&RQ¿JXUHWKHV\VWHP
EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA
Settings from EM24 E1
General settings
7KHDYDLODEOHVHWWLQJVGHSHQGRQWKHDSSOLFDWLRQVHW
Page title
Sub-menu
Description
Values
Default value
Cng PASS
-
Change password
From 0 to 9999
0
APPLiCAt
Application
tYP.A
tYP.b
tYP.C
tYP.d
tYP.E
tYP.F
tYP.G
tYP.H
tYP.H
User
USEr 1
User
From 0 to 9999
1
USEr 2
From 0 to 9999
2
USEr 3
From 0 to 9999
3
dHCP
-
DHCP enabling
oFF/on
oFF
IP Addr
IP o.-.-.-
IP address
From 000 to 255
192
IP -.o.-.-
From 000 to 255
168
IP -.-.o.-
From 000 to 255
1
IP -.-.-.o
From 000 to 255
10
SUb
SUb o.-.-.-
Subnet mask
From 000 to 255
255
SUb -.o.-.-
From 000 to 255
255
SUb -.-.o.-
From 000 to 255
255
SUb -.-.-.o
From 000 to 255
0
GAtE
GAtE o.-.-.-
Default gateway
From 000 to 255
192
GAtE -.o.-.-
From 000 to 255
168
GAtE -.-.o.-
From 000 to 255
1
GAtE -.-.-.o
From 000 to 255
1
Port
-
MODBUS TCP port
502
SELECtor
SELEC. 1
Page displayed according to selector
position among the available pages for
each application (see”Frontal selector”
on page 15)
From 1 to 28
1
SELEC. 2
From 1 to 28
25
SELEC. 3
From 1 to 28
28
SELEC.LoC
From 1 to 28
3
SYS
-
System
3P.n
3P.1
2P
1P
3P
Note:
MID (PFA, PFB): only 3P.n
3P.n
Ut rAtio
-
Voltage transformer ratio (VT)
AV5: from 1 to 6975
AV2: N/A
1
Ct rAtio
-
Current transformer ratio (CT)
AV5: from 1 to 6975
AV2: N/A
1
P int.ti
-
Dmd integration time (min)
From 1 to 30
15
FiLtEr.S
-
,QWHUYDORI¿OWHULQWHUYHQWLRQZLWKUHVSHFW
to full scale (%)
From 0 to 100
2
FiLtEr.Co
-
)LOWHUFRHI¿FLHQW
From 1 to 32
2
End
-
Exit and save
-
-
Note:
the
Ut rAtio
is available for compatibility with other versions, even though the AV5 version is not meant to be used with voltage transformers. It should
be therefore set to 1.