background image

24VNA6: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

5

Outdoor  units  may  be  connected  to  indoor  section  using  accessory

tubing package or field-supplied refrigerant grade tubing of correct size

and  condition.  For  tubing  requirements  beyond  80  ft.  (24.38  m),

substantial capacity and performance losses can occur. Follow the pipe

sizing recommendations in the 24VNA6 Product data to manage these

losses.
Refer  to 

Table 1

  for  field  tubing  diameters.  Refer  to 

Table 2

  for

accessory requirements. 

* Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance data when using different size and length line sets.

Notes

:

1.Do not apply capillary tube indoor coils to these units.

2.For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal and / or greater than 20 ft. (6.1 m) vertical differential, an accessory Liquid Line Solenoid must be installed.

CAUTION

!

UNIT DAMAGE HAZARD

Failure  to  follow  this  caution  may  result  in  equipment  damage  or

improper operation.
Do  not  leave  system  open  to  atmosphere  any  longer  than  minimum

required  for  installation.  PVE  oil  in  compressor  is  extremely

susceptible to moisture absorption. Always keep ends of tubing sealed

during installation.

CAUTION

!

UNIT DAMAGE HAZARD

Failure  to  follow  this  caution  may  result  in  equipment  damage  or

improper operation.
If ANY refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical

rise at service valve. Refrigerant tubing lengths up to 36 in. (914.4 mm)

may be buried without further special consideration. Do not bury lines

longer than 36 in. (914.4 mm).

Table 1 – Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (in.)

UNIT SIZE

LIQUID

VAPOR*

Connection

 Diameter

Tube

Diameter

Connection

Diameter

Max (Rated)

Diameter

Minimum Tube

Diameter

24VNA624

3/8

3/8

3/4

3/4

5/8

24VNA636

3/8

3/8

7/8

7/8

5/8

24VNA648

3/8

3/8

7/8

1-1/8

3/4

24VNA660

3/8

3/8

7/8

1-1/8

3/4

Table 2 – Accessory Usage

ACCESSORY

REQUIRED FOR

LOW-AMBIENT COOLING

APPLICATIONS

(Below 55°F/12.8_C)

REQUIRED FOR LONG LINE

APPLICATIONS

*

(Over 80 ft/24.38 m)

*. For tubing set lengths between 80 and 200 ft. (24.38 and 60.96 m) horizontal or 20 ft. (6.10 m) vertical differential (total equivalent length),  an accessory Liquid Line Solenoid must be 

installed.

REQUIRED FOR SEA 

COAST APPLICATIONS

(Within 2 miles/3.22 km)

Crankcase Heater

Standard

Standard

Standard

Evaporator Freeze Protection

Standard with Infinity Control

No

No

Liquid-Line Solenoid Valve

No

Yes

No

Low-Ambient Control

Standard with Infinity Control

No

No

Puron Refrigerant Balance Port 

Hard-ShutOff TXV

Yes

†. Required on all indoor units. Standard on all new Puron refrigerant fan coils and furnace coils.

Yes

Yes

Support Feet

Recommended

No

Recommended

Summary of Contents for 24VNA6 Series

Page 1: ...thin 24VNA6 11 Step13 System Functions and Major Components 12 Primary Control Module 12 Utility Interface With Infinity Control 12 Infinity Control Green Communications COMM Light 12 Amber Status Lig...

Page 2: ...ration with enough bends to provide 10 ft 3 05 m of total line set length outside the dwelling 3 Ensure that vapor and liquid tube diameters are appropriate for unit capacity 4 Run refrigerant tubes a...

Page 3: ...t and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit This unit employs one louver spacer on each of the four sides to prevent louver movement during operation...

Page 4: ...ant piping arrangements with equivalent lengths of greater than 80 ft 24 38 m and or when elevation difference between indoor and outdoor unit is greater than 20 ft 6 10 m follow the piping configurat...

Page 5: ...stallation CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation If ANY refrigerant tubing is buried provide a 6 in 152 4 mm vertical rise at s...

Page 6: ...lves see Table 1 Sweat Connections Use refrigerant grade tubing Service valves are closed from factory and ready for brazing After wrapping service valve with a wet cloth braze sweat connections using...

Page 7: ...nate transferred noise If further communication issues exist consider using shielded low voltage wires and only connect shielding to C terminal at end nearest indoor coil Final Wiring Check IMPORTANT...

Page 8: ...Do not attempt to operate the system in heating or cooling mode at this time Mode OFF Vapor and liquid line service valves should be fully closed 2 If the outdoor ambient temperature is between 65 F...

Page 9: ...e text line set and vapor line to choose line set length and vapor line diameter see Fig 17 and Fig 18 After complete press next to advance to next screen 12 If this is a new install i e the ODU is fa...

Page 10: ...ice and without obligations 10 A200035 Fig 17 Select Line Set Length Vapor Line Diameter A200036 Fig 18 Adjust Line Set Length Vapor Line Diameter that is Installed A200037 Fig 19 Charging Mode Select...

Page 11: ...or and outdoor unit prior to servicing unit A200040 Fig 22 Pump Down Setup Screen A200041 Fig 23 Pump Down Status Screen Evacuation and Recovery of Refrigerant from within 24VNA6 Because the 5 ton uni...

Page 12: ...he user interface UI displays the operation mode and fault codes as specified in the troubleshooting section See Table 7 for codes and definitions NOTE Only one code will be displayed on the outdoor u...

Page 13: ...any time specifications and designs without notice and without obligations 13 A200049 Fig 26 Variable Speed Control Board with optional Utility Relay A200044 Fig 27 Primary Control Board Status LED Ye...

Page 14: ...an air cooled device that communicates with the PCM and drives the compressor to the demanded RPM The VFD provides DC voltage to the fan motor and sends a fan RPM signal to the electronics on the fan...

Page 15: ...temporarily Pressure Switch Protection The outdoor unit is equipped with high pressure switch If this switch opens the VFD will lose line power and the compressor and fan motor will not operate The hi...

Page 16: ...ting Locations Failed Thermistor Default Operation Factory defaults have been provided in the event of failure of outdoor air thermistor OAT and or outdoor coil thermistor OCT If the OAT sensor should...

Page 17: ...lash and first long flash is 1 0 second Time between code repeating is 2 5 seconds with LED OFF Codes are easily read from user interface UI or the 5x7 LED display on the PCM EXAMPLE 3 short flashes f...

Page 18: ...ommon C COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com SRTN Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor Y1 J1 Jumper on Control Board Jumper Wire Required for...

Page 19: ...High Temperature Limit 35 11 58 Compressor High Compression Limit 36 15 55 Compressor Low Compression Limit 38 13 53 Compressor Starting Error 54 Compressor No Pump 18 High Differential Pressure Start...

Page 20: ...pressor Underspeed Shutdown 84 11 58 VFD Heat Sink Overtemp Shutdown 85 13 53 DC Under Voltage Shutdown 14 54 DC Over Voltage Shutdown 86 06 46 VFD Communication Error 87 13 53 VFD Initialization Erro...

Page 21: ...8 71 VFD Estimator Malfunction 4 hours 39 53 Fan Start Malfunction 4 hours 39 55 Unexpected Fan Shutdown Malfunction 4 hours 39 58 Fan Motor Malfunction 4 hours 53 41 OST Open Low Temp Duration of Eve...

Page 22: ...nal residential HVAC training resources that help strengthen careers and businesses We believe in providing high quality learning experiences both online and in the classroom Access My Learning Center...

Reviews: