PLAN INSTALLATION (cont.)
MOUNTING OPTIONS
CONVERTING FROM RIGHT-ANGLE TO IN-LINE
Remove and reverse duct flanges and access panel
positions on housing.
For correct intake and exhaust duct size, see Table 1.
TABLE 1
ACCESS
PANEL
INTAKE DUCT
FLANGES
EXHAUST
DUCT FLANGE
EXHAUST
DUCT FLANGE
Typical mounting with threaded rod through
mounting channels on top of housing.
3/8” MIN.
THREADED RODS
(By Others)
DIM. VCDD210
I
VCDD330
I
C
12-5/8”
12-5/8”
D
39-5/8”
47-3/8”
Mounting with threaded rod through adjustable
mounting brackets located at top of housing.
3/8” MIN. THREADED RODS
(By Others)
DIM. VCDD210
I
VCDD330
I
A
7-3/4”
10-1/4”
B
33-3/4”
41-3/4”
Mounting with threaded rods through adjustable
mounting brackets located at bottom of housing.
Mounting brackets can be bolted to housing ends in a variety of
configurations. Use screws and nuts provided in parts bag.
If installing unit as a ceiling ventilator, make sure that either duct
flanges or housing will be flush with finished ceiling. Duct flanges
may be removed and discarded if they interfere with a ceiling instal-
lation.
MOUNTING OPTIONS
MODEL
INTAKE DUCT SIZE EXHAUST DUCT SIZE
VCDD210
I
12-3/8” x 35-3/4”
7-3/4” x 33-3/4”
VCDD330
I
14-1/2” x 43-1/2”
9-3/4” x 41-3/8”
Provide solid support to minimize sound leves. There are two basic
mounting methods for these units.
Carnes VCDD210I-330I Inline Cabinet Fan
Operation & Instructions Manual
MODELS • VCDD210
I
• VCDD330
I
Page 2
®
PLAN INSTALLATION (cont.)
MOUNTING OPTIONS
CONVERTING FROM RIGHT-ANGLE TO IN-LINE
Remove and reverse duct flanges and access panel
positions on housing.
For correct intake and exhaust duct size, see Table 1.
TABLE 1
ACCESS
PANEL
INTAKE DUCT
FLANGES
EXHAUST
DUCT FLANGE
EXHAUST
DUCT FLANGE
Typical mounting with threaded rod through
mounting channels on top of housing.
3/8” MIN.
THREADED RODS
(By Others)
DIM. VCDD210
I
VCDD330
I
C
12-5/8”
12-5/8”
D
39-5/8”
47-3/8”
Mounting with threaded rod through adjustable
mounting brackets located at top of housing.
3/8” MIN. THREADED RODS
(By Others)
DIM. VCDD210
I
VCDD330
I
A
7-3/4”
10-1/4”
B
33-3/4”
41-3/4”
Mounting with threaded rods through adjustable
mounting brackets located at bottom of housing.
Mounting brackets can be bolted to housing ends in a variety of
configurations. Use screws and nuts provided in parts bag.
If installing unit as a ceiling ventilator, make sure that either duct
flanges or housing will be flush with finished ceiling. Duct flanges
may be removed and discarded if they interfere with a ceiling instal-
lation.
MOUNTING OPTIONS
MODEL
INTAKE DUCT SIZE
EXHAUST DUCT SIZE
VCDD210
I
12-3/8” x 35-3/4”
7-3/4” x 33-3/4”
VCDD330
I
14-1/2” x 43-1/2”
9-3/4” x 41-3/8”
Provide solid support to minimize sound leves. There are two basic
mounting methods for these units.
Carnes VCDD210I-330I Inline Cabinet Fan
Operation & Instructions Manual