
: Service Manual
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
24
A95422
Fig. 25 – Electronic Leak Detection
Assuming that a system is pressurized with either all refrigerant or a
mixture of nitrogen and refrigerant, leaks in the system can be found
with an electronic leak detector that is capable of detecting specific
refrigerants.
If system has been operating for some time, first check for a leak
visually. Since refrigerant carries a small quantity of oil, traces of oil at
any joint or connection is an indication that refrigerant is leaking at that
point.
A simple and inexpensive method of testing for leaks is to use soap
bubbles. (See
.) Any solution of water and soap may be used.
Soap solution is applied to all joints and connections in system. A small
pinhole leak is located by tracing bubbles in soap solution around leak. If
the leak is very small, several minutes may pass before a bubble will
form. Popular commercial leak detection solutions give better,
longer-lasting bubbles and more accurate results than plain soapy water.
The bubble solution must be removed from the tubing and fittings after
checking for leaks as some solutions may corrode the metal.
A95423
Fig. 26 – Bubble Leak Detection
You may use an electronic leak detector designed for specific refrigerant
to check for leaks. (See
.) This unquestionably is the most
efficient and easiest method for checking leaks. There are various types
of electronic leak detectors. Check with manufacturer of equipment for
suitability. Generally speaking, they are portable, lightweight, and
consist of a box with several switches and a probe or sniffer. Detector is
turned on and probe is passed around all fittings and connections in
system. Leak is detected by either the movement of a pointer on detector
dial, a buzzing sound, or a light.
In all instances when a leak is found, system charge must be recovered
and leak repaired before final charging and operation. After leak testing
or leak is repaired, replace liquid line filter drier, evacuate system, and
recharge with correct refrigerant quantity.
Coil Removal
Coils are easy to remove if required for compressor removal, or to
replace coil.
1. Shut off all power to unit.
2. Recover refrigerant from system through high flow service valves.
3. Break vacuum with nitrogen.
4. Remove top cover. (See Access Compressor or other internal
.)
5. Remove screws in coil panels.
6. Use midget tubing cutter to cut liquid and vapor lines at both sides
of coil. Cut in convenient location for easy reassembly with copper
slip couplings.
7. Lift coil vertically from basepan and carefully place aside.
8. Reverse procedure to reinstall coil.
9. Replace filter drier, evacuate system, recharge, and check for
normal systems operation.
Compressor Removal and Replacement
Once it is determined that compressor has failed and the reason
established, compressor must be replaced.
1. Shut off all power to unit.
2. Remove and recover all refrigerant from system until pressure
gauges read 0 psig. Use all service ports. Never open a system
under a vacuum to atmosphere. Break vacuum with dry nitrogen
holding charge first. Do not exceed 5 psig.
3. Disconnect electrical leads from compressor. Disconnect or remove
crankcase heater and remove compressor hold-down bolts.
4. Cut compressor from system with tubing cutter. Do not use brazing
torch for compressor removal. Oil vapor may ignite when
compressor is disconnected.
5. Scratch matching marks on stubs in old compressor. Make
corresponding marks on replacement compressor.
6. Use torch to remove stubs from old compressor and to reinstall
them in replacement compressor.
7. Use copper couplings to tie compressor back into system.
WARNING
!
PERSONAL INJURY AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death.
Due to the high pressure of nitrogen, it should never be used without a
pressure regulator on the tank.
BEEP
BEEP
LEAK
DETECTOR
SOLUTION
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal injury or
equipment damage.
Cut tubing to reduce possibility of personal injury and fire.
CAUTION
!
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
Turn off all power to unit before proceeding. Lock out and tag switch
with suitable warning label. Wear safety glasses, protective clothing,
and gloves when handling refrigerant. Acids formed as a result of
motor burnout can cause burns.
CAUTION
!
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
Wear safety glasses, protective clothing, and gloves when handling
refrigerant and when using brazing torch.