background image

Wiring Diagram

24ACB7

Comfort

t

17 2---Stage Air Conditioner

with Puron

r

Refrigerant

1---1/2 to 5 Tons

 

NOTES:

1.   Symbols are electrical representation only.
2.   Compressor and fan motor furnished with inherent thermal protection.
3.   To be wired in accordance with National Electric N.E.C. and local codes.
4.   N.E.C. class 2, 24 V  circuit, min.  40 VA  required, 60 VA on units installed with LLS.
5.   Use copper conductors only.  Use conductors suitable for at least 75ºC (167ºF).
6.   Connection for typical cooling only thermostat.  For other arrangements see Installation
      Instructions.
7.   If indoor section has a transformer with a  grounded secondary,  connect the grounded 
      side to the BRN/YEL lead.
8.    When start relay and start capacitor are installed, start thermistor is not used.
9.    CH not used on all units.
10.    If any of the original wire, as supplied, must be replaced, use the same or equivalent wire.
11.   Check all electrical connections inside control box for tightness.
12.  Do not attempt to operate unit until service valves have been opened.
13.  Do not rapid cycle compressor.  Compressor must be off 3 minutes to allow pressures to
      equalize between high and low side before starting.

 * MAY BE FACTORY INSTALLED

LEGEND

FACTORY POWER WIRING

FACTORY CONTROL WIRING

FIELD CONTROL WIRING

FIELD POWER WIRING

CONDUCTOR ON CIRCUIT BOARD

COMPONENT CONNECTION

FIELD SPLICE

JUNCTION

PLUG RECEPTACLE

 

 

 

*CHS

COMP

CONT

CS

*CTD
*HPS

IFR

*LLS

*LPS
OFM

*SC
*SR

CRANKCASE HEATER SWITCH
COMPRESSOR
CONTACTOR
COMPRESSOR SOLENOID
COMPRESSOR TIME DELAY
HIGH PRESSURE SWITCH
INDOOR FAN RELAY
LIQUID LINE SOLENOID VALVE
LOW PRESSURE SWITCH
OUTDOOR FAN MOTOR
START CAPICATOR
START RELAY

1.  Compressor damage may occur if system is over charged.
2.  This unit is factory charged with R-410A in accordance with the amount shown 
      on the rating plate.  The charge is adequate for most systems using matched 
      coils and tubing not over 15 feet long. Check refrigerant charge for maximum 
      efficiency.  See Product Data Literature for required Indoor air Flow Rates and 
      for use of line lengths over 15 feet.
3.  Relieve pressure and recover all refrigerant before system repair or final 
     disposal.  Use all service ports and open all flow-control devices, including 
     solenoid valves.
4.  Never vent refrigerant to atmosphere.  Use approved recovery equipment.

CAUTION

 

CONDENSING UNIT CHARGING INSTRUCTIONS

For use with units using R-410A refrigerant

COOLING ONLY

CHARGING PROCEDURE

REQUIRED LIQUID LINE TEMPERATURE

Required Subcooling

Temperature  (ºF)

Liquid 

Pressure

at Service

Valve (psig)

6

8

10 12 14 16

251

259
266
274
283
291
299

308
317
326
335
345
354
364
374

76

74

72

70

68

78

76

74

72

70

80

78

76

74

72

82

80

78

76

74

84

82

80

78

76

86

84

82

80

78

88

86

84

82

80

90

88

86

84

82

92

90

88

86

84

94

92

90

88

86

96

94

92

90

88

98

96

94

92

90

100

98

96

94

92

102 100

98

96

94

104 102 100 98

96

384
395
406
416
427

439
450

462

474

106 104 102 100 98
108 106 104 102 100
110 108 106 104 102
112 110 108 106 104
114 112 110 108 106
116 114 112 110 108
118 116 114 112 110

120 118 116 114 112

122 120 118 116 114

78

80
82
84
86
88
90

92
94
96
98

100
102
104
106

108
110
112
114
116
118
120

122

124

1.  Only use subcooling charging method 
     when OD ambient is greater than 70ºF 
     and less than 100ºF, indoor temp is 
     greater than 70ºF and less than 80ºF, 
     and line set is less than 80 ft.
2.  Operate unit a minimum of 15 minutes 
     before checking the charge.
3.  Measure liquid service valve pressure
     by attaching an accurate gauge to the 
     service port.
4.  Measure the liquid line temperature by 
     attaching an accurate thermistor type 
     or electronic thermometer to the
     liquid line near the outdoor coil.
5.  Refer to unit rating plate for required 
     subcooling temperature.
6.  Find the point where the required 
     subcooling temperature intersects the 
     measured liquid service valve pressure.
7.  To obtain the required subcooling 
     temperature at specific liquid line 
     pressure, add refrigerant if liquid line
     temperature is higher than indicated.  
     When adding refrigerant, charge in 
     liquid form using a flow restricting 
     device into suction service port.  
     Recover refrigerant if temperature is 
     lower. Allow a tolerance  of +/- 3ºF.

CAP

*CH

CAPACITOR 
CRANKCASE HEATER

CONNECTION  DIAGRAM

COMP

OFM

S

C

R

BRN

BLK

YEL

BLK

YEL

RED or BLK

208/230 1Ø

POWER

SUPPLY

EQUIP  GND

L1

L2

CAP

H

C

F

YEL

BLU

YEL

*SC

*CHS

*SR

(NOTE #8)

1

2

5

*CH

BLK

BLK

or

RED

BLK

BRN

(NOTE #9)

BLK

INDOOR BLOWER MOTOR

EXTERNAL

POWER 
SUPPLY

24 V

(NOTE #3)

INDOOR THERMOSTAT  (NOTE #6)

R

G

Y1

*LLS

BLK

BLK

C
R

VIO

BRN/YEL

*LPS

*HPS

LOGIC

T1

*CTD

BLK

 BLU/PNK

T3

T2

SCHEMATIC DIAGRAM  (LADDER FORM)

L1

*CH

EQUIP

GND

*SR

*SC

H

C

F

CAP

OFM

L2

5

2

1

*HPS

* CTD

*LLS

IFR

INDOOR THERMOSTAT

Y1

G

R

C

R

EXTERNAL POWER SUPPLY 24 V

LOGIC

T1

T3

T2

CONT

COMP

S

C

R

*CHS

*LPS

CONT

11

21

23

23

11

21

CONT

CONT

23

23

YEL/ PNK

YEL/ PNK

 BLU/PNK

Y2

CS

BLU

RED

CS

Y2

C

C

BLU

336323-101 R E V .  B

Fig. 1 – Wiring Diagram — Model sizes 2 -- 5 tons, 208/230--1

Reviews: