ACCESSORY USAGE GUIDELINE

ACCESSORY

REQUIRED FOR LOW---AMBIENT

COOLING APPLICATIONS

(Below 55

°

F/12.8

°

C)

REQUIRED FOR

LONG LINE

APPLICATIONS*

(Over 80 Ft.)

REQUIRED FOR

SEA COAST

APPLICATIONS

(Within 2 miles)

Accumulator

Standard

Standard

Standard

Ball Bearing Fan Motor

Yes

{

No

No

Compressor Start Assist Capacitor and Relay

Yes

{

Yes

No

Crankcase Heater

Yes

{

Yes

No

Evaporator Freeze Thermostat

Yes

{

No

No

Isolation Relay

Yes

{

No

No

Liquid Line Solenoid Valve

or Hard Shut---Off TXV

Yes

{

See Long---Line

Application Guideline

Yes

Motor Master

®

Control or

Low---ambient Pressure Switch

Yes

{

No

No

Support Feet

Recommended

No

Recommended

* For tubing line sets between 80 and 200 ft. and/or 20 ft. vertical differential, refer to Residential Split---System Longline Application Guideline.

{

Required for Low---Ambient Controller MotorMaster

r

Control only. Hard Shut---Off TXV is standard on new Carrier evaporator coils and fan coils.

Accessory Description and Usage (Listed Alphabetically)

1. Ball--Bearing Fan Motor

A fan motor with ball bearings which permits speed reduction

while maintaining bearing lubrication.

Usage Guideline:

Required on all units when using MotorMaster

r

2. Compressor Start Assist -- Capacitor and Relay

Start capacitor and relay gives a ”hard” boost to compressor

motor at each start up.

Usage Guideline:

Required for reciprocating compressors in the

following applications:

Long line
Low ambient cooling
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil

Required for single--phase scroll compressors in the

following applications:

Long line
Low ambient cooling

Suggested for all compressors in areas with a history of
low voltage problems.

3. Compressor Start Assist — PTC Type

Solid state electrical device which gives a ”soft” boost to the
compressor at each start--up.

Usage Guideline:

Suggested in installations with marginal power supply.

4. Crankcase Heater

An electric resistance heater which mounts to the base of the
compressor to keep the lubricant warm during off cycles.

Improves compressor lubrication on restart and minimizes the
chance of liquid slugging.

Usage Guideline:

Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.

5. Evaporator Freeze Thermostat

An SPST temperature--actuated switch that stops unit operation
when evaporator reaches freeze--up conditions.

Usage Guideline:

Required when low ambient kit has been added.

6. Isolation Relay

An SPDT relay which switches the low--ambient controller out of

the outdoor fan motor circuit when the heat pump switches to
heating mode.

Usage Guideline:

Required in all heat pumps where low ambient kit has
been added.

7. Liquid--Line Solenoid Valve (LLS)

An electrically operated shutoff valve which stops and starts

refrigerant liquid flow in response to compressor operation. It is

to be installed at the outdoor unit to control refrigerant off cycle
migration in the heating mode.

Usage Guideline:

An LLS is required in all long line heat pump

applications to control refrigerant off cycle migration in

the heating mode. See Long Line Guideline.

8. Low--Ambient Pressure Switch Kit

A long life pressure switch which is mounted to outdoor unit
service valve. It is designed to cycle the outdoor fan motor in

order to maintain head pressure within normal operating limits.
The control will maintain working head pressure at low--ambient

temperatures down to 0

_

F when properly installed.

Usage Guideline:

A Low--Ambient Pressure Switch or MotorMaster

r

Low--Ambient Controller must be used when cooling operation is
used at outdoor temperatures below 55

_

F (12.8

_

C).

9. MotorMaster

r

Low--Ambient Controller

A fan--speed control device activated by a temperature sensor,
designed to control condenser fan motor speed in response to the

saturated, condensing temperature during operation in cooling
mode only. For outdoor temperatures down to --20

_

F (--28.9

_

C),

it maintains condensing temperature at 100

_

F

±

10

_

F (37.8

_

C

±

6.5

_

C).

Usage Guideline:

A MotorMaster

r

Low Ambient Controller or

Low--Ambient Pressure Switch must be used when

cooling operation is used at outdoor temperatures
below 55

_

F (12.8

_

C).

