Motor Controllers AC Variable Frequency Drives
RVBS
Specifications are subjected to change without notice.10/08/2021
18
-
Rated voltage at base frequency (F05)
Set "0" or the rated voltage printed on the nameplate labeled on the motor.
➢
If "0" is set, the rated voltage at base frequency is determined by the power source of the inverter. The
output voltage will vary in line with any variance in input voltage.
➢
If the data is set to anything other than "0," the inverter automatically keeps the output voltage constant in
line with the setting. When slip compensation function is active, the voltage settings should be equal to the
rated voltage of the motor.
-
Maximum Output Voltage (F06)
Set the voltage for the maximum frequency 1 (F03).
➢
If F05 (Rated Voltage at Base Frequency 1) is set to "0," settings of F06 do not take effect.
< Output voltage & frequency defined via F03 to F06 >
Function
Code
Mod.
add.
Description
Def
Min
Max
U.M.
R/W
F03
0x0003
Maximum Frequency 1
900
250
1200
0.1Hz
R/W
F04
0x0004
Base Frequency 1
500
250
1200
0.1Hz
R/W
F05
0x0005
Rated Voltage at Base Frequency
1
0
0
500
Vrms
R/W
F06
0x0006
Maximum Output Voltage 1
230
80
500
Vrms
R/W
4.2.2
Torque boost setting
F32 specifies V/f pattern, torque boost type for optimizing the operation in accordance with the characteristics
of the load. F30 specifies the type of torque boost in order to provide sufficient starting torque.
Data for F32
V/f pattern
Torque boost (F30)
Applicable load
0
Variable torque
V/f pattern
Torque boost
specified by F30
Variable torque load (General purpose
fans and pumps)