![Carrier 124ANS40MKQB Service Manual Download Page 3](http://html1.mh-extra.com/html/carrier/124ans40mkqb/124ans40mkqb_service-manual_2560414003.webp)
3
STANDARD FEATURES AND ACCESSORIES
Table 1—Standard Features
Ease Of Installation
Indoor and Outdoor Compact Size
S
Outdoor Unit Wall Mounting Kit
A
Outdoor Unit Stacking Kit
A
Indoor Mounting Bracket
S
Comfort Features
Microprocessor Controls
S
Wireless Remote Control
S
Automatic Air Sweep
S
Air Direction Control
S
Auto Restart Function
S
Cold Blow Protection On Heat Pumps
S
Turbo Mode
S
Silence Mode
S
Follow Me
S
Energy Saving Features
Sleep Mode
S
Stop/Start Timer
S
46
°
F Heating Mode (Heating Setback)
S
Safety And Reliability
3 Minute Time Delay For Compressor
S
Over Current Protection For Compressor
S
Crankcase Heater (standard on size 30 Heat Pump)
A
Indoor Coil Freeze Protection
S
Indoor Coil High Temperature Protection On Heat Pumps
S
Condenser High Temperature Protection On Heat Pumps
S
Accumulator On Heat Pumps
S
Ease Of Service And Maintenance
Cleanable Filters
S
Diagnostics
S
Liquid Line Pressure Taps
S
Suction And Discharge Pressure Taps
S
Application Flexibility
Low Ambient Controls (--20
_
F) (--28.9
_
C)
A
3--Phase on size 32 (Cooling Only)
S
Wind Baffles
A
Condensate Pumps
A
Wired Controls
A
Legend
S Standard
A Accessory
Table 2—Accessories
Part Number
Description
For Models
KSACN0101AAA
Wired Remote Control
Only Sizes 18, 22
53DS--900------118
Condensate Pump (230v)
All Sizes
KAAVC0101AAA
Controls Kit (Required on High Walls
Cooling Only units)
40MKC
KHAVC0101AAA
Controls Kit (Required on High Walls
Heat Pump units)
40MKQ
KSALA0801AAA
Low Ambient Control (for cooling --20F)
24AHA4/25HHA4
/124ANS/224ANS (208/230V)
KSALA0901AAA
Low Ambient Control (for cooling --20F)
24AHA4 /124ANS (460V--3)
KAACH1401AAA
Crankcase Heater
24AHA4/124ANS Sizes 18--36
(208/230V)
KAACH1501AAA
Crankcase Heater
24AHA4/124ANS Size 36
(460V--3)
KAACH1701AAA
Crankcase Heater
25HHA4/224ANS Size 24
(208/230V)
KAAWS0101AAA
Winter Start Kit (for low ambient on
cooling only systems)
24AHA4/124ANS All Sizes
KHAIR0201AAA
Isolation Relay (Required when using
Low Ambient cooling with HP)
25HHA4/224ANS All Sizes
KSAHS1501AAA
Hard Start Kit (Capacitor & Relay)
24AHA4/25HHA4
/124ANS/224AN S (208/230V--1)
53DS--900------087
Wind Baffle
24AHA4/124ANS Sizes 18 & 24;
25HHA4/224ANS Size 24
53DS--900------071
Wind Baffle
24AHA4/124ANS Sizes 30 -- 36;
25HHA4/224ANS Size 30
53DS--900------075
Stacking Kit
24AHA4/124ANS Sizes 18, 24
53DS--900------076
Stacking Kit
24AHA4/124ANS Sizes 30, 36
53DS--900------077
Wall Mount Kit
24AHA4/25HHA4/124ANS/224A
NS Sizes 18, 24
53DS--900------078
Wall Mount Kit
24AHA4/25HHA4
/124ANS/224ANS Sizes 30, 36
KAALS0201LLS
Liquid Line Solenoid for Cooling Only
24AHA4/124ANS All Sizes --
Required for Long Line
Applications
KHALS0401LLS
Liquid Line Solenoid for Heat Pump
25HHA4 /224ANS All Sizes --
Required for Long Line
Applications
INDOOR UNIT ACCESSORIES
Condensate Pump
A07892
Fig. 1 – Condensate Pump Accessory
On high wall fan coils, the condensate pump has a lift capability of
12 ft (3.6 m) on the discharge side with the pump mounted in the
fan coil or 6 ft (1.8 m) on the suction side if the pump is remote
mounted. The pump is recommended when adequate drain line
pitch cannot be provided, or when the condensate must move up to
exit.
Wired Remote Controller
For applications where the use of wireless remote control is not
desired, the MK units can be controlled by means of a wired
wall--mounted control with an LCD display.
Fig. 2 – Wall Mounted Control with LCD Display