Suggested for all commercial applications.

25H

B

A

3

Summary of Contents for 25HBA3 Series

Page 1: ... 7 8 3 HSPF nominal S Microtube Technologyt refrigeration system S Indoor air quality accessories available Sound S Sound level as low as 74 dBA Comfort S System supports Thermidistatt or standard thermostat controls Reliability S Puronr refrigerant environmentally sound won t deplete the ozone layer and low lifetime service cost S Scroll compressor S Internal pressure relief valve S Internal ther...

Page 2: ...ritical to achieve rated capacity and efficiency Installation of this product should follow all manufacturing refrigerant charging and air flow instructions Failure to confirm proper charge and air flow may reduce energy efficiency and shorten equipment life STANDARD FEATURES Feature 18 24 30 36 42 48 60 Puron Refrigerant X X X X X X X 13 SEER X X X X X X X Scroll Compressor X X X X X X X Dense Wi...

Page 3: ... The maximum vertical separation is 200 ft when outdoor unit is above indoor unit and 80 ft when the outdoor unit is below the indoor unit Refer to Accessory Usage Guideline below for required accessories See Longline Application Guideline for required piping and system modifications Also refer to the table below for the acceptable vapor tube diameters based on the total length to minimize the coo...

Page 4: ... applications Includes Outdoor Air Temperature Sensor TSTATCCPHH01 B Hybrid Heatt Dual Fuel Thermostat Auto Changeover 7 Day Programmable F C Includes Outdoor Sensor TSTATXXSEN01 B TSTATCCPHP01 B Thermostat Auto Changeover 7 Day Programmable F C 2 Stage Heat 1 Stage Cool TSTATCCNHP01 C Thermostat Auto Changeover Non Programmable F C 2 Stage Heat 1 Stage Cool TSTATCCSHP01 Standard Programmable Ther...

Page 5: ...ing off cycles Improves compressor lubrication on restart and minimizes the chance of liquid slugging Usage Guideline Required in low ambient cooling applications Required in long line applications Suggested in all commercial applications 5 Evaporator Freeze Thermostat An SPST temperature actuated switch that stops unit operation when evaporator reaches freeze up conditions Usage Guideline Require...

Page 6: ...oint Usage Guideline Outdoor thermostat applications where electric heater is capable of 3 stage operation 13 Sound Hood Wraparound sound reducing cover for the compressor Reduces the sound level by about 2 dBA Usage Guideline Suggested when unit is installed closer than 15 ft to quiet areas bedrooms etc Suggested when unit is installed between two houses less than 10 ft apart 14 Thermostatic Expa...

Page 7: ...Locked Rotor Amps MCA Minimum Circuit Amps RLA Rated Load Amps NOTE Control circuit is 24 V on all units and requires external power source Copper wire must be used from service disconnect to unit All motors compressors contain internal overload protection SOUND POWER UNIT SIZE VOLTAGE SERIES STANDARD RATING dBA TYPICAL OCTAVE BAND SPECTRUM dB without tone adjustment 125 250 500 1000 2000 4000 800...

Page 8: ...8 DIMENSIONS 25HBA3 ...

Page 9: ...LDING HEAT LOSS UNIT INTEGRATED HEATING CAPACITY MBTUH 0 0 2 9 5 9 8 8 11 7 14 6 17 6 20 5 23 4 kW 25HBA324A FX4CNF024 25HBA330A FX4CNF030 25HBA342A FX4CNF042 25HBA336A FX4CNF036 25HBA348A FC4DNF048 25HBA360A FX4CNB060 BASED ON INDOOR ENT AIR AT 70 ºF AND AT RATED CFM 25HBA318A FX4CNF018 25HBA348A FX4CNF048 25HBA3 ...

Page 10: ... 34 7 9 58CV A X 070 12 CNPV 2414A 17 300 TXV 13 20 10 80 18 000 3 54 10 800 2 26 7 8 CNPV 2417A 17 200 TDR TXV 14 50 12 00 17 500 3 58 10 100 2 34 7 9 58CV A X 090 16 CNPV 2417A 17 300 TDR TXV 14 50 11 70 17 400 3 56 10 100 2 34 7 9 58MVB060 14 CNPV 2417A 17 300 TXV 13 20 10 80 18 000 3 54 10 800 2 28 7 9 CSPH 2412A 17 300 TDR TXV 14 50 12 00 17 400 3 52 10 100 2 32 7 9 58CV A X 070 12 CSPH 2412A...

Page 11: ... 8 4 58CV A X 070 12 CNPV 3014A 23 000 TXV 13 00 10 60 23 400 3 56 15 200 2 52 8 3 CNPV 3017A 23 000 TDR TXV 14 00 11 70 23 000 3 70 14 300 2 62 8 5 58CV A X 090 16 CNPV 3017A 23 000 TDR TXV 14 00 11 70 23 000 3 68 14 300 2 62 8 5 58MVB060 14 CNPV 3017A 23 000 TXV 13 00 10 60 23 400 3 56 15 200 2 52 8 3 CSPH 2412A 22 600 TDR TXV 14 00 11 60 23 400 3 70 14 400 2 60 8 5 58CV A X 070 12 CSPH 2412A 22...

Page 12: ...20 600 2 62 8 3 58MVB080 20 CNPH 3017A 29 400 TDR TXV 14 00 10 90 30 800 3 48 20 600 2 62 8 3 58MVB100 20 CNPH 3017A 29 400 TDR TXV 14 00 11 00 30 800 3 46 20 400 2 62 8 2 58MVB120 20 CNPH 3017A 29 600 TXV 13 00 10 10 32 000 3 48 21 400 2 58 8 3 CNPH 3617A 29 400 TDR TXV 13 50 10 90 30 800 3 46 20 600 2 62 8 3 58CV A X 070 12 CNPH 3617A 29 400 TDR TXV 14 00 11 00 30 800 3 48 20 400 2 64 8 3 58CV A...

Page 13: ...21 600 2 54 8 5 FY4ANF036 33 000 TDR TXV 13 00 10 50 35 200 3 36 21 600 2 34 7 7 CAP 3614A 32 400 TDR TXV 13 50 11 00 34 600 3 44 21 000 2 42 7 9 58CV A X 070 12 CAP 3614A 32 400 TXV 13 00 10 50 35 200 3 40 21 800 2 38 7 8 CAP 3617A 33 400 TDR TXV 14 00 11 50 34 400 3 48 21 000 2 46 8 0 58CV A X 090 16 CAP 3617A 33 400 TDR TXV 13 50 11 20 34 400 3 46 21 000 2 44 7 9 58MVB060 14 CAP 3617A 33 400 TX...

Page 14: ... 11 50 34 600 3 62 21 000 2 50 8 2 58CV A X 090 16 CSPH 3612A 33 400 TDR TXV 14 00 11 50 34 600 3 64 21 200 2 52 8 3 58CV A X 110 20 CSPH 3612A 33 400 TDR TXV 14 00 11 50 34 600 3 64 21 000 2 52 8 3 58CV A X 135 22 CSPH 3612A 33 400 TDR TXV 14 00 11 70 34 600 3 66 21 000 2 54 8 3 58CV A X 155 22 CSPH 3612A 33 400 TDR TXV 13 50 11 20 34 600 3 56 21 200 2 48 8 1 58MVB040 14 CSPH 3612A 33 400 TDR TXV...

Page 15: ... 25 000 2 56 8 2 58CV A X 135 22 CNPH 4221A 40 500 TDR TXV 14 00 11 60 41 000 3 58 24 800 2 56 8 2 58CV A X 155 22 CNPH 4221A 40 000 TDR TXV 13 50 11 20 41 000 3 48 25 200 2 50 8 0 58MVB040 14 CNPH 4221A 40 000 TDR TXV 14 00 11 30 41 000 3 50 25 200 2 52 8 1 58MVB060 14 CNPH 4221A 40 000 TDR TXV 13 50 11 10 41 000 3 48 25 200 2 50 8 0 58MVB080 14 CNPH 4221A 40 000 TDR TXV 14 00 11 20 41 000 3 50 2...

Page 16: ...000 3 68 25 400 2 56 8 4 58MVB120 20 CSPH 4812A 41 000 TXV 13 00 10 70 42 000 3 68 26 400 2 52 8 4 48 31 FY4ANF048 46 500 TDR TXV 13 00 10 8 48 500 3 60 30 800 2 58 8 3 FV4BNB006 48 000 TDR TXV 14 00 12 50 46 000 3 86 29 400 2 78 8 8 FV4BNF005 47 000 TDR TXV 14 00 12 20 47 500 3 78 29 400 2 72 8 6 FX4BNB060 47 500 TDR TXV 13 00 11 20 45 000 3 52 30 800 2 62 8 4 FX4BNF048 46 500 TDR TXV 13 00 11 10...

Page 17: ...TXV 14 00 11 70 46 000 3 74 29 600 2 66 8 5 58CV A X 090 16 CSPH 6012A 47 000 TDR TXV 14 00 11 70 46 000 3 76 29 600 2 68 8 6 58CV A X 110 20 CSPH 6012A 47 000 TDR TXV 14 00 12 00 46 000 3 78 29 600 2 70 8 6 58CV A X 135 22 CSPH 6012A 47 000 TDR TXV 14 00 12 00 46 000 3 80 29 400 2 70 8 7 58CV A X 155 22 CSPH 6012A 46 500 TDR TXV 14 00 11 70 46 000 3 70 29 800 2 64 8 5 58MVB080 20 CSPH 6012A 46 50...

Page 18: ... 0 95 15 57 15 57 1 05 14 77 14 77 1 17 13 89 13 89 1 30 12 94 12 94 1 44 675 72 21 30 11 03 0 86 20 23 10 65 0 96 19 11 10 25 1 06 17 93 9 84 1 18 16 67 9 40 1 31 15 30 8 93 1 45 67 19 34 14 03 0 87 18 35 13 64 0 96 17 31 13 22 1 07 16 21 12 79 1 18 15 04 12 32 1 31 13 78 11 82 1 45 63 17 93 13 50 0 87 16 99 13 10 0 97 16 01 12 68 1 07 14 97 12 24 1 19 13 87 11 76 1 32 12 68 11 25 1 46 62 17 68 1...

Page 19: ...4CNF024 1 02 0 94 FX4CNF030 1 04 0 93 FY4ANF030 1 02 1 01 CAP 2414A 1 01 1 01 CAP 2417A 1 01 1 01 CAP 3014A 1 02 1 01 CAP 3017A 1 02 1 01 CNPF 2418A 1 01 1 01 CNPH 2417A 1 01 1 01 CNPH 3017A 1 02 1 01 CNPV 2414A 1 01 1 01 CNPV 2417A 1 01 1 01 CNPV 3014A 1 02 1 01 CNPV 3017A 1 02 1 01 CSPH 2412A 1 01 1 00 CSPH 3012A 1 02 1 01 CAP 2414A 1 00 0 91 58CV A X 070 12 CAP 3014A 1 02 0 91 58CV A X 070 12 C...

Page 20: ...1 01 CAP 3617A 1 01 1 01 CAP 3621A 1 01 1 01 CNPF 3618A 1 01 1 01 CNPH 3017A 1 01 1 01 CNPH 3617A 1 01 1 01 CNPV 3014A 1 01 1 01 CNPV 3017A 1 01 1 01 CNPV 3617A 1 01 1 01 CNPV 3621A 1 01 1 01 CSPH 3012A 1 01 1 00 CSPH 3612A 1 01 0 99 CAP 3014A 1 00 0 94 58CV A X 070 12 CAP 3614A 1 01 0 93 58CV A X 070 12 CNPH 3017A 1 01 0 93 58CV A X 070 12 CNPH 3617A 1 01 0 93 58CV A X 070 12 CNPV 3014A 1 00 0 94...

Page 21: ...221A 0 99 0 99 CNPV 3617A 0 98 0 99 CNPV 3621A 0 98 0 99 CNPV 4221A 0 99 0 99 CSPH 3612A 0 98 0 97 CSPH 4212A 0 99 0 98 CAP 3614A 0 95 0 92 58CV A X 070 12 CNPH 3617A 0 98 0 92 58CV A X 070 12 CNPH 4221A 0 99 0 91 58CV A X 070 12 CSPH 3612A 0 98 0 91 58CV A X 070 12 CSPH 4212A 0 99 0 92 58CV A X 070 12 CAP 3617A 0 98 0 91 58CV A X 090 16 CNPH 3617A 0 98 0 93 58CV A X 090 16 CNPH 4221A 0 99 0 90 58...

Page 22: ...212A 0 99 0 96 CSPH 4812A 1 01 0 98 CNPH 4221A 0 99 0 93 58CV A X 070 12 CNPH 4821A 1 00 0 94 58CV A X 070 12 CSPH 4212A 0 98 0 91 58CV A X 070 12 CSPH 4812A 1 01 0 95 58CV A X 070 12 CAP 4817A 0 99 0 90 58CV A X 090 16 CNPH 4221A 0 99 0 90 58CV A X 090 16 CNPH 4821A 1 01 0 92 58CV A X 090 16 CNPV 4221A 1 00 0 93 58CV A X 090 16 CSPH 4212A 0 99 0 90 58CV A X 090 16 CSPH 4812A 1 01 0 92 58CV A X 09...

Page 23: ...e Model FY4ANF048 1 00 1 00 FB4BNB070 1 02 0 99 FV4BNB006 1 03 0 89 FV4BNF005 1 01 0 89 FX4CN B F 048 1 02 0 94 FX4CN B F 060 1 03 0 93 FY4ANB060 1 02 1 00 CAP 4817A 0 97 0 97 CAP 4821A 0 99 0 99 CAP 4824A 0 99 0 99 CAP 6021A 0 99 0 99 CAP 6024A 1 01 1 01 CNPF 4818A 0 97 0 97 CNPH 4821A 0 97 0 97 CNPH 6024A 1 01 1 01 CNPV 4821A 0 99 0 99 CNPV 4824A 0 99 0 99 CNPV 6024A 1 01 1 01 CSPH 4812A 0 99 0 ...

Page 24: ...48 14 42 52 7 33 63 62 58 48 57 4 56 59 40 47 16 5 01 56 09 45 69 5 51 52 66 44 18 6 05 49 01 42 56 6 65 45 05 40 80 7 30 62 61 68 60 83 4 56 58 79 58 79 5 01 56 05 56 05 5 51 53 19 53 19 6 06 50 08 50 08 6 66 46 62 46 62 7 31 57 61 37 61 37 4 55 58 79 58 79 5 01 56 06 56 06 5 51 53 19 53 19 6 06 50 08 50 08 6 66 46 62 46 62 7 31 Cooling Indoor Model Capacity Power Furnace Model FY4ANB060 1 00 1 0...

Page 25: ... 1 50 18 16 18 16 1 55 20 56 20 56 1 60 22 95 22 95 1 66 75 525 5 73 5 27 1 32 7 79 7 16 1 39 9 90 9 03 1 45 12 14 10 78 1 51 14 56 13 25 1 58 17 32 17 32 1 67 20 17 20 17 1 76 22 69 22 69 1 84 600 5 89 5 42 1 34 7 97 7 32 1 40 10 10 9 21 1 46 12 36 10 97 1 51 14 84 13 50 1 57 17 64 17 64 1 65 20 35 20 35 1 71 22 82 22 82 1 79 675 6 04 5 56 1 36 8 13 7 47 1 42 10 28 9 37 1 47 12 55 11 15 1 51 15 0...

Page 26: ...14A 0 98 0 97 CAP 3017A 0 98 0 97 CNPF 2418A 1 02 0 98 CNPH 2417A 1 02 0 98 CNPH 3017A 0 98 0 97 CNPV 2414A 1 02 0 98 CNPV 2417A 1 02 0 98 CNPV 3014A 0 98 0 97 CNPV 3017A 0 98 0 97 CSPH 2412A 1 01 0 97 CSPH 3012A 0 97 0 96 CAP 2414A 0 98 0 96 58CV A X 070 12 CAP 3014A 0 96 0 93 58CV A X 070 12 CNPH 2417A 0 98 0 95 58CV A X 070 12 CNPH 3017A 0 96 0 93 58CV A X 070 12 CNPV 2414A 0 98 0 94 58CV A X 0...

Page 27: ...A 1 01 1 00 CNPV 3017A 1 01 1 00 CNPV 3617A 1 01 1 00 CNPV 3621A 1 01 1 00 CSPH 3012A 1 01 1 00 CSPH 3612A 1 01 0 96 CAP 3014A 0 97 0 98 58CV A X 070 12 CAP 3614A 0 97 0 97 58CV A X 070 12 CNPH 3017A 0 97 0 97 58CV A X 070 12 CNPH 3617A 0 97 0 97 58CV A X 070 12 CNPV 3014A 0 97 0 98 58CV A X 070 12 CSPH 3012A 0 97 0 97 58CV A X 070 12 CSPH 3612A 0 97 0 94 58CV A X 070 12 CAP 3017A 0 97 0 97 58CV A...

Page 28: ...97 CAP 3614A 0 97 1 00 58CV A X 070 12 CNPH 3617A 0 96 1 00 58CV A X 070 12 CNPH 4221A 0 97 0 97 58CV A X 070 12 CSPH 3612A 0 97 0 96 58CV A X 070 12 CSPH 4212A 0 97 0 95 58CV A X 070 12 CAP 3617A 0 96 0 98 58CV A X 090 16 CNPH 3617A 0 96 0 99 58CV A X 090 16 CNPH 4221A 0 96 0 96 58CV A X 090 16 CNPV 3617A 0 96 0 99 58CV A X 090 16 CSPH 3612A 0 97 0 95 58CV A X 090 16 CSPH 4212A 0 97 0 93 58CV A X...

Page 29: ...212A 0 99 0 97 58CV A X 070 12 CSPH 4812A 0 99 0 96 58CV A X 070 12 CAP 4817A 0 96 0 93 58CV A X 090 16 CNPH 4221A 0 98 0 98 58CV A X 090 16 CNPH 4821A 0 98 0 94 58CV A X 090 16 CNPV 4221A 1 00 1 03 58CV A X 090 16 CSPH 4212A 0 98 0 95 58CV A X 090 16 CSPH 4812A 0 98 0 93 58CV A X 090 16 CAP 4221A 0 98 0 99 58CV A X 110 20 CAP 4821A 0 98 0 94 58CV A X 110 20 CNPH 4221A 0 98 0 97 58CV A X 110 20 CN...

Page 30: ... 0 98 0 94 FX4CN B F 060 0 91 0 87 FY4ANB060 0 93 0 95 CAP 4817A 0 99 0 97 CAP 4821A 1 01 0 99 CAP 4824A 1 01 0 99 CAP 6021A 0 93 0 95 CAP 6024A 0 93 0 95 CNPF 4818A 1 00 1 03 CNPH 4821A 1 01 0 99 CNPH 6024A 0 93 0 91 CNPV 4821A 1 01 0 99 CNPV 4824A 1 01 0 99 CNPV 6024A 0 93 0 91 CSPH 4812A 1 01 0 98 CSPH 6012A 0 93 0 91 CAP 4817A 0 98 0 96 58CV A X 090 16 CNPH 4821A 0 99 0 98 58CV A X 090 16 CNPH...

Page 31: ...50 23 57 21 68 4 21 29 50 27 11 4 38 35 86 32 70 4 57 42 56 37 80 4 77 49 72 45 25 4 99 57 81 57 81 5 26 67 28 67 28 5 51 76 15 76 15 5 82 2000 24 12 22 19 4 29 30 09 27 65 4 44 36 50 33 28 4 60 43 24 38 40 4 78 50 48 45 93 4 98 58 94 58 94 5 21 67 93 67 93 5 43 76 69 76 69 5 70 2250 24 63 22 66 4 37 30 63 28 15 4 51 37 07 33 80 4 66 43 83 38 93 4 82 51 15 46 54 5 00 59 80 59 80 5 19 68 35 68 35 5...

Page 32: ...will be corrosion resistant Fan blades will be statically and dynamically balanced Condenser fan openings will be equipped with steel wire safety guards Compressor Compressor will be hermetically sealed Compressor will be mounted on rubber vibration isolators Condenser Coil Condenser coil will be air cooled Coil will be constructed of aluminum fins mechanically bonded to copper tubes which are the...