - Minimum chilled water flow
The minimum chilled water flow is shown in the table on the
next page. If the flow is less than this, the evaporator flow can
be recirculated, as shown in the diagram. The temperature of
the mixture leaving the evaporator must never be less than
2.8 K lower than the chilled water entering temperature.
EVAPORATOR
RECIRCULATION
Compressors
Reference
Size
I nom.
MHA
LRA
LRA (Y)
LRA (S) 1 cp.
LRA (S) 2 cp.
06NA2146S7N
39
70
95
605
191
220
-
06NA2174S7N
46
90
120
715
226
260
-
06NA2209S7N
56
113
145
856
270
330
420
06NA2250S7N
66
130
175
960
303
380
500
06NA2300S5N
80
156
210
1226
387
445
550
06NA2300S5E
80+
174
240
1265
400
460
600
Legend:
06NA
- Compressor for air-cooled units
N
- Non-economized compressor
E
- Economized compressor
INOM
- Average current draw of the compressor at Eurovent conditions
MHA
- Must hold amperes (maximum operating current) at 360 V
LRA
- Locked rotor current with across-the-line start
LRA (Y)
- Locked rotor current at reduced current (star/delta start-up mode)
LRA (S) 1 cp.
- Start-up with reduced current with electronic starter (start-up duration 3 seconds max.) for one compressor per circuit
LRA (S) 2 cp.
- Start-up with reduced current with electronic starter (start-up duration 3 seconds max.) for two compressors per circuit
FOR MINIMUM CHILLED WATER FLOW RATE
9.3 - Maximum chilled water flow
The maximum chilled water flow is limited by the maximum
permitted pressure drop in the evaporator. It is provided in the
table on the next page. If the flow exceeds the maximum value,
two solutions are possible:
a - Select a non-standard evaporator with one water pass less
which will allow a higher maximum water flow rate.
b - Bypass the evaporator as shown in the diagram to obtain a
highter temperature difference with a lower evaporator flow
rate.
EVAPORATOR
BYPASS
FOR MAXIMUM CHILLED WATER FLOW RATE