See the 09FC pressure drop Fig. 25-27 for reference. The
09FC020, 09FC030, and 09FC040 are shown. Larger units are
combinations of these piping systems. Combine pressures for
larger systems. Add pressures for series configuration. For par
-
allel configurations, combine the pressure drop for each using
the equation Rt=R1*R2/(R1+R2). Rt equals the equivalent
pressure drop which R1 and R2 are the individual circuits.
Curves are for 30% Propylene Glycol (PG). Use multipliers for
other fluids or brine concentration amounts.