Installation Instructions

Part No. 00EFN900044000A, 00EFN900005600A

SAFETY CONSIDERATIONS

Installation of this accessory can be hazardous due to system pres-

sures, electrical components, and equipment location (such as a

roof or elevated structure).
Only trained, qualified installers and service mechanics should in-

stall, start up, and service this equipment.
When installing this accessory, observe precautions in the litera-

ture, labels attached to the equipment, and any other safety precau-

tions that apply.

• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use care in handling and installing this accessory. 

PACKAGE CONTENTS (00EFN900044000A)

*Connector comes wired to the thermistor.

NOTE: Accessory 00EFN900044000A is used with 30RB060-300,
30XA080-501 fixed speed, 30XW150-400 and 30XV140-500 units.
30XA fixed speed units are identified by a number in the 9th position of
the model number; for example, 30XAB200

6

-------.

PACKAGE CONTENTS (00EFN900005600A)

*Connector comes wired to the thermistor.

NOTE: Accessory 00EFN900005600A is used for 30XA140-352 vari-
able speed units only. These units are identified by a letter in the 9th
position of the model number; for example, 30XAB200

F

-------.

GENERAL

These instructions cover installation of the dual chiller thermistor

accessory. If two chillers are installed in parallel, additional chilled

water sensors (one for each chiller) must be installed in the com-

mon leaving water piping. The accessory kit contains the required

thermistors, wells, and wiring connectors. This accessory is not re-

quired for chillers piped in series.

INSTALLATION (00EFN900044000A)

To prepare the chillers for parallel operation, perform the follow-

ing procedure:
1. Lock out and tag all disconnects.
2. Determine the location for the thermistor wells. The well loca-

tions must be in the common leaving water header. See Fig 1.
DO NOT relocate the chiller’s leaving water thermistors. They

must remain in place for the unit to operate properly.

3. Install the thermistor wells. The thermistor well is a 

1

/

4

 in.

NPT fitting. See Fig. 2. Select a location that will allow for

removal of the thermistor without any restrictions. Installa-
tion method will depend on the type of piping.

4. Insert the thermistors into the wells until the O-rings on the

thermistors reach the well body. Use the nut on the thermis-
tors to secure the thermistors in place.
It is recommended that a small amount of heat compound

(such as Dow Corning 340 Heat Sink Compound) be inserted

with the thermistor for better heat transfer.

5. Once the thermistors are in place, it is recommended that a

wire loop be made and secured with a wire tie to the chilled
water pipe. This will provide strain relief. See Fig. 3.

6. The wiring connector (part no. HY06AM016) comes

attached to the thermistor lead. Run connector wiring to the
chiller control box of the master and slave chillers. Plug the

connectors into MBB-J6 CH-3 on the main base board. For

30RB060-300, 30XA080-501 fixed speed and 30XW150-
400 units. See Fig. 4. For 30XV140-500 plug the connectors

into SIOB-B J-25 (AI-03). See Fig. 5.

7. Restore power to unit.
NOTE: For 30RB315-300 units, as well as all units using the dual

chiller algorithm, a Carrier Comfort Network

®

 (CCN) bus must be

connected between the two modules.

INSTALLATION (00EFN900005600A)

To prepare the chillers for parallel operation, perform the follow-

ing procedure:
1. Lock out and tag all disconnects.
2. Determine the location for the thermistor wells. The well loca-

tions must be in the common leaving water header. See Fig 1.
DO NOT relocate the chiller’s leaving water thermistors. They

must remain in place for the unit to operate properly.

3. Install the thermistor wells. The thermistor well is a 

1

/

4

 in.

NPT fitting. See Fig. 2. Select a location that will allow for

removal of the thermistor without any restrictions. Installa-

tion method will depend on the type of piping.

WARNING

Electrical shock can cause personal injury and death. Shut off

all power to this equipment during installation. There may be

more than one disconnect switch. Tag all disconnect locations

to alert others not to restore power until work is completed.

ITEM

PART NO.

QUANTITY

Thermistor

00PPG000008106A

2

Well

00PPG000008000A

2

Connector*

HY06AM016

2

ITEM

PART NO.

QUANTITY

Thermistor

00PPG000008106A

2

Well

00PPG000008000A

2

Connector*

HY84EE004

2

AUX 1 Board

CEPLP130567-02-SA

2

CB4

HH83ZB010

2

Harness

00PPN500011200A

2

30RB060-300, 30XA Fixed Speed 080-501,

30XA Variable Speed 140-352, 30XW150-400,

30XV140-500

Dual Chiller Thermistor Accessory

Summary of Contents for 00EFN900044000A

Page 1: ... 2 Select a location that will allow for removal of the thermistor without any restrictions Installa tion method will depend on the type of piping 4 Insert the thermistors into the wells until the O rings on the thermistors reach the well body Use the nut on the thermis tors to secure the thermistors in place It is recommended that a small amount of heat compound such as Dow Corning 340 Heat Sink ...

Page 2: ...itch settings on Aux Board 1 refer to Fig 6 for location should be set as follows 8 Install circuit breaker CB 4 inside power box on bracket as shown in Fig 8 Using wiring harness part no 00PPN500011200A connect power from CB 4 to Aux Board 1 J1 at location shown in Fig 6 Neatly route wiring harness so wiring is protected from damage 9 Using the accessory supplied wiring harness part no 00PPN50001...

Page 3: ...1 195 195 195 195 195 195 195 CH1 CH2 CH3 CH4 CH11 CH12 CONNECTOR HY06AM016 INSTALLATION LOCATION CH13 CH14 CH 15A J4 ANALOG INPUTS J3 J2C J2B J15 J1A J9D G DISCRETE INPUTS J5A C 16A CH 15B C C CH16B 11 C16 J2A TR1 TR2 TR3 TR4 TR5 CH19 CH20 CH21 CH22 CH23 CH24 CH25 CH26 J8 CH17 CH18 J5B J5C CH5 CH6 CH7 CH8 CH9 J7A J7B J7C J7D RELAY OUTPUTS MOV1 C41 C42 C43 C32 C33 C34 C35 12 11 12 11 J10 19 J12 J1...

Page 4: ...4 Fig 5 SIOB B CONNECTOR HY06AM016 INSTALLATION LOCATION ...

Page 5: ... CH11 CH12 JP2 C61 CH13 D12 JP1 L3 L5 U21 L2 D6 D5 Q5 Y1 D7 D8 S1 D3 U1 Q1 U5 U6 U7 U8 U9 Q10 Q11 U10 J4 J3 J2 U4 U2 Q12 Q60 3 2 1 G 3 2 1 G DIP SWITCH J5 J6 J7 J8 POWER FROM CB 4 CONNECTS HERE CONNECT LEN WIRING HARNESS 00PPN500011200A HERE a30 5941 THERMISTOR CONNECTOR HY84EE004 INSTALLATION LOCATION Fig 6 AUX Board NOTE Applies only to 30XA140 352 variable speed units ...

Page 6: ...rd Location Fig 8 CB 4 Location POWER BOX RIGHT INSIDE VIEW AUX BOARD 1 MOUNTING LOCATION a30 5939 NOTE Applies only to 30XA140 352 variable speed units a30 5940 NOTE Applies only to 30XA140 352 variable speed units ...

Page 7: ......

Page 8: ... right to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53300215 01 Printed in U S A Form 30 37SI Pg 8 8 19 Replaces 30 25SI Carrier Corporation 2019 ...

Reviews: