PROGRAMMING WM30-96

Key-pad

NOTE

CARLO GAVAZZI

A u t o m a t i o n   C o m p o n e n t s

7

Push for at

least 2 s

10 CHANGE PAS

: this function allows the user to modify the PASS value

with a new value (from 0 to 1000). 

20 BACKLIGHT:

backlight time from 0 (always on) to 255 minutes. 

30 MODULES:

the WM30 96 does not support the automatic ackno-

wledgment of the installed modules, therefore this information must be
entered using the “MODULES” menu.

40 APPLICAT.:

this function which enables a simple, quick, clear and

immediate visualization of the instrument measurements, making available
only specific variables (page 4/5) depending on the application of the
instrument.

50 SYSTEM:

this function allows the user to select the type of

electrical system. 

60 CT RATIO:

this function allows the user to select the

value of the CT ratio (primary/secondary ratio of the current transformer
being used). Example: if the CT primary (current transformer) has a current
of 300A and the secondary a current of 5A, the CT ratio corresponds to 60
(obtained using the following calculation: 300/5.  

70 PT RATIO:

this function allows you to select the value of the VT-PT ratio

(primary/secondary ratio of the voltage transformer being used). Example:

if the primary of the connected VT (voltage transformer) is 20kV and the
secondary is 100V, then the VT-PT ratio corresponds to 200 (obtained car-
rying out the following calculation: 20000/100). 

80 DMD:

This function allows the user to select the calculation method of

the DMD/AVG value of the selected variable. 81 TYPE: select the type of
calculation mode to be used for the DMD/AVG calculation FIXED: if, for
example, a time interval of 15 minutes has been selected, the instrument
will calculate the AVD/DMD value of the measured variable and updates its
value every 15 minutes. SLIDE: if for example a time interval of 15 minu-
tes has been selected, the instrument calculates the AVG/DMD value and
updates its value at the beginning after the first 15 values and then after
every minute, thus generating a window whose width is of 15 minutes and
that moves forward every minute. 82 TIME: select the time interval for the
DMD/AVG calculation 83 SYNC: select the synchronization mode, that is
the method that controls the calculation method of the average/demand
according to the selected time. 

90 SET POWER:

This menu allows you to set a power value (installed power)

that, in the measuring phase, will represent 100% of the graph indicator. 

100 HOME PAGE:

This function allows the user to select the variables to

be displayed on first page (home page). 101 TYPE: A, you can select the
variable for each row. B, you can select a preset combination of variables. 

110 FILTER:

Thanks to the digital filter, it’s possible to stabilize the mea-

surements which are too instable when displaying the relevant values. 111
FILTER S: set the operating range of the digital filter. The value is expres-
sed as a %. 112 FILTER CO: set the filtering coefficient of the instantane-
ous measures. By increasing the value, also the stability and the settling

time of the measures are increased

.

Some specific menus display only if the relevant modules are instal-

led
*

Self-recognize.

Measuring

mode

Page 9

See details on the next
page.

Summary of Contents for WM30 96

Page 1: ...Instruction Manual Display Programming Modular system Class 0 2 A V...

Page 2: ...ogical answer to your needs of power quality analysis Moreover you can count on a ISO9001 VISION 2000 certified company structure an experi ence of many years and a wide spread pres ence both in Europ...

Page 3: ...s programming Up button enables to browse the menus and to increase the values to be set Down button enables to browse the menus and to decrease the values to be set Access to the programming menu hol...

Page 4: ...nd of the multiplier k M V W A var VAr PF Pf Hz An ALR the alarm display function is active PROG the programming function is active Area dedicated to the visualization of counters text messages date a...

Page 5: ...plication G which enables a complete and detailed analysis of the electric energy 4 Selection Application Note A Cost allocation Imported energy metering B Cost control Imported and partial energy met...

Page 6: ...x x x x x 6 kvarh part x x x x x 7 kWh part x x x 8 kvarh part x x x 9 Run Hours 99999999 99 x x x x x 10 Phase seq VLN VL1 VL2 VL3 x x x x 11 Phase seq VLN VL1 2 VL2 3 VL3 1 x x x x 12 Phase seq An A...

Page 7: ...x x x x 5 PULSE out2 text kWh kvarh xxxx kWh kvarh per pulse tot PAr x x x x x x x 6 Remote out out1 text on oFF Out2 text on oFF x x x x x x x 7 Alarm 1 nE nd None out 1 out 2 Set 1 Set 2 measurement...

Page 8: ...selected variable 81 TYPE select the type of calculation mode to be used for the DMD AVG calculation FIXED if for example a time interval of 15 minutes has been selected the instrument will calculate...

Page 9: ...var1 VA1 PF1 Hz E D 0 1 2 3 4 5 6 7 8 9 10 11 Row 2 V LN V LN An Hz VA var W PF Row 3 V LN V L1 2 A L1 ASY VA L1 var L1 W L1 PF L1 THD V1 THD V12 THD A1 Row 4 V L2 V L2 3 A L2 VLL sys asy VA L2 var L...

Page 10: ...al output 181 FUNCTION Alarm the digital output is enabled only if the expected alarm status occurs Pulse the measured energy is retransmitted by the digital output by means of pulses Remote the digit...

Page 11: ...the variable input range to which the MAX OUT value retransmitted by the analog output will be coupled 220 METERS reset the ENERGY METERS choosing among TOTAL PARTIAL resets all energy meters both to...

Page 12: ...N rated current 5A for the AV5 type input CT primary secondary ratio of the voltage transformer being used in this example 400 1 5 60 3 360kW The RANGE parameter representing the digital filtering coe...

Page 13: ...VT and CT values Retransmission of the POWER FACTOR PF by means of the 0 20mA analog output It s necessary to retransmit the whole range of the admitted values for the PF with a signal from 0 to 20mA...

Page 14: ...load when a set value of absorbed power is required For example when 300kW are exceeded the alarm occurs and a set load is disconnected An UP alarm is selected Below you ll find the recommended progr...

Page 15: ...www GavazziOnline com...

Reviews